0 |
Model |
1 |
.1f |
2 |
4.2f |
3 |
A000: Undefined |
4 |
A001: EEPROM Error (CP) |
5 |
A002: RAM Error (CP) |
6 |
A003: No Sensor Response |
7 |
A004: Temperature Overrange |
8 |
A005: Mass Flow Rate Overrange |
9 |
A006: Characterization Required |
10 |
A007: Real-Time Interrupt Failure |
11 |
A008: Density Overrange |
12 |
A009: Transmitter Initializing/Warming Up |
13 |
A010: Calibration Failure |
14 |
A011: Zero Calibration Failed: Low |
15 |
A012: Zero Calibration Failed: High |
16 |
A013: Zero Calibration Failed: Unstable |
17 |
A014: Transmitter Failure |
18 |
A015: MA Readback Error |
19 |
A016: Sensor RTD Failure |
20 |
A017: T-Series RTD Failure |
21 |
A018: EEPROM Error (Xmtr) |
22 |
A019: RAM Error (Xmtr) |
23 |
A020: No Flow Cal Value |
24 |
A021: No K1 Value |
25 |
A022: Config DB Corrupt (CP) |
26 |
A023: Internal Totals Corrupt (CP) |
27 |
A024: Program Corrupt (CP) |
28 |
A025: Boot Sector Fault (CP) |
29 |
A026: Sensor/Xmtr Comm Failure |
30 |
A027: Security Breach |
31 |
A028: CP Write Failure |
32 |
A029: PIC/Daughterboard Comm Failure |
33 |
A030: Incorrect Board Type |
34 |
A031: Low Power |
35 |
A032: SMV: Outputs Fixed |
36 |
A033: No LPO/RPO Signal |
37 |
A034: Smart Meter Verification Failed |
38 |
A035: Smart Meter Verification Aborted |
39 |
A036: Undefined |
40 |
A037: Undefined |
41 |
A038: Undefined |
42 |
A039: Undefined |
43 |
A100: MAO1 Saturated |
44 |
A101: MAO1 Fixed |
45 |
A102: Drive Overrange |
46 |
A103: Data Loss Possible |
47 |
A104: Calibration-In-Progress |
48 |
A105: Two-Phase Flow |
49 |
A106: Burst Mode Enabled |
50 |
A107: Power Reset Occurred |
51 |
A108: Single-SP Event 1 ON |
52 |
A109: Single-SP Event 2 ON |
53 |
A110: FO Saturated |
54 |
A111: FO Fixed |
55 |
A112: Upgrade Transmitter Software |
56 |
A113: MAO2 Saturated |
57 |
A114: MAO2 Fixed |
58 |
A115: No External Data |
59 |
A116: API: Temperature Overrange |
60 |
A117: API: Density Overrange |
61 |
A118: DO1 Fixed |
62 |
A119: DO2 Fixed |
63 |
A120: ED: Curve Fit Failure |
64 |
A121: ED: Extrapolation Alert |
65 |
A122: DO3 Fixed |
66 |
A123: DO4 Fixed |
67 |
A124: FI Saturated |
68 |
A125: Batch Timeout |
69 |
A126: Batch Overrun |
70 |
A127: Batch No Reset |
71 |
A128: Batch/Fill No Start |
72 |
A129: PPI Display Error |
73 |
A130: Printer Out of Paper |
74 |
A131: SMV in Progress |
75 |
A132: Sensor Simulation Active |
76 |
A133: PIC UI EEPROM Error |
77 |
A134: PPI Memory Error |
78 |
A135: PPI Communication Error |
79 |
A136: Undefined |
80 |
A137: Undefined |
81 |
A138: Undefined |
82 |
A139: Undefined |
83 |
D1 Calibration in Progress |
84 |
D2 Calibration in Progress |
85 |
D3 Calibration in Progress |
86 |
D4 Calibration in Progress |
87 |
FD Calibration in Progress |
88 |
Zero Calibration in Progress |
89 |
Temperature Slope Calibration in Progress |
90 |
Temperature Offset Calibration in Progress |
91 |
Discrete Event 1 Active |
92 |
Discrete Event 2 Active |
93 |
Discrete Event 3 Active |
94 |
Discrete Event 4 Active |
95 |
Discrete Event 5 Active |
96 |
Discrete Output 1 Active |
97 |
Discrete Output 2 Active |
98 |
Discrete Output 3 Active |
99 |
Discrete Input 1 Active |
100 |
Discrete Input 2 Active |
101 |
Flow Rate Switch Active |
102 |
Undefined |
103 |
Live Zero Flow Rate |
104 |
Core Processor Input Voltage |
105 |
Present MAO Gauge |
106 |
Present Freq Gauge |
107 |
Smart Meter Verification Results |
108 |
Time in Seconds |
109 |
Left and Right Pickoff Stiffness |
110 |
% |
111 |
mA Output Trim |
112 |
Resets all totalizers. |
113 |
Resets mass flow totalizer. |
114 |
Resets volumne flow totalizer. |
115 |
Read Modbus Data |
116 |
Write Modbus Data |
117 |
Smart Meter Verification |
118 |
Starts Smart Meter Verification and shows the result PASS or FAIL. This procedure takes upto 4 minutes. |
119 |
Most Recent Test Results |
120 |
Configure the transmitter for sensor characteristics. |
121 |
Configure channels, inputs, outputs, map variables, and communication settings. |
122 |
Special Units |
123 |
Configure the parameters required to convert an existing measurement unit to a different unit. |
124 |
External Pressure/Temperature |
125 |
Configure the transmitter to accept external input from polled pressure and/or temperature devices. |
126 |
Configure the transmitter for gas standard volume measurement. |
127 |
Map variables to the Primary Variable (PV), Secondary Variable (SV), Third Variable (TV), and Fourth Variable (QV). |
128 |
No Additional Information for Above |
129 |
Additional Information for Above |
130 |
A032: Smart Meter Verification in Progress: Outputs Fixed |
131 |
A104: Calibration in Progress |
132 |
A131: Smart Meter Verification in Progress |
133 |
Start |
134 |
Turn Off Schedule |
135 |
Turn off the Smart Meter Verification scheduler. |
136 |
Setup |
137 |
A034: Smart Meter Verification Failed |
138 |
A035: Smart Meter Verification Aborted |
139 |
LD Optimization |
140 |
Configure the transmitter for LD optimization. LD optimization is used only with large sensors in hydrocarbon applications. |
141 |
Show Last 20 Results |
142 |
Device Reset |
143 |
Restore Factory Configuration |
144 |
A: Discrete Output 1 Fixed |
145 |
Overview |
146 |
Configure |
147 |
Service Tools |
148 |
All Totalizers |
149 |
Variables |
150 |
Primary Variable |
151 |
Secondary Variable |
152 |
Totalizers |
153 |
Inputs/Outputs Fault Actions |
154 |
Alert Severity |
155 |
Mass Special Units |
156 |
Volume Special Units |
157 |
GSV |
158 |
Identification |
159 |
Revisions |
160 |
Security and Simulation |
161 |
mA Output Fault Settings |
162 |
Manual Verification |
163 |
Most Recent Test Results |
164 |
Automatic Verification |
165 |
F: EEPROM Error (CP) |
166 |
F: RAM Error (CP) |
167 |
F: No Sensor Response |
168 |
F: Temperature Overrange |
169 |
Additional Information |
170 |
F: Mass Flow Overrange |
171 |
View Diagnostic Variables |
172 |
F: Characterization Required |
173 |
F: Density Overrange |
174 |
View Density Characterization |
175 |
F: Transmitter Initializing/Warming Up |
176 |
F: Calibration Failure |
177 |
F: Zero Calibration Failed: Low |
178 |
F: Zero Calibration Failed: High |
179 |
F: Zero Calibration Failed: Unstable |
180 |
F: Transmitter Failure |
181 |
F: Sensor RTD Failure |
182 |
F: T-Series RTD Failure |
183 |
F: No Flow Calibration Value |
184 |
F: No K1 Value |
185 |
F: PIC/Daughterboard Communication Failure |
186 |
F: Incorrect Board Type |
187 |
F: Low Power |
188 |
F: Outputs Fixed During Smart Meter Verification |
189 |
F: No Right/Left Pickoff Signal |
190 |
View Two-Phase Flow Condition |
191 |
F: Smart Meter Verification Aborted |
192 |
A: mA Output Saturated |
193 |
A: mA Output Fixed |
194 |
M: Drive Overrange |
195 |
A: Calibration in Progress |
196 |
M: Two-Phase Flow |
197 |
A: Burst Mode Enabled |
198 |
M: Power Reset Occurred |
199 |
A: Frequency Output Saturated |
200 |
A: Frequency Output Fixed |
201 |
A: mA Output 2 Saturated |
202 |
A: mA Output 2 Fixed |
203 |
M: No External Input or Polled Data |
204 |
M: Smart Meter Verification in Progress |
205 |
A: Sensor Simulation Active |
206 |
M: EEPROM Error (Display) |
207 |
A: Discrete Event 1 Active |
208 |
A: Discrete Event 2 Active |
209 |
A: Discrete Event 3 Active |
210 |
A: Discrete Event 4 Active |
211 |
A: Discrete Event 5 Active |
212 |
A: Discrete Input Active |
213 |
M: Primary Variable Out of Limits |
214 |
M: Non-Primary Variable Out of Limits |
215 |
A: Cold Start |
216 |
F: Field Device Malfunction |
217 |
Zero |
218 |
Electronics |
219 |
Calibration |
220 |
Reset/Restore |
221 |
Offline Menu |
222 |
Download |
223 |
This process variable is the rate at which mass is flowing through the sensor. |
224 |
.2f |
225 |
.3f |
226 |
.4f |
227 |
.5f |
228 |
8d |
229 |
8.2f |
230 |
8.3f |
231 |
8.6f |
232 |
Min Span |
233 |
Mass Flow Classification |
234 |
Mass Flow Family |
235 |
Mass Flow PDQ |
236 |
Mass Flow LS |
237 |
Mass Flow Family Status |
238 |
The temperature of the liquid or gas being measured. |
239 |
Temperature Classification |
240 |
Temperature Family |
241 |
Temperature PDQ |
242 |
Temperature LS |
243 |
Temperature Family Status |
244 |
Mass Total Classification |
245 |
Mass Total Family |
246 |
Mass Total PDQ |
247 |
Mass Total LS |
248 |
Mass Total Family Status |
249 |
The density of the liquid being measured. |
250 |
.6f |
251 |
Density Classification |
252 |
Density Family |
253 |
Density PDQ |
254 |
Density LS |
255 |
Density Family Status |
256 |
Mass Inventory Classification |
257 |
Mass Inventory Family |
258 |
Mass Inventory PDQ |
259 |
Mass Inventory LS |
260 |
Mass Inventory Family Status |
261 |
This process variable is the rate at which volume is flowing through the sensor. |
262 |
10.4f |
263 |
Volume Flow Classification |
264 |
Volume Flow Family |
265 |
Volume Flow PDQ |
266 |
Volume Flow LS |
267 |
Volume Flow Family Status |
268 |
Volume Total Classification |
269 |
Volume Total Family |
270 |
Volume Total PDQ |
271 |
Volume Total LS |
272 |
Volume Total Family Status |
273 |
Volume Inventory Classification |
274 |
Volume Inventory Family |
275 |
Volume Inventory PDQ |
276 |
Volume Inventory LS |
277 |
Volume Inventory Family Status |
278 |
Pressure Classification |
279 |
Pressure Family |
280 |
Pressure PDQ |
281 |
Pressure LS |
282 |
Pressure Family Status |
283 |
6.2f |
284 |
Drive Gain Upper Sensor Limit |
285 |
Drive Gain Lower Sensor Limit |
286 |
Drive Minimum Span |
287 |
Drive Classification |
288 |
Drive Family |
289 |
Drive PDQ |
290 |
Drive LS |
291 |
Drive Family Status |
292 |
External Temperature Classification |
293 |
External Temperature Family |
294 |
External Temperature PDQ |
295 |
External Temperature LS |
296 |
External Temperature Family Status |
297 |
ANSI 150 |
298 |
ANSI 300 |
299 |
ANSI 600 |
300 |
PN40 |
301 |
JIS 10K |
302 |
JIS 20K |
303 |
ANSI 900 |
304 |
Sanitary clamp fitting |
305 |
Union |
306 |
PN100 |
307 |
Unknown |
308 |
Tube Lining |
309 |
PTFE |
310 |
Tefzel |
311 |
Tube Wetted Material |
312 |
Hast-C |
313 |
Monel |
314 |
Tantalum |
315 |
Titanium |
316 |
316L SST |
317 |
Inconel |
318 |
Base Unit |
319 |
Base Time |
320 |
Forward |
321 |
Reverse |
322 |
Bi directional |
323 |
A programmable high limit on density,which enables the transmitter to indicate two-phase flow (extremes in fluid density caused by slugs of gas or accumulation of solids in a liquid flow stream) if fluid density goes outside programmed two-phase flow limits. |
324 |
Two-Phase High Limit |
325 |
5.4f |
326 |
A programmable low limit on density, which enables the transmitter to indicate two-phase flow (extremes in fluid density caused by slugs of gas or accumulation of solids in a liquid flow stream) if fluid density goes outside programmed two-phase flow limits. |
327 |
Two-Phase Low Limit |
328 |
A programmable time period,from 0.00 to 60.00 seconds,during which outputs representing flow hold their last measured value before indicating two-phase flow. |
329 |
Two-Phase Duration |
330 |
5.2f |
331 |
Polarity |
332 |
5d |
333 |
5.3f |
334 |
5.5f |
335 |
µs |
336 |
Standard deviation is the two sigma result from the number of zero samples taken during the last zero. 'Standard Deviation', 'Live Zero', 'Smart Zero Verification' and 'Field Verification Zero' can be used to see how stable the zero is on your meter. |
337 |
6.5f |
338 |
2d |
339 |
Fault Action |
340 |
Upscale (21.0-24.0 mA) |
341 |
Downscale (1.0-3.6 mA) |
342 |
Fault Action |
343 |
Fault Action |
344 |
Internal Zero - All 0 |
345 |
Internal Zero - Flow 0 |
346 |
Fault Level |
347 |
Fault Level |
348 |
1d |
349 |
RTD Cable Resistance |
350 |
T-Series RTD Resistance |
351 |
Line RTD Resistance |
352 |
Power On Time |
353 |
Smart Meter Verification/Outputs in fault (A32) |
354 |
Smart Meter Verification/Outputs at last value (A131) |
355 |
7.2f |
356 |
Passcode(4 Digits) |
357 |
4d |
358 |
Refresh Rate (100-10,000) |
359 |
Poll as Primary Host |
360 |
Poll as Secondary Host |
361 |
Polled Variable 1 |
362 |
Polled Variable 2 |
363 |
10.7f |
364 |
7.5f |
365 |
Pressure Compensation |
366 |
Disable |
367 |
Enable |
368 |
Compensation Pressure |
369 |
This parameter allows you to enable/disable the external temperature feature. |
370 |
This parameter allows you to enter a static temperature when using the external temperature feature. |
371 |
Correction Temperature |
372 |
The variable that is monitored to determine if a flow switch has occurred. |
373 |
Smart Meter Verification Fail |
374 |
The state to which the discrete output will be set if the transmitter detects a fault with 'Alert Severity' = 'Fault'. If 'None' is selected, the behavior of the discrete output will be controlled by 'Discrete Output Source'. |
375 |
4.4f |
376 |
Start Smart Meter Verification |
377 |
Polarity |
378 |
Discrete Input State |
379 |
This parameter identifies the physical output channel to be configured. Channel 1 is terminals 1 and 2, and Channel 2 is terminals 3 and 4. |
380 |
Assignment |
381 |
Milliamp Output |
382 |
Assignment |
383 |
Power Source |
384 |
Power Source |
385 |
Tube Classification |
386 |
Tube Family |
387 |
Tube PDQ |
388 |
Tube LS |
389 |
Tube Family Status |
390 |
Board Temperature Classification |
391 |
Board Temperature Family |
392 |
Board Temperature PDQ |
393 |
Board Temperature LS |
394 |
Board Temperature Family Status |
395 |
Case Temperature Classification |
396 |
Case Temperature Family |
397 |
Case Temperature PDQ |
398 |
Case Temperature LS |
399 |
Case Temperature Family Status |
400 |
Engineer to Order Number |
401 |
Engineered to Order (ETO) number for the transmitter. |
402 |
3d |
403 |
Number of decimal points to be displayed for the value. |
404 |
Disabled |
405 |
Enabled |
406 |
Gas Reference Density |
407 |
Conversion Factor |
408 |
Flow Label |
409 |
Total Label |
410 |
Specifies the lowest gas standard volume flow rate that will be reported as measured. All gas standard volume flow rates below this cutoff are reported as 0. |
411 |
Simulate Primary Purpose Variables |
412 |
The state of the overall simulation mode. |
413 |
Control |
414 |
Fixed Value |
415 |
Ramp Low Point |
416 |
Ramp High Point |
417 |
Ramp Period |
418 |
A standard volume flow rate measurement used when the process fluid is a gas. |
419 |
Gas Volume Flow Classification |
420 |
Gas Volume Flow Family |
421 |
Gas Volume Flow PDQ |
422 |
Gas Volume Flow LS |
423 |
Gas Volume Flow Family Status |
424 |
Gas Volume Total Classification |
425 |
Gas Volume Total Family |
426 |
Gas Volume Total PDQ |
427 |
Gas Volume Total LS |
428 |
Gas Volume Total Family Status |
429 |
Gas Volume Inventory Classification |
430 |
Gas Volume Inventory Family |
431 |
Gas Volume Inventory PDQ |
432 |
Gas Volume Inventory LS |
433 |
Gas Volume Inventory Family Status |
434 |
Live Zero Classification |
435 |
Live Zero Family |
436 |
Live Zero PDQ |
437 |
Live Zero LS |
438 |
Live Zero Family Status |
439 |
Input Voltage Classification |
440 |
Input Voltage Family |
441 |
Input Voltage PDQ |
442 |
Input Voltage LS |
443 |
Input Voltage Family Status |
444 |
Enable Smart Meter Verification |
445 |
Specifies Smart Meter Verification enabling option |
446 |
Background Smart Meter Verification |
447 |
Ouput state during Smart Meter Verification |
448 |
Specifies Ouput state during Smart Meter Verification |
449 |
Uncertainty Limit |
450 |
Stiffness limit set point for Smart Meter Verification |
451 |
Reason for Abort |
452 |
Indicates the number of times the Smart Meter Verification routine has successfully completed. |
453 |
Smart Meter Verification Dataset Mean |
454 |
Smart Meter Verification Dataset Satndard Deviation |
455 |
Smart Meter Verification dataset LPO stiffness. |
456 |
Smart Meter Verification dataset RPO stiffness. |
457 |
Smart Meter Verification dataset damping. |
458 |
Smart Meter Verification dataset LPO mass. |
459 |
Smart Meter Verification dataset RPO mass. |
460 |
Smart Meter Verification Dataset |
461 |
The version of the Device Description (DD) being used. |
462 |
Hours until Next Run |
463 |
The number hours until the next time Smart Meter Verification runs. |
464 |
4.1f |
465 |
Hours between Recurring Runs (0=Schedule is not Repeating) |
466 |
The number of hours between successive Smart Meter Verification runs. Valid range is 1 to 1000 hours or 0 for no recurring schedule. |
467 |
Hours Remaining until Next Run |
468 |
The number of hours remaining until Smart Meter Verification runs. |
469 |
Smart Meter Verification Run Counter |
470 |
The run counter for this Smart Meter Verification run. |
471 |
Manual Abort |
472 |
Watchdog Timeout |
473 |
High Peak Drive Voltage |
474 |
High Drive Current Standard Deviation |
475 |
High Drive Current Mean Value |
476 |
Drive Loop Reported Error |
477 |
High Delta T Standard Deviation |
478 |
High Delta T Value |
479 |
State Running |
480 |
Verification Complete |
481 |
Wrong Verification Enable |
482 |
No Factory Air Verification |
483 |
No Factory Water Verification |
484 |
Parameter Registers not Set |
485 |
Transmitter Running Seconds at Test |
486 |
Keep Existing Assignment |
487 |
Initial Setup |
488 |
Configures the sensor characteristics of the transmitter. |
489 |
Configures channels, inputs, outputs and variable mapping. |
490 |
Any changes made on this screen will be written to the device when the Next button is clicked. Transmitter operation could be affected. Click Next to write changes to the device, or click Cancel to abort. |
491 |
The 'Milliamp Output' uses the 'Primary Variable' as its source. |
492 |
The 'Secondary Variable' is only used in HART communications. |
493 |
The 'Frequency Output' uses the 'Third Variable' as its source. |
494 |
The 'Fourth Variable' is only used in HART communications. |
495 |
Loop Tests |
496 |
Set a fixed output value for the Milliamp Output. |
497 |
Set a fixed output value for the Frequency Output. |
498 |
Set a fixed output state for the Discrete Output. |
499 |
Digital Communications |
500 |
Enter an Alert number and change the Alert's severity to Fault, Information or Ignore. |
501 |
Enter an Alert number and view the current severity of the alert. |
502 |
Configures the process monitor screens by selecting the desired process variables for each screen. |
503 |
Configures the number of decimal places for each process variable. |
504 |
Assigns output channel type and variable. |
505 |
Assigns a variable to the Milliamp Output, define Upper and Lower Range Values, Cutoff and Damping. |
506 |
Assigns a variable to the Frequency Output, set Maximum Pulse Width, Polarity and Scaling. |
507 |
Assigns a variable to the Discrete Output, set Flow Switch. |
508 |
Assigns polarity to the Discrete Input. |
509 |
Sets up Bell-202 port (HART only). |
510 |
Assigns variables to Primary (PV), Secondary (SV), Third (TV) and Fourth (QV) Variables. |
511 |
This screen will not automatically refresh after changing the 'Type' field. Select Guided Setup and then return to this screen to see the current configuration. |
512 |
Optional Setup |
513 |
Set Up Bell 202 Port |
514 |
HART Burst Mode |
515 |
Performs digital to analog trim of the Milliamp Output. |
516 |
Performs first point (air) calibration. |
517 |
Performs second point (water) calibration. |
518 |
Performs third point (user's choice) calibration. |
519 |
Performs fourth point (user's choice) calibration. |
520 |
Performs flowing density calibration. |
521 |
Status |
522 |
Tag, model code, revision, security, and related data. |
523 |
Displays values of process variables and outputs. |
524 |
Trend charts for process and diagnostic variables. |
525 |
Perform a zero calibration which sets a zero reference for a no-flow condition. |
526 |
Revision Numbers |
527 |
Security Switch Status |
528 |
Simulation Status |
529 |
Reads Modbus data from device memory. |
530 |
Writes Modbus data to device memory. |
531 |
Performs Smart Meter Verification, which will determine the health of the meter without stopping the process flow or removing the meter from the line. |
532 |
Simulation Configuration |
533 |
Mass Flow Rate Simulation Settings |
534 |
Density Simulation Settings |
535 |
Temperature Simulation Settings |
536 |
Simulation Settings |
537 |
|
538 |
Recommended Actions:
1. Check the sensor circuitry.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
3. If the problem persists, contact Micro Motion. |
539 |
Recommended Actions:
1. Verify that a sensor is connected to the transmitter.
2. Check the sensor RTD circuitry.
3. Verify that process temperature is within range of sensor and transmitter.
4. If the problem persists, contact Micro Motion. |
540 |
Recommended Actions:
1. If other alerts are present (typically, A003, A006, A008, A102, or A105), resolve those alerts first. If the A005 alert persists, continue with the suggestions below.
2. View the diagnostic variables to verify whether tubes are vibrating. Left and Right pickoffs should be above 10mV.
3. Check the sensor circuitry.
4. Check the sensor tubes for erosion by verifying density.
5. If the problem persists, contact Micro Motion. |
541 |
Recommended Actions:
1. Check the characterization. Specifically, verify the Flow FCF and K1 values on the sensor tag.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
3. If the problem persists, contact Micro Motion. |
542 |
Recommended Actions:
1. Check the characterization. Specifically, verify the FlowCal and K1 values on the sensor tag.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
3. If the problem persists, contact Micro Motion. |
543 |
The measured density has exceeded 0-10 g/Cucm. |
544 |
Recommended Actions:
1. If other alerts are present (typically, A003, A006, A102, or A105), resolve those alerts first. If the A008 alert persists, continue with the suggestions below.
2. Verify process. Check for air in the flow tubes, tubes not filled, foreign material in tubes, or coating in tubes.
3. Check the sensor circuitry.
4. Verify density characterization and verify configuration matches sensor tag.
5 View diagnostic variables to verify raw tube frequency is in the proper range for the sensor type.
6. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
7. If the problem persists, contact Micro Motion. |
545 |
Recommended Actions:
1. Allow the flowmeter to warm up (approximately 30 seconds). The error should disappear once the flowmeter is ready for normal operation.
2. Check the input voltage to ensure its between 12 and 15 V.
3. If alert does not clear, make sure that the sensor is completely full or completely empty.
4. Check the sensor circuitry.
5. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
546 |
Mechanical Zero: The resulting zero was greater than 3 microseconds.
Temperature or Density Calibrations: Many possible causes. |
547 |
Recommended Actions:
1. If alert appears during a transmitter zero, ensure that there is no flow through the sensor, then retry.
2. Cycle power to the flowmeter to clear the alert.
3. If appropriate, restore the factory zero to return the flowmeter to operation.
4. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
5. If alert appears during a density calibration, contact Micro Motion. |
548 |
Mechanical Zero: Calibration procedure failed due to reverse flow through the sensor. |
549 |
Mechanical Zero: Calibration procedure failed due to reverse flow through the sensor.
The resulting zero was greater than 3 microseconds. |
550 |
Mechanical Zero: The resulting zero was greater than 3 microseconds. |
551 |
Internal memory or program fault has been detected. |
552 |
Recommended Actions:
1. Resolve other active alerts first.
2. Cycle power to the flowmeter.
3. If alert persists, the transmitter might need service. Contact Micro Motion. |
553 |
Recommended Actions:
1. Check the sensor RTD circuitry.
2. Verify that process temperature is within range of sensor and transmitter.
3. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
4. If the problem persists, contact Micro Motion. |
554 |
Recommended Actions:
1. Check the characterization against the sensor tag. Specifically, verify the Flow FCF, K1 and K2 values.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
3. If the problem persists, contact Micro Motion. |
555 |
Recommended Actions:
1. Check the characterization against the sensor tag. Specifically, verify the FlowCal, K1 and K2 values.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
3. If the problem persists, contact Micro Motion. |
556 |
Recommended Actions:
1. If A017 is active, resolve it first.
2. Check the characterization against the sensor tag. Specifically, verify the Flow FCF, K1 and K2 values.
3. Check the sensor RTD circuitry.
4. If the problem persists, contact Micro Motion. |
557 |
Recommended Actions:
1. Cycle power to the flowmeter.
2. If the problem persists, contact Micro Motion. |
558 |
Recommended Actions:
1. Verify the core processor input voltage is at least 12V.
2. Check the power supply and all power wiring. |
559 |
Smart Meter Verification is in progress, with outputs are fixed. |
560 |
Recommended Actions:
1. Allow the procedure to complete.
2. If desired, abort the procedure and restart with outputs set to continue measuring. |
561 |
Recommended Actions:
1. Check for two-phase flow.
2. View the diagnostic variables to verify whether tubes are vibrating. Left and Right pickoffs should be above 10mV.
3. Check the sensor circuitry.
4. Check sensor tubes for plugging.
5. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
6. If the problem persists, contact Micro Motion. |
562 |
Smart Meter Verification failed. The stiffness values not within acceptable limits. |
563 |
Recommended Actions:
1. Immediately re-run the Smart Meter Verification test with outputs held at fault or last measured value. If the meter passes the second test, the fail result can be ignored. If the meter fails the second test, the flow tubes may be damaged.
2. Use the knowledge of your process to consider the type of damage and determine the appropriate action. These actions might include removing the meter from service and physically inspecting the tubes. At a minimum, perform a flow validation and a density calibration.
3. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
564 |
Smart Meter Verification aborted. |
565 |
Reason:
User Initiated Abort
Recommend Actions:
1. Wait for 15 seconds before starting Smart Meter Verification again.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
566 |
Reason:
Frequency Drift
Recommend Actions:
1. Ensure temperature, flow and density are stable and run Smart Meter Verification again.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
567 |
Reason:
High Drive Gain
Recommend Actions:
1. Ensure flow is steady and minimize entrained gas and run Smart Meter Verification again.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
568 |
Reason:
Unstable Flow
Recommend Actions:
1. Reduce flow rate and run Smart Meter Verification again.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
569 |
Reason:
No Air Reference
Recommend Actions:
1. Perform factory calibration on air.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
570 |
Reason:
No Water Reference
Recommend Actions:
1. Perform factory calibration on water.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
571 |
Reason:
Missing Configuration
Recommend Actions:
1. Load verification parameter registers with proper values.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
572 |
Reason:
Other
Recommend Actions:
1. Run Smart Meter Verification again.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
3. If abort persists, contact Micro Motion. |
573 |
Recommended Actions:
1. Verify that mA output range values are set to appropriate values.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
574 |
Recommended Actions:
1. Check the HART address. If non-zero, set 'mA Output Action' parameter to enable 'Live mA Output' or if multi-drop mode is desired change the alert severity to ignore by going to the Configure-> Alert Setup-> Alert Severity screen.
2. If mA output trim is being performed, exit mA output trim.
3. If mA output loop test is being performed, exit mA output loop test.
4. Check to see if the output has been fixed via digital communications or the local display. |
575 |
Recommended Actions:
1. Check the sensor circuitry.
2. If this is the only active alarm, it can be ignored. If desired, reconfigure the alarm severity to Ignore.
3. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
576 |
Recommended Actions:
1. Allow the flowmeter to complete calibration.
2. For zero calibration procedures, you may abort the calibration, set the zero time parameter to a lower value, and restart the calibration.
3. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
577 |
Recommended Actions:
1. Check that sensor is completely full.
2. Check that slug limits are set to appropriate values.
3. Verify density cutoff is at least 0.2 g/cc.
4. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
578 |
Recommended Actions:
1. No action required.
2. If desired, reconfigure the alert severity to Ignore by going to the Configure-> Alert Setup-> Alert Severity screen. |
579 |
Recommended Actions:
1. No action required.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
580 |
Process variable assigned to frequency output is outside configured scale limits. |
581 |
Recommended Actions:
1. Change frequency output scaling factors to more appropriate settings.
2. If the Third Variable is set to volume flow, low density or empty tubes can cause the frequency output to saturate.
3. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
582 |
Recommended Actions:
1. Exit frequency output loop test.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
583 |
Recommended Actions:
1. If mA output trim is being performed, exit mA output trim.
2. If mA output loop test is being performed, exit mA output loop test.
3. Check to see if the output has been fixed via digital communications or the local display.
4. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
584 |
Recommended Actions:
1. Exit discrete output test.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
585 |
Recommended Actions:
1. HART polling connection to external device has failed. Ensure that external device is available.
2. Verify external device is not in fault.
3. Verify HART segment power, wiring and loop resistance.
4. Verify polling configuration in the transmitter and external device.
5. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
586 |
A131: Smart Meter Verification in Progress |
587 |
Smart Meter Verification is in progress. |
588 |
Recommended Actions:
1. Allow the procedure to complete.
2. If desired, abort the procedure and restart with outputs set to fault.
3. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
589 |
Recommended Actions:
1. Disable output simulation.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
590 |
Recommended Actions:
1. Cycle power to the flow meter.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
3. The flow meter might need service. Contact Micro Motion. |
591 |
Recommended Actions:
1. Verify process and check for two-phase flow.
2. Check the diagnostic variables.
3. Check the sensor circuitry.
4. Check the sensor tubes for erosion.
5. If the problem persists, contact Micro Motion. |
592 |
Recommended Actions:
1. Verify process and check for two-phase flow.
2. Check the test points.
3. Check the sensor circuitry.
4. Check the sensor tubes for erosion.
5. If the problem persists, contact Micro Motion. |
593 |
Recommended Actions:
1. Check the HART address. If non-zero, set mA Output Action parameter to enable Live mA Output.
2. If mA output trim is being performed, exit mA output trim.
3. If mA output loop test is being performed, exit mA output loop test.
4. Check to see if the output has been fixed via digital communications or the local display. |
594 |
Recommended Actions:
1. This is a summary alert and is generated when one of the fault severity alerts is active. Resolve the other active alerts first. |
595 |
Density Characterization |
596 |
Two-Phase Flow Condition |
597 |
Electronic Conditions |
598 |
Recommended Actions:
1. Cycle power to the flow meter.
2. The flow meter might need service. Contact Micro Motion. |
599 |
Sensor Conditions |
600 |
Process Conditions |
601 |
Configuration Conditions |
602 |
Recommended Actions:
1. If A26 also appears, resolve the A26 first if connected to core 700.
2. Allow the flowmeter to warm up (approximately 30 seconds). The error should disappear once the flowmeter is ready for normal operation.
3. Check the input voltage to ensure its between 12 and 15 V.
4. Check for proper voltage into the transmitter if connected to core 700.
5. If alert does not clear, make sure that the sensor is completely full or completely empty.
6. Check the sensor circuitry.
7. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
603 |
Recommended Actions:
1. Contact Micro Motion. |
604 |
Recommended Actions:
1. Allow the procedure to complete.
2. If desired, abort the procedure and restart with outputs set to last measured value. |
605 |
Recommended Actions:
1. Smart Meter Verification aborted.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
606 |
Recommended Actions:
1. Allow the procedure to complete. You may abort the procedure if desired.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
607 |
Recommended Actions:
1. Verify that mA output range values are set to appropriate values. |
608 |
Recommended Actions:
1. No action required. |
609 |
Recommended Actions:
1. The first command to recognize this condition will automatically reset this flag.
2. This flag may also be set following a Master Reset or a Self Test. |
610 |
Classic View |
611 |
Performs a zero calibration. |
612 |
Performs a density calibration. |
613 |
Performs a temperature calibration. |
614 |
Power cycles the device without affecting device configuration. |
615 |
Overwrites the existing device configuration with the configuration set at the factory. |
616 |
Resets the configuration changed flag if the host is not able to reset the flag automatically. |
617 |
PV Analog Channel Saturated |
618 |
PV Analog Channel Fixed |
619 |
Enable on token-passing data link layer only |
620 |
Enable on TDMA data link layer only |
621 |
Enable on both TDMA and token-passing data link layer |
622 |
Wireless |
623 |
WirelessHART Device |
624 |
IEEE 802.15.4 2.4GHz DSSS with O-QPSK Modulation |
625 |
Primary |
626 |
Primary Analog Channel |
627 |
Secondary |
628 |
Secondary Analog Channel |
629 |
Tertiary |
630 |
Tertiary Analog Channel |
631 |
Quaternary |
632 |
Quaternary Analog Channel |
633 |
Quinary |
634 |
Quinary Analog Channel |
635 |
Critical Power Failure |
636 |
Lock all |
637 |
Trim not supported |
638 |
Configuration cannot be changed |
639 |
Locked by gateway |
640 |
Analog Input Channel |
641 |
Analog Output Channel |
642 |
Secondary Analog Channel Saturated |
643 |
Tertiary Analog Channel Saturated |
644 |
Quaternary Analog Channel Saturated |
645 |
Quinary Analog Channel Saturated |
646 |
Secondary Analog Channel Fixed |
647 |
Tertiary Analog Channel Fixed |
648 |
Quaternary Analog Channel Fixed |
649 |
Quinary Analog Channel Fixed |
650 |
Wired HART Enabled |
651 |
Enabled on Wired HART device connection only |
652 |
Wireless HART Enabled |
653 |
Enabled on WirelessHART device connection only |
654 |
Both Wired and WirelessHart Enabled |
655 |
Enabled on both Wired and WirelessHART connections |
656 |
8u |
657 |
Device Variable |
658 |
Analog Channel Number |
659 |
Analog Channel Number- Index into an array of Analog Channels. |
660 |
Burst Command |
661 |
Changing configuration can affect transmitter operation. Ensure that the control loop is set for manual operation before continuing. |
662 |
Enter 'Zero Time': |
663 |
Flow must be zero. Click Next to perform a zero calibration. |
664 |
A problem was detected: |
665 |
It is now safe to return the control loop to automatic control. |
666 |
Zero calibration is starting... |
667 |
Calibration is in progress...
Zero: %{0} µs
Standard Deviation: %{1} µs |
668 |
Auto Zero is complete.
Zero: %{0} µs
Standard Deviation: %{1} µs |
669 |
Enter 'Density': |
670 |
Calibration is in progress... |
671 |
Density calibration is complete. |
672 |
Note: Flow rate must be greater than 50% of the nominal flow for the meter. |
673 |
Select 'Discrete Output State': |
674 |
'Discrete Output State' is Off. |
675 |
'Discrete Output State' is On. |
676 |
Returning 'Discrete Output' to normal function... |
677 |
Select 'Frequency Output' level: |
678 |
10000 Hz;Other;End |
679 |
Enter the desired 'Frequency Output': |
680 |
'Frequency Output' is fixed at %0 Hz. |
681 |
Select 'mA Output' level: |
682 |
Output Value: |
683 |
'mA Output' is fixed at %0 mA. |
684 |
Connect the reference meter. |
685 |
Click Next to set 'mA Output' to %0 mA. |
686 |
Enter reading from the reference meter: |
687 |
Does the device output match the reference meter? |
688 |
Yes;No |
689 |
All totalizers have been started. |
690 |
All totalizers have been stopped. |
691 |
All totalizers have been reset. |
692 |
Mass total has been reset. |
693 |
Volume total has been reset. |
694 |
GSV total has been reset. |
695 |
Returning 'Frequency Output' to normal function... |
696 |
Returning 'mA Output' to normal function... |
697 |
Note-Variables which use this as the units code will be in the previous units until this value is sent to the device. |
698 |
alarmNum |
699 |
Select Alert Severity: |
700 |
Start Sensor Zero;Reset Mass Total;Reset Volume Total;Reset All Totals;Start/Stop Totals;Start Smart Meter Verification |
701 |
Start Sensor Zero;Reset Mass Total;Reset Gas Standard Volume Total;Reset All Totals;Start/Stop Totals;Start Smart Meter Verification |
702 |
None;Discrete Event 1;Discrete Event 2;Discrete Event 3;Discrete Event 4;Discrete Event 5 |
703 |
Start Sensor Zero;Reset Mass Total;Reset Volume Total;Reset All Totals;Start/Stop Totals |
704 |
Start Sensor Zero;Reset Mass Total;Reset Gas Standard Volume Total;Reset All Totals;Start/Stop Totals |
705 |
%0 is assigned to %1. |
706 |
All alerts are acknowledged. |
707 |
Selection for data type: |
708 |
Enter 'Coil Number': |
709 |
number |
710 |
Enter 'Register Number': |
711 |
'Coil Mode' is %0 and 'Exception Code' is %1. |
712 |
'Unsigned 16 Value' is %0 and 'Exception Code' is %1. |
713 |
'Unsigned 32 Value' is %0 and 'Exception Code' is %1. |
714 |
'Floating Point Value' is %0 and 'Exception Code' is %1. |
715 |
Coil Mode: |
716 |
Disable;Enable |
717 |
Enter 'Unsigned 16 Value': |
718 |
uValue |
719 |
Enter 'Unsigned 32 Value': |
720 |
Enter 'Floating Point Value': |
721 |
fValue |
722 |
Select the 'Simulation Mode': |
723 |
select |
724 |
'Simulation Mode' is %0. |
725 |
floatFaultVal |
726 |
intLMVFaultTimeout |
727 |
Starting Smart Meter Verification, please wait. |
728 |
Smart Meter Verification completed: %{0} % |
729 |
Smart Meter Verification PASSED.
Meter meets factory specifications. |
730 |
Smart Meter Verification FAILED.
Meter may not meet factory specifications.
Press Help for more Information. |
731 |
Smart Meter Verification error. |
732 |
Smart Meter Verification error.
%{0} |
733 |
Frequency Factor (Hz): |
734 |
floatFreqVal |
735 |
Rate Factor: |
736 |
floatRateVal |
737 |
Pulses/Unit: |
738 |
floatPulsesPerUnit |
739 |
Units/Pulse: |
740 |
floatUnitsPerPulse |
741 |
'Configuration Changed Flag' is being reset, please wait. |
742 |
'Configuration Changed Flag' has been reset. |
743 |
Mass Flow Rate:
Value %0 %1
Gas Standard Volume Flow Rate:
Value %2 %3
Density:
Value %4 %5 |
744 |
Select Burst Mode: |
745 |
Select Burst Option: |
746 |
Burst Mode configuration completed. |
747 |
Current sensor type selection is Other (Curved Tube).
Select Sensor Type: |
748 |
Current sensor type selection is T-Series (Straight Tube).
Select Sensor Type: |
749 |
Select 'Pressure Unit' used by the external pressure device: |
750 |
Current primary variable selection is %0.
Select Primary Variable: |
751 |
View Alert Severity of: |
752 |
Priority: Failed - Fix Now
Description:
An uncorrectable checksum mismatch has been detected.
Recommended Actions:
1. Cycle power to the flow meter.
2. The flow meter might need service. Contact Micro Motion. |
753 |
No Additional Information Available |
754 |
Priority: Failed - Fix Now
Description:
ROM checksum error or a RAM location cannot be written to.
Recommended Actions:
1. Cycle power to the flowmeter.
2. The flow meter might need service. Contact Micro Motion. |
755 |
Priority: Failed - Fix Now
Description:
Continuity failure of drive circuit, LPO, or RPO, or LPO-RPO mismatch when driving.
Recommended Actions:
1. Check the sensor circuitry.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
3. If the problem persists, contact Micro Motion. |
756 |
Drive Gain:
Value %0 |
757 |
Priority: Failed - Fix Now
Description:
The value computed for the resistance of the line RTD or the Meter/Case RTD is outside limits.
Recommended Actions:
1. Verify that a sensor is connected to the transmitter.
2. Check the sensor RTD circuitry.
3. Verify that process temperature is within range of sensor and transmitter.
4. If the problem persists, contact Micro Motion. |
758 |
Temperature:
Value %0 |
759 |
Priority: Failed - Fix Now
Description:
The measured flow has exceeded the maximum flow rate of the sensor.
Recommended Actions:
1. If other alerts are present (typically, A003, A006, A008, A102, or A105), resolve those alerts first. If the A005 alert persists, continue with the suggestions below.
2. View the diagnostic variables to verify whether tubes are vibrating. Left and Right pickoffs should be above 10mV.
3. Check the sensor circuitry.
4. Check the sensor tubes for erosion by verifying density.
5. If the problem persists, contact Micro Motion. |
760 |
Priority: Failed - Fix Now
Description:
One or more required characterization parameters have not been entered.
Recommended Actions:
1. Check the characterization. Specifically, verify the FlowCal and K1 values on the sensor tag.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
3. If the problem persists, contact Micro Motion. |
761 |
Flow Cal:
Value %0
K1:
Value %1 uSec
K2:
Value %2 uSec |
762 |
Priority: Failed - Fix Now
Description:
One or more required characterization parameters have not been entered.
Recommended Actions:
1. Check the characterization. Specifically, verify the Flow FCF and K1 values on the sensor tag.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
3. If the problem persists, contact Micro Motion. |
763 |
Flow FCF:
Value %0
K1:
Value %1 uSec
K2:
Value %2 uSec |
764 |
Priority: Failed - Fix Now
Description:
The measured density has exceeded 0-10 g/Cucm.
Recommended Actions:
1. If other alerts are present (typically, A003, A006, A102, or A105), resolve those alerts first. If the A008 alert persists, continue with the suggestions below.
2. Verify process. Check for air in the flow tubes, tubes not filled, foreign material in tubes, or coating in tubes.
3. Check the sensor circuitry.
4. Verify density characterization and verify configuration matches sensor tag.
5 View diagnostic variables to verify raw tube frequency is in the proper range for the sensor type.
6. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
7. If the problem persists, contact Micro Motion. |
765 |
Priority: Failed - Fix Now
Description:
Transmitter in power-up mode.
Recommended Actions:
1. Allow the flowmeter to warm up (approximately 30 seconds). The error should disappear once the flowmeter is ready for normal operation.
2. Check the input voltage to ensure its between 12 and 15 V.
3. If alert does not clear, make sure that the sensor is completely full or completely empty.
4. Check the sensor circuitry.
5. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
766 |
Priority: Failed - Fix Now
Description:
Mechanical zero: The resulting zero was greater than 3 microseconds.
Temperature or Density Calibrations: Many possible causes.
Recommended Actions:
1. If alert appears during a transmitter zero, ensure that there is no flow through the sensor, then retry.
2. Cycle power to the flowmeter to clear the alert.
3. If appropriate, restore the factory zero to return the flowmeter to operation.
4. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
5. If alert appears during a density calibration, contact Micro Motion. |
767 |
Priority: Failed - Fix Now
Description:
Mechanical zero: Calibration procedure failed due to reverse flow through the sensor.
Recommended Actions:
1. If alert appears during a transmitter zero, ensure that there is no flow through the sensor, then retry.
2. Cycle power to the flowmeter to clear the alert.
3. If appropriate, restore the factory zero to return the flowmeter to operation.
4. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
5. If alert appears during a density calibration, contact Micro Motion. |
768 |
Priority: Failed - Fix Now
Description:
Mechanical zero: Calibration procedure failed due to flow through the sensor.The resulting zero was greater than 3 microseconds.
Recommended Actions:
1. If alert appears during a transmitter zero, ensure that there is no flow through the sensor, then retry.
2. Cycle power to the flowmeter to clear the alert.
3. If appropriate, restore the factory zero to return the flowmeter to operation.
4. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
5. If alert appears during a density calibration, contact Micro Motion. |
769 |
Priority: Failed - Fix Now
Description:
Mechanical zero: The resulting zero was greater than 3 microseconds.
Recommended Actions:
1. If alert appears during a transmitter zero, ensure that there is no flow through the sensor, then retry.
2. Cycle power to the flowmeter to clear the alert.
3. If appropriate, restore the factory zero to return the flowmeter to operation.
4. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
5. If alert appears during a density calibration, contact Micro Motion. |
770 |
Priority: Failed - Fix Now
Description:
Internal memory or program fault has been detected.
Recommended Actions:
1. Resolve other active alerts first.
2. Cycle power to the flowmeter.
3. If alert persists, the transmitter might need service. Contact Micro Motion. |
771 |
Priority: Failed - Fix Now
Description:
The value computed for the resistance of the Line RTD is outside limits.
Recommended Actions:
1. Check the sensor RTD circuitry.
2. Verify that process temperature is within range of sensor and transmitter.
3. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
4. If the problem persists, contact Micro Motion. |
772 |
Priority: Failed - Fix Now
Description:
The value computed for the resistance of the Meter/Case RTD is outside limits.
Recommended Actions:
1. Check the sensor RTD circuitry.
2. Verify that process temperature is within range of sensor and transmitter.
3. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
4. If the problem persists, contact Micro Motion. |
773 |
Priority: Failed - Fix Now
Description:
The flow calibration factor and/or K1 has not been entered since the last master reset.
Recommended Actions:
1. Check the characterization against the sensor tag. Specifically, verify the FlowCal, K1 and K2 values.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
3. If the problem persists, contact Micro Motion. |
774 |
Priority: Failed - Fix Now
Description:
The flow calibration factor and/or K1 has not been entered since the last master reset.
Recommended Actions:
1. Check the characterization against the sensor tag. Specifically, verify the Flow FCF, K1 and K2 values.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
3. If the problem persists, contact Micro Motion. |
775 |
Priority: Failed - Fix Now
Description:
The sensor is recognized as a straight tube but the K1 value indicates a curved tube, or vice versa.
Recommended Actions:
1. If A017 is active, resolve it first.
2. Check the characterization against the sensor tag. Specifically, verify the Flow FCF, K1 and K2 values.
3. Check the sensor RTD circuitry.
4. If the problem persists, contact Micro Motion. |
776 |
Flow FCF:
Value %0
K1:
Value %1 us
K2:
Value %2 us |
777 |
Priority: Failed - Fix Now
Description:
Transmitter electronics failure has occurred.
Recommended Actions:
1. Cycle power to the flowmeter.
2. If the problem persists, contact Micro Motion. |
778 |
Priority: Failed - Fix Now
Description:
The loaded software is not compatible with the programmed board type.
Recommended Actions:
1. Contact Micro Motion. |
779 |
Priority: Failed - Fix Now
Description:
The core processor is not receiving enough power.
Recommended Actions:
1. Verify the core processor input voltage is at least 12V.
2. Check the power supply and all power wiring. |
780 |
Priority: Failed - Fix Now
Description:
Smart Meter Verification is in progress, with outputs are fixed.
Recommended Actions:
1. Allow the procedure to complete.
2. If desired, abort the procedure and restart with outputs set to last measured value. |
781 |
Priority: Failed - Fix Now
Description:
No signal from Left Pickoff or Right Pickoff, suggesting that sensor tubes are not vibrating.
Recommended Actions:
1. Check for two-phase flow.
2. View the diagnostic variables to verify whether tubes are vibrating. Left and Right pickoffs should be above 10mV.
3. Check the sensor circuitry.
4. Check sensor tubes for plugging.
5. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
6. If the problem persists, contact Micro Motion. |
782 |
Priority: Advisory
Description:
The calculated amount of current output is outside of the linear range.
Recommended Actions:
1. Verify that mA output range values are set to appropriate values.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
783 |
Primary Variable:
%0
%0:
Value %1 %2 |
784 |
PV LRV:
Value %0 %1
PV URV:
Value %2 %3 |
785 |
Priority: Advisory
Description:
Non-zero HART address configured, or user has set the mA output to a fixed value.
Recommended Actions:
1. Check the HART address. If non-zero, set 'mA Output Action' parameter to enable 'Live mA Output' or if multi-drop mode is desired change the alert severity to ignore by going to the Configure-> Alert Setup-> Alert Severity screen.
2. If mA output trim is being performed, exit mA output trim.
3. If mA output loop test is being performed, exit mA output loop test.
4. Check to see if the output has been fixed via digital communications or the local display. |
786 |
HART Address:
%0
mAO Fault Action:
%1 |
787 |
Priority: Maintenance - Fix Soon
Description:
The drive power (current/voltage) is at its maximum.
Recommended Actions:
1. Check the sensor circuitry.
2. If this is the only active alarm, it can be ignored. If desired, reconfigure the alarm severity to Ignore.
3. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
788 |
Priority: Advisory
Description:
A calibration procedure is in progress.
Recommended Actions:
1. Allow the flowmeter to complete calibration.
2. For zero calibration procedures, you may abort the calibration, set the zero time parameter to a lower value, and restart the calibration.
3. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
789 |
Priority: Maintenance - Fix Soon
Description:
The density has exceeded the user-defined slug (density) limits.
Recommended Actions:
1. Check that sensor is completely full.
2. Check that slug limits are set to appropriate values.
3. Verify density cutoff is at least 0.2 g/cc.
4. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
790 |
Slug High Limit:
Value %0 g/Cucm
Slug Low Limit:
Value %1 g/Cucm
Slug Duration:
Value %2 sec |
791 |
Priority: Advisory
Description:
Device is in HART burst mode.
Recommended Actions:
1. No action required.
2. If desired, reconfigure the alert severity to Ignore by going to the Configure-> Alert Setup-> Alert Severity screen. |
792 |
Priority: Maintenance - Fix Soon
Description:
Transmitter has been restarted.
Recommended Actions:
1. No action required.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
793 |
Priority: Advisory
Description:
Process variable assigned to frequency output is outside configured scale limits.
Recommended Actions:
1. Change frequency output scaling factors to more appropriate settings.
2. If the Third Variable is set to volume flow, low density or empty tubes can cause the frequency output to saturate.
3. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
794 |
Third Variable:
%0
%0:
Value %1 %2 |
795 |
Rate Factor:
Value %0 Hz
Pulses/Unit:
Value %1
Units/Pulse:
Value %2 |
796 |
Priority: Advisory
Description:
User has set the frequency output to a fixed value.
Recommended Actions:
1. Exit frequency output loop test.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
797 |
Tube Frequency:
Value %0 Hz |
798 |
Priority: Advisory
Description:
Non-zero HART address configured, or user has set the mA output to a fixed value.
Recommended Actions:
1. Check the HART address. If non-zero, set 'mA Output Action' parameter to enable 'Live mA Output' or if multi-drop mode is desired change the alert severity to ignore by going to the Configure-> Alert Setup-> Alert Severity screen.
2. If mA output trim is being performed, exit mA output trim.
3. If mA output loop test is being performed, exit mA output loop test.
4. Check to see if the output has been fixed via digital communications or the local display. |
799 |
Priority: Maintenance - Fix Soon
Description:
No response received from polled device.
Recommended Actions:
1. HART polling connection to external device has failed. Ensure that external device is available.
2. Verify device operation.
3. Verify wiring.
4. Verify polling configuration. |
800 |
Poll Control:
%0
Ext Device Tag 1:
%1
Polled Variable 1:
%2 |
801 |
Ext Device Tag 2:
%0
Polled Variable 2:
%1 |
802 |
Priority: Maintenance - Fix Soon
Description:
Smart Meter Verification is in progress.
Recommended Actions:
1. Allow the procedure to complete. You may abort the procedure if desired.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
803 |
Priority: Advisory
Description:
Simulation mode is enabled.
Recommended Actions:
1. Disable output simulation.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
804 |
Priority: Maintenance - Fix Soon
Description:
An uncorrectable checksum mismatch has been detected.
Recommended Actions:
1. Cycle power to the flow meter.
2. The flow meter might need service. Contact Micro Motion. |
805 |
Priority: Advisory
Description:
Discrete Event 1 has been triggered.
Recommended Actions:
1. No action required. |
806 |
Discrete Event Var:
%0
Discrete Event Type:
%1 |
807 |
Setpoint A:
Value %0
Setpoint B:
Value %1 |
808 |
Priority: Advisory
Description:
Discrete Event 2 has been triggered.
Recommended Actions:
1. No action required. |
809 |
Priority: Advisory
Description:
Discrete Event 3 has been triggered.
Recommended Actions:
1. No action required. |
810 |
Priority: Advisory
Description:
Discrete Event 4 has been triggered.
Recommended Actions:
1. No action required. |
811 |
Priority: Advisory
Description:
Discrete Event 5 has been triggered.
Recommended Actions:
1. No action required. |
812 |
Priority: Advisory
Description:
Discrete Input is active.
Recommended Actions:
1. No action required. |
813 |
Priority: Maintenance - Fix Soon
Description:
Primary variable has exceeded sensor limits.
Recommended Actions:
1. Verify process and check for two-phase flow.
2. Check the diagnostic variables.
3. Check the sensor circuitry
4. Check the sensor tubes for erosion.
5. If the problem persists, contact Micro Motion. |
814 |
Priority: Maintenance - Fix Soon
Description:
Non-primary variable has exceeded sensor limits.
Recommended Actions:
1. Verify process and check for two-phase flow.
2. Check the diagnostic variables.
3. Check the sensor circuitry
4. Check the sensor tubes for erosion.
5. If the problem persists, contact Micro Motion. |
815 |
Priority: Maintenance - Fix Soon
Description:
The calculated amount of current output is outside of the linear range.
Recommended Actions:
1. Verify that mA output range values are set to appropriate values. |
816 |
Priority: Maintenance - Fix Soon
Description:
Non-zero HART address configured, or user has set the mA output to a fixed value.
Recommended Actions:
1. Check the HART address. If non-zero, set mA Output Action parameter to enable Live mA Output.
2. If mA output trim is being performed, exit mA output trim.
3. If mA output loop test is being performed, exit mA output loop test.
4. Check to see if the output has been fixed via digital communications or the local display. |
817 |
Priority: Advisory
Description:
Power has been removed and reapplied resulting in the reinstallations of the setup information.
Recommended Actions:
1. The first command to recognize this condition will automatically reset this flag.
2. This flag may also be set following a Master Reset or a Self Test. |
818 |
Priority: Maintenance - Fix Soon
Description:
A write or set command has been executed.
Recommended Actions:
1. No action required. |
819 |
Priority: Failed - Fix Now
Description:
A hardware error or failure has been detected by the device.
Recommended Actions:
1. This is a summary alert and is generated when one of the fault severity alerts is active. Resolve the other active alerts first. |
820 |
Factory zero has been restored. |
821 |
Smart Meter Verification will hold outputs at last value for about 2 minutes.
Press Next to Start or Cancel to End. |
822 |
Smart Meter Verification will hold outputs at fault value for about 2 minutes.
Press Next to Start or Cancel to End. |
823 |
Smart Meter Verification in progress: %{intSMVprogress}% complete |
824 |
Smart Meter Verification FAILED.
Meter may not meet factory specifications.
Recommended Action: Run Smart Meter Verification with outputs held at last measured value or fault. |
825 |
Smart Meter Verification FAILED.
Meter may not meet factory specifications.
Recommended Action: Immediately re-run the Smart Meter Verification test. If the meter passes the second test, the fail result can be ignored. If the meter fails the second test, the flow tubes may be damaged and should be investigated. |
826 |
Smart Meter Verification ABORTED.
Reason: %{0}
Recommended Action: Wait for 15 seconds before starting Smart Meter Verification again. |
827 |
The device is write protected, switch off the 'Security Switch' to disable write protection mode. |
828 |
Aborting due to field device error. |
829 |
Smart Meter Verification schedule is turned off. |
830 |
Can't abort verification,Smart Meter Verification already complete. |
831 |
Smart Meter Verification ABORTED.
Reason: User Initiated Abort
Recommended Action: Wait for 15 seconds before starting Smart Meter Verification again. |
832 |
Uploading Smart Meter Verification results from the device.
This will take a few minutes.
Uploading progress (19 total) : %{0} |
833 |
For Hours between Recurring Runs, valid range is 1 to 1000 hours or 0 for no recurring schedule. Please enter again. |
834 |
Uploading results data from device.
This will take a few minutes. |
835 |
Test Result #%{Datalog_Index}
Run Number: %0
Result: %1
Abort Code: %2
Time in Seconds: %3 |
836 |
Priority: Failed - Fix Now
Description:
Smart Meter Verification failed. The stiffness values not within acceptable limits.
Recommended Actions:
1. Immediately re-run the Smart Meter Verification test with outputs held at fault or last measured value. If the meter passes the second test, the fail result can be ignored. If the meter fails the second test, the flow tubes may be damaged.
2. Use the knowledge of your process to consider the type of damage and determine the appropriate action. These actions might include removing the meter from service and physically inspecting the tubes. At a minimum, perform a flow validation and a density calibration.
3. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
837 |
Smart Meter Verification Run Counter: %0
Transmitter Running Hours at Test: %1
Left Pickoff Stiffness: %2 |
838 |
Right Pickoff Stiffness: %0 |
839 |
Priority: Failed - Fix Now
Description:
Smart Meter Verification aborted.
Reason:
User Initiated Abort
Recommend Actions:
1. Wait for 15 seconds before starting Smart Meter Verification again.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
840 |
Priority: Failed - Fix Now
Description:
Smart Meter Verification aborted.
Reason:
Frequency Drift
Recommend Actions:
1. Ensure temperature, flow and density are stable and run Smart Meter Verification again.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
841 |
Priority: Failed - Fix Now
Description:
Smart Meter Verification aborted.
Reason:
High Drive Gain
Recommend Actions:
1. Ensure flow is steady and minimize entrained gas and run Smart Meter Verification again.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
842 |
Priority: Failed - Fix Now
Description:
Smart Meter Verification aborted.
Reason:
Unstable Flow
Recommend Actions:
1. Reduce flow rate and run Smart Meter Verification again.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
843 |
Priority: Failed - Fix Now
Description:
Smart Meter Verification aborted.
Reason:
No Air Reference
Recommend Actions:
1. Perform factory calibration on air.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
844 |
Priority: Failed - Fix Now
Description:
Smart Meter Verification aborted.
Reason:
No Water Reference
Recommend Actions:
1. Perform factory calibration on water.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
845 |
Priority: Failed - Fix Now
Description:
Smart Meter Verification aborted.
Reason:
Missing Configuration
Recommend Actions:
1. Load verification parameter registers with proper values.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
846 |
Priority: Failed - Fix Now
Description:
Smart Meter Verification aborted.
Reason:
Other
Recommend Actions:
1. Run Smart Meter Verification again.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
3. If abort persists, contact Micro Motion. |
847 |
Smart Meter Verification Run Counter: %0
Transmitter Running Hours at Test: %1
Abort Code: %2 |
848 |
Left Pickoff Stiffness: %0
Right Pickoff Stiffness: %1 |
849 |
LD Optimization is %0. |
850 |
LD Optimization: |
851 |
Next |
852 |
select1 |
853 |
Select Alert Number: |
854 |
Current severity is %0. |
855 |
%{1} is set to %{0}. |
856 |
A001: EEPROM Error (CP) is set to %0. |
857 |
A002: RAM Error (CP) is set to %0. |
858 |
A003: No Sensor Response is set to %0. |
859 |
A004: Temperature Overrange is set to %0. |
860 |
A005: Mass Flow Rate Overrange is set to %0. |
861 |
A006: Characterization Required is set to %0. |
862 |
A008: Density Overrange is set to %0. |
863 |
A009: Transmitter Initializing Warming Up is set to %0. |
864 |
A010: Calibration Failure is set to %0. |
865 |
A011: Zero Calibration Failed: Low is set to %0. |
866 |
A012: Zero Calibration Failed: High is set to %0. |
867 |
A013: Zero Calibration Failed: Unstable is set to %0. |
868 |
A014: Transmitter Failure is set to %0. |
869 |
A016: Sensor RTD Failure is set to %0. |
870 |
A017: T-Series RTD Failure is set to %0. |
871 |
A020: No Flow Cal Value is set to %0. |
872 |
A021: No K1 Value is set to %0. |
873 |
A029: PIC Daughterboard Comm Failure is set to %0. |
874 |
A030: Incorrect Board Type is set to %0. |
875 |
A031: Low Power is set to %0. |
876 |
A032: SMV: Outputs Fixed is set to %0. |
877 |
A033: No LPO RPO Signal is set to %0. |
878 |
A034: Smart Meter Verification Failed is set to %0. |
879 |
A035: Smart Meter Verification Aborted is set to %0. |
880 |
A100: MAO1 Saturated is set to %0. |
881 |
A101: MAO1 Fixed is set to %0. |
882 |
A102: Drive Overrange is set to %0. |
883 |
A103: Data Loss Possible is set to %0. |
884 |
A104: Calibration-In-Progress is set to %0. |
885 |
A105: Two-Phase Flow is set to %0. |
886 |
A106: Burst Mode Enabled is set to %0. |
887 |
A107: Power Reset Occurred is set to %0. |
888 |
A110: FO Saturated is set to %0. |
889 |
A111: FO Fixed is set to %0. |
890 |
A115: No External Data is set to %0. |
891 |
A118: DO1 Fixed is set to %0. |
892 |
A131: SMV in progress is set to %0. |
893 |
A132: Sensor Simulation Active is set to %0. |
894 |
Access Restricted |
895 |
Device is being reset, please wait. |
896 |
Device reset completed successfully. |
897 |
You are about to overwrite the device configuration with factory values. Before continuing, set the control loop for manual operation and ensure that existing configuration values are documented or saved to a file. If the device connection is lost, reconnect using the defaults. Proceed? |
898 |
Factory values were restored successfully. |
899 |
Priority: Advisory
The user has set the discrete output to a fixed state.
Recommended Actions:
1. Exit discrete output test.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |