0 |
Model |
1 |
.1f |
2 |
No specific error |
3 |
Field device specific error |
4 |
Update fail |
5 |
Access restricted |
6 |
A000: Undefined |
7 |
A001: EEPROM Error (CP) |
8 |
A002: RAM Error (CP) |
9 |
A003: No Sensor Response |
10 |
A004: Temperature Overrange |
11 |
A005: Mass Flow Rate Overrange |
12 |
A006: Characterization Required |
13 |
A007: Real-Time Interrupt Failure |
14 |
A008: Density Overrange |
15 |
A009: Transmitter Initializing/Warming Up |
16 |
A010: Calibration Failure |
17 |
A011: Zero Calibration Failed: Low |
18 |
A012: Zero Calibration Failed: High |
19 |
A013: Zero Calibration Failed: Unstable |
20 |
A014: Transmitter Failure |
21 |
A015: MA Readback Error |
22 |
A016: Sensor RTD Failure |
23 |
A017: T-Series RTD Failure |
24 |
A018: EEPROM Error (Xmtr) |
25 |
A019: RAM Error (Xmtr) |
26 |
A020: No Flow Cal Value |
27 |
A021: No K1 Value |
28 |
A022: Config DB Corrupt (CP) |
29 |
A023: Internal Totals Corrupt (CP) |
30 |
A024: Program Corrupt (Core Processor) |
31 |
A025: Boot Sector Fault (CP) |
32 |
A026: Sensor/Transmitter Communications Failure |
33 |
A027: Security Breach |
34 |
A028: Core Processor Write Failure |
35 |
A029: PIC/Daughterboard Comm Failure |
36 |
A030: Incorrect Board Type |
37 |
A031: Low Power |
38 |
A032: MV: Outputs to Fault |
39 |
A033: No LPO/RPO Signal |
40 |
A034: Undefined |
41 |
A035: Undefined |
42 |
A036: Undefined |
43 |
A037: Undefined |
44 |
A038: Undefined |
45 |
A039: Undefined |
46 |
A100: MAO1 Saturated |
47 |
A101: MAO1 Fixed |
48 |
A102: Drive Overrange |
49 |
A103: Data Loss Possible |
50 |
A104: Calibration-In-Progress |
51 |
A105: Slug Flow |
52 |
A106: Burst Mode Enabled |
53 |
A107: Power Reset Occurred |
54 |
A108: Single-Setpoint Event 1 ON |
55 |
A109: Single-Setpoint Event 2 ON |
56 |
A110: Frequency Output Saturated |
57 |
A111: Frequency Output Fixed |
58 |
A112: Upgrade Transmitter Software |
59 |
A113: mA Output 2 Saturated |
60 |
A114: mA Output 2 Fixed |
61 |
A115: No External Data |
62 |
A116: API: Temperature Overrange |
63 |
A117: API: Density Overrange |
64 |
A118: Discrete Output 1 Fixed |
65 |
A119: Discrete Output 2 Fixed |
66 |
A120: Enhanced Density: Curve Fit Failure |
67 |
A121: ED: Extrapolation Alert |
68 |
A122: Discrete Output 3 Fixed |
69 |
A123: DO4 Fixed |
70 |
A124: Frequency Input Saturated |
71 |
A125: Batch Timeout |
72 |
A126: Batch Overrun |
73 |
A127: Batch No Reset |
74 |
A128: Batch/Fill No Start |
75 |
A129: PPI Display Error |
76 |
A130: Printer Out of Paper |
77 |
A131: Meter Verification: Outputs to Last Measured Value |
78 |
A132: Sensor Simulation Active |
79 |
A133: PIC UI EEPROM Error |
80 |
A134: PPI Memory Error |
81 |
A135: PPI Communication Error |
82 |
A136: Undefined |
83 |
A137: Undefined |
84 |
A138: Undefined |
85 |
A139: Undefined |
86 |
D1 Calibration In Progress |
87 |
D2 Calibration In Progress |
88 |
D3 Calibration In Progress |
89 |
D4 Calibration In Progress |
90 |
FD Calibration In Progress |
91 |
Zero Calibration In Progress |
92 |
Temperature Slope Calibration In Progress |
93 |
Temperature Offset Calibration In Progress |
94 |
Discrete Event 1 Active |
95 |
Discrete Event 2 Active |
96 |
Discrete Event 3 Active |
97 |
Discrete Event 4 Active |
98 |
Discrete Event 5 Active |
99 |
Discrete Output 1 Active |
100 |
Discrete Output 2 Active |
101 |
Discrete Output 3 Active |
102 |
Discrete Input 1 Active |
103 |
Discrete Input 2 Active |
104 |
Undefined |
105 |
Field Device Variable- Digital measurement that changes with respect to time without user intervention. |
106 |
Too few data bytes received |
107 |
In 'Write Protect' mode |
108 |
Invalid unit |
109 |
Enter mA Measurement Point |
110 |
The range of the mA output on the Model 2200S is 12-20 mA. If an adapter-barrier is installed, the range is converted to 4-20 mA. Specify the mA measurement point so that the mA output data can be reported correctly. If you specify Don't Know, data will be reported for both spans. |
111 |
Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. |
112 |
8d |
113 |
mA Output Alarm Type |
114 |
High |
115 |
Low |
116 |
None |
117 |
Transfer Function |
118 |
Mass Flow Rate |
119 |
Current mass flow rate as calculated from external volume flow rate. |
120 |
.2f |
121 |
.3f |
122 |
.4f |
123 |
.5f |
124 |
The mass flow rate below which the frequency/pulse output indicates zero flow,and below which totalizers stop counting. Cutoffs can also be configured for the mA output(s) (the mA output cutoffs). An mA output cutoff is active only if the process variable assigned to the output is mass flow or volume flow. |
125 |
4.2f |
126 |
mA Output Upper Limit |
127 |
mA output Lower Endpoint Value- Defines the lower endpoint, of the respective mA output, for normal operating conditions. |
128 |
mA Output Lower Limit |
129 |
mA Output Added Damping Value- Damping time constant applied the mA output. The units of this variable are always in seconds. |
130 |
Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. |
131 |
Mass Flow Lower Range Value |
132 |
Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective mA output. The units of this variable are always in seconds. |
133 |
Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. |
134 |
Mass Flow Upper Sensor Limit |
135 |
8.2f |
136 |
Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. |
137 |
Mass Flow Lower Sensor Limit |
138 |
Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. |
139 |
Mass Flow Minimum Span |
140 |
Damping |
141 |
Sensor Unit |
142 |
mA Output Cutoff |
143 |
Mass Total Unit |
144 |
Density |
145 |
The density of the liquid being measured. |
146 |
.6f |
147 |
Current volume flow rate from an external device. |
148 |
Volume Flow Rate |
149 |
The volume flow rate below which the frequency/pulse output indicates zero flow,and below which totalizers stop counting. Cutoffs can also be configured for the mA output(s) (the mA output cutoffs). An mA output cutoff is active only if the process variable assigned to the output is mass flow or volume flow. |
150 |
Volume Flow Lower Range Value |
151 |
Volume Flow Upper Sensor Limit |
152 |
10.4f |
153 |
Volume Flow Lower Sensor Limit |
154 |
Volume Flow Minimum Span |
155 |
Volume Flow Total Unit |
156 |
Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit. |
157 |
Pressure value from an external device. |
158 |
Drive gain is the amount of current required to drive the vibrating element, expressed as a percentage of the maximum allowable drive gain. |
159 |
6.2f |
160 |
Upper Range Value (20mA) |
161 |
Temperature value from an external device. |
162 |
NLPD |
163 |
NLPH |
164 |
NLPM |
165 |
NLPS |
166 |
Nm3/day |
167 |
Nm3/hr |
168 |
Nm3/min |
169 |
Nm3/sec |
170 |
SCFD |
171 |
SCFH |
172 |
SCFM |
173 |
SCFS |
174 |
SLPD |
175 |
SLPH |
176 |
SLPM |
177 |
SLPS |
178 |
Sm3/day |
179 |
Sm3/hr |
180 |
Sm3/min |
181 |
Sm3/sec |
182 |
Gas Volume Flow |
183 |
Meter Temperature: T-Series |
184 |
Input voltage is the current power input. |
185 |
Core Processor Input Voltage |
186 |
Temperature |
187 |
Primary Variable |
188 |
Secondary Variable |
189 |
Third Variable |
190 |
Fourth Variable |
191 |
ANSI 150 |
192 |
ANSI 300 |
193 |
ANSI 600 |
194 |
PN40 |
195 |
JIS 10K |
196 |
JIS 20K |
197 |
ANSI 900 |
198 |
Sanitary clamp fitting |
199 |
Union |
200 |
PN100 |
201 |
Unknown |
202 |
Tube Lining |
203 |
Tube Wetted Material |
204 |
Hast-C |
205 |
Monel |
206 |
Tantalum |
207 |
Titanium |
208 |
316L SST |
209 |
Inconel |
210 |
Base Unit |
211 |
Base Time |
212 |
Conversion Factor |
213 |
Flow Label |
214 |
Total Label |
215 |
Forward |
216 |
Reverse |
217 |
5.4f |
218 |
5.2f |
219 |
Flow Cal |
220 |
The mass or volume flow rate below which is a mA output representing flow indicates zero flow. |
221 |
mA Output Flow Rate Cutoff |
222 |
Start |
223 |
Stop |
224 |
Reset |
225 |
5d |
226 |
5.5f |
227 |
µsec |
228 |
6.5f |
229 |
Fault Timeout |
230 |
2d |
231 |
Downscale: mA outputs that indicate flow go to the configured limit. Upscale: mA outputs go to the configured limit. Internal zero: Flow outputs indicate zero flow. |
232 |
Fault Action |
233 |
Upscale |
234 |
Downscale |
235 |
Fault Level (Adapter-Barrier) |
236 |
Digital Communications Fault Action |
237 |
1d |
238 |
Reference temperature |
239 |
mA Output 1 Cutoff |
240 |
Cutoff Type |
241 |
11.5f |
242 |
8.3f |
243 |
Pickoff amplitude indicates the distance that the vibrating element is traveling from its resting state. |
244 |
Drive Gain |
245 |
Live Zero Flow Rate |
246 |
RTD Cable Resistance |
247 |
T-Series RTD Resistance |
248 |
Line RTD Resistance |
249 |
The resistance of the line RTD. |
250 |
'Power On Time' is the number of seconds since the last power cycle. |
251 |
Power On Time |
252 |
7.2f |
253 |
Scroll Time (1-30) |
254 |
Passcode (4 Digits) |
255 |
4d |
256 |
Refresh Rate (100-10,000) |
257 |
On |
258 |
Option Model Number |
259 |
2500 Config I/O |
260 |
9.8f |
261 |
10.7f |
262 |
Pressure Compensation |
263 |
Compensation Pressure |
264 |
External Temperature |
265 |
Correction Temperature |
266 |
Engineer to Order Number |
267 |
Meter Verification |
268 |
Alarm Number |
269 |
3d |
270 |
Information |
271 |
Coil |
272 |
Disabled |
273 |
Enabled |
274 |
Gas Reference Density |
275 |
Reference density of the gas being measured. |
276 |
SL |
277 |
Sm3 |
278 |
Specifies the lowest gas standard volume flow rate that will be reported as measured. All gas standard volume flow rates below this cutoff are reported as 0. |
279 |
Simulate Primary Purpose Variables |
280 |
Control |
281 |
Ramp Low Point |
282 |
Ramp High Point |
283 |
Ramp Period |
284 |
Time is measured in terms of time elapsed since trasmitter has been switched on first time. |
285 |
A001: EEPROM Error (Core Processor) |
286 |
A002: RAM Error (Core Processor) |
287 |
A006: Characterization Required |
288 |
A020: No Flow Calibration Value |
289 |
A022: Configuration Database Corrupt (Core Processor) |
290 |
A023: Internal Totals Corrupt (Core Processor) |
291 |
A025: Boot Sector Fault (Core Processor) |
292 |
A029: PIC/Daughterboard Communication Failure |
293 |
A032: Meter Verification: Outputs to Fault |
294 |
A033: No Right/Left Pickoff Signal |
295 |
A100: mA Output 1 Saturated |
296 |
A101: mA Output 1 Fixed |
297 |
The version of the Device Description (DD) being used. |
298 |
Keep Existing Assignment |
299 |
Perform Auto Zero |
300 |
First Point |
301 |
Second Point |
302 |
Third Point |
303 |
Fourth Point |
304 |
Flowing Density |
305 |
Fix mA Output- Allows the User to manually manipulate a selected mA output to a selected constant output value. |
306 |
mA Output 1 Fault value |
307 |
mA Output Trim |
308 |
Digital to Analog Trim- Allows the calibration of a selected mA output with an external reference at the operating endpoints of the mA output. |
309 |
Reset All |
310 |
Reset Total |
311 |
Change Alert Severity |
312 |
Read Modbus Data |
313 |
Write Modbus Data |
314 |
Leaving fixed current mode |
315 |
Leaving Fixed Current Mode- Takes the selected mA output out of a mode where the output was a constant value, and returns the output to a mode where the output then tracks the input. |
316 |
Sensor |
317 |
Configure the transmitter for sensor characteristics. |
318 |
Configure channels, inputs, outputs, map variables, and communication settings. |
319 |
Special Units |
320 |
Configure the parameters required to convert an existing measurement unit to a different unit. |
321 |
External Pressure/Temperature |
322 |
Configure polled connections to an external temperature or pressure transmitter. |
323 |
Configure the transmitter for gas standard volume measurement. |
324 |
Configure the process monitor screens by selecting the desired variables for each screen. |
325 |
No Additional Information for Above |
326 |
Additional Information for Above |
327 |
A004: Temperature Overrange |
328 |
A006: Characterization Required |
329 |
A008: Density Overrange |
330 |
A009: Transmitter Initializing/Warming Up |
331 |
A011: Zero Calibration Failed: Low |
332 |
A012: Zero Calibration Failed: High |
333 |
A013: Zero Calibration Failed: Unstable |
334 |
A020: No Flow Calibration Value |
335 |
A029: PIC/Daughterboard Communication Failure |
336 |
A100: mA Output Saturated |
337 |
A101: mA Output Fixed |
338 |
Primary Variable Out of Limits |
339 |
Non-Primary Variable Out of Limits |
340 |
Primary Variable mA Output Saturated |
341 |
Primary Variable mA Output Fixed |
342 |
Write Protect |
343 |
Device Reset |
344 |
Restore Factory Configuration |
345 |
GetHealthStatus |
346 |
Invalid flange type |
347 |
Invalid liner material code |
348 |
Invalid sensor material code |
349 |
Invalid base mass time unit |
350 |
Invalid base flow unit |
351 |
Invalid selection |
352 |
Invalid base volume time unit |
353 |
Invalid base volume flow unit |
354 |
Incorrect format |
355 |
Temperature correction factor out of range |
356 |
Zero Pressure Correction Point too low |
357 |
Online |
358 |
Overview |
359 |
Configure |
360 |
Service Tools |
361 |
Routine Maintenance |
362 |
Variables |
363 |
Totalizers |
364 |
Totalizer |
365 |
All Totalizers |
366 |
Volume |
367 |
Inputs/Outputs Fault Actions |
368 |
Alert Severity |
369 |
GSV |
370 |
Special Units |
371 |
Mass Special Units |
372 |
Volume Special Units |
373 |
Density Parameters |
374 |
Sensor |
375 |
Electronics |
376 |
Zero |
377 |
Identification |
378 |
Revisions |
379 |
Display |
380 |
Specify the number of decimal places to be shown on the display. |
381 |
Process Variables |
382 |
Totalizer Variables |
383 |
Diagnostic Variables |
384 |
Perform a zero calibration which sets a zero reference for a no-flow condition. |
385 |
Display Variable Menu Features |
386 |
mA Output Fault Settings |
387 |
Hot key |
388 |
F: EEPROM Error (CP) |
389 |
F: RAM Error (CP) |
390 |
F: No Sensor Response |
391 |
F: Temperature Overrange |
392 |
Additional Information |
393 |
F: Mass Flow Rate Overrange |
394 |
F: Characterization Required |
395 |
F: Density Overrange |
396 |
View Density Characterization |
397 |
F: Transmitter Initializing/Warming Up |
398 |
F: Calibration Failure |
399 |
F: Zero Calibration Failed: Low |
400 |
F: Zero Calibration Failed: High |
401 |
F: Zero Calibration Failed: Unstable |
402 |
F: Transmitter Failure |
403 |
F: Sensor RTD Failure |
404 |
F: T-Series RTD Failure |
405 |
F: No Flow Calibration Value |
406 |
F: No K1 Value |
407 |
F: PIC/Daughterboard Communication Failure |
408 |
F: Incorrect Board Type |
409 |
F: Low Power |
410 |
F: No Right/Left Pickoff Signal |
411 |
View Slug Flow Condition |
412 |
A: mA Output Saturated |
413 |
A: mA Output Fixed |
414 |
M: Drive Overrange |
415 |
A: Calibration In Progress |
416 |
M: Slug Flow |
417 |
View Diagnostic Variables |
418 |
Additional |
419 |
A: Burst Mode Enabled |
420 |
M: Power Reset Occurred |
421 |
A: Sensor Simulation Active |
422 |
M: EEPROM Error (Display) |
423 |
M: Primary Variable Out of Limits |
424 |
M: Non-Primary Variable Out of Limits |
425 |
M: Primary Variable mA Output Saturated |
426 |
M: Primary Variable mA Output Fixed |
427 |
M: Cold Start |
428 |
M: Field Device Malfunction |
429 |
Security |
430 |
Reset/Restore |
431 |
Calibration |
432 |
Process Var Charts |
433 |
Primary Variable |
434 |
3rd Variable |
435 |
4th Variable |
436 |
|
437 |
GSV Flow Rate |
438 |
Current (Adapter-Barrier) |
439 |
Secondary Variable |
440 |
Tertiary Variable |
441 |
Quarternary Variable |
442 |
Enable or Disable write protect mode |
443 |
Configures the transmitter for sensor characteristics. |
444 |
Configures map variables and primary output settings. |
445 |
Sets fixed output value for the mA output. |
446 |
Performs digital to analog trim of mA output. |
447 |
Performs auto zero or restore factory zero. |
448 |
The DensCal Factor field on the old style sensor tag contains the K1, K2 and TC values.
The first 5 characters are K1, the second 5 characters are K2 and the remaining characters are TC. |
449 |
Any changes made on this screen will be written to the device when the next button is clicked and could affect transmitter operation.Click next to write changes to the device,or click cancel to abort. |
450 |
The 'First Miliamp Output' uses the 'Primary Variable' as its source. |
451 |
The 'Secondary Variable' is only used in HART communications. |
452 |
The 'Third Variable' is only used in HART communications. |
453 |
The 'Fourth Variable' is only used in HART communications. |
454 |
Advisory |
455 |
Analog Output Information |
456 |
Sensor Model |
457 |
Diagnostics |
458 |
Enters an Alert number and change the Alert's severity to Fault, Information or Ignore. |
459 |
Enters an Alert number and view the current severity of the alert. |
460 |
Configures the Process Monitor Screens by selecting the desired process variables for each screen. |
461 |
Configures the number of decimal places for each process variable. |
462 |
Assigns a variable to the mA output, define upper and lower range values, cutoff and damping. |
463 |
Sets up Bell-202 port settings. |
464 |
Assigns variables to primary (PV), secondary (SV), third (TV) and fourth (4V) variables. |
465 |
Set Up Bell 202 Port |
466 |
This screen will not automatically refresh after changing the 'Type' field. Select Guided Setup and then return to this screen to see the current configuration. |
467 |
Optional Setup |
468 |
Standard Gas Volume |
469 |
|
470 |
All Variables |
471 |
Input/Output |
472 |
T-Series Config |
473 |
HART Burst Mode |
474 |
Field Device Variables |
475 |
The Temperature Calibration Factor is a 14 character string that contains two real numbers.
The first number, before the "T", is the slope.
The slope must be a positive real number containing 7 characters (including the decimal point).
The "T" is a delimiter and must be present.
The second number, after the "T", is the offset.
The offset must be a real number containing 7 characters (including the decimal point and negative sign if present).
The offset must be between -10 and +10. |
476 |
Performs first point (air) calibration. |
477 |
Performs second point (water) calibration. |
478 |
Performs third point (user's choice) calibration. |
479 |
Performs fourth point (user's choice) calibration. |
480 |
Performs flowing density calibration. |
481 |
Status |
482 |
Tag, model code, revision, security, and related data. |
483 |
Control and configure totalizers and inventories. |
484 |
Trend charts for process and diagnostic variables. |
485 |
Revision Numbers |
486 |
Displays values of process variables and outputs. |
487 |
Note:-Fault Level range for Direct (12-20mA)
:Downscale 11.5mA to 11.8mA
: Upscale 20.5mA to 22.0mA |
488 |
Note:-Fault Level range for Adapter-Barrier (4-20mA)
:Downscale 3.0mA to 3.6mA
:Upscale 21.0mA to 24.0mA |
489 |
Reads modbus register values. |
490 |
Writes modbus register values. |
491 |
Displays a trend chart for mass flow rate. |
492 |
Displays a trend chart for volume flow rate. |
493 |
Displays a trend chart for gas standard volume flow rate. |
494 |
Simulation Configuration |
495 |
Mass Flow Rate Simulation Settings |
496 |
Density Simulation Settings |
497 |
Temperature Simulation Settings |
498 |
Simulation Settings |
499 |
2nd Variable Information |
500 |
Continuity failure of drive circuit Left PickOff,Right PickOff or Left PickOff-Right PickOff mismatch when driving. |
501 |
Recommended Actions:
1. Check for 'Slug Flow'.
2.View the diagnostic vaiables to verify whether tubes are vibrating.Left and Right pickoffs should be above 10mV.
3. Check the sensor circuitry.
4. Check sensor tubes for plugging.
5.If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
6. If the problem persists, contact Micro Motion. |
502 |
Recommended Actions:
1. Verify that a sensor is connected to the transmitter.
2. Check the sensor RTD circuitry.
3. Verify that process temperature is within range of sensor and transmitter.
4. If the problem persists, contact Micro Motion. |
503 |
Recommended Actions:
1. If other alerts are present (typically A003, A006, A008, A102 or A105), resolve those alerts first. If the A005 alert persists, continue with the suggestions below.
2. View the diagnostic variables to verify whether tubes are vibrating. Left and Right pickoffs should be above 10mV.
3. Check the sensor circuitry.
4. Check the sensor tubes for erosion by verifying density.
5. If the problem persists, contact Micro Motion. |
504 |
Recommended Actions:
1. Check the characterization. Specifically, verify the 'Flow Cal' and 'K1' values with the values on the sensor tag.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
3. If the problem persists, contact Micro Motion. |
505 |
Recommended Actions:
1. Check the characterization. Specifically, verify the Flow FCF and K1 values on the sensor tag.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
3. If the problem persists, contact Micro Motion. |
506 |
The measured 'Density' is below 0 g/cm3 or above 10 g/cm3. |
507 |
Recommended Actions:
1. If other alerts are present (typically A003, A006, A033, A102 or A105) resolve those alerts first. If the A008 alert persists, continue with the suggestions below.
2. Verify process. Check for air in the flow tubes, tubes not filled, foreign material in tubes, or coating in tubes.
3. Check the sensor circuitry.
4. Verify density characterization and verify configuration matches sensor tag.
5 View diagnostic variables to verify raw tube frequency is in the proper range for the sensor type.
6. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
7. If the problem persists, contact Micro Motion. |
508 |
Recommended Actions:
1. If 'A26' also appears, resolve the 'A26' first.
2. Allow the flowmeter to warm up (approximately 30 seconds). The error should disappear once the flowmeter is ready for normal operation.
3. Make sure the transmitter is receiving sufficient power.
4. If alert does not clear, make sure that the sensor is completely full or completely empty.
5. Check the sensor circuitry.
6. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
509 |
Recommended Actions:
1. If alert appears during a transmitter zero, ensure that there is no flow through the sensor, then retry.
2. Cycle power to the flowmeter to clear the alert.
3. If appropriate, restore the factory zero to return the flowmeter to operation.
4. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
5. If alert appears during a density calibration, contact Micro Motion. |
510 |
Mechanical Zero: The resulting zero was greater than 3 microseconds. |
511 |
Internal memory or program fault has been detected. |
512 |
Recommended Actions:
1. Resolve other active alerts first.
2. Cycle power to the flowmeter.
3. If alert persists, the transmitter might need service. Contact Micro Motion. |
513 |
Recommended Actions:
1. Check the sensor RTD circuitry.
2. Verify that process temperature is within range of sensor and transmitter.
3. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
4. If the problem persists, contact Micro Motion. |
514 |
The 'Flow Calibration Factor' and/or 'K1' has not been entered since the last master reset. |
515 |
Recommended Actions:
1. Check the characterization against the sensor tag. Specifically, verify the 'Flow Cal','K1' and 'K2' values.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
3. If the problem persists, contact Micro Motion. |
516 |
Recommended Actions:
1. Check the characterization against the sensor tag. Specifically, verify the 'Flow FCF','K1' and 'K2' values.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
3. If the problem persists, contact Micro Motion. |
517 |
The sensor is recognized as a straight tube but the 'K1' value indicates a curved tube,or vice versa. |
518 |
Recommended Actions:
1. If 'A017' is active, resolve it first.
2. Check the characterization against the sensor tag. Specifically, verify the 'Flow FCF','K1' and 'K2' values.
3. Check the sensor RTD circuitry.
4. If the problem persists, contact Micro Motion. |
519 |
Recommended Actions:
1. Verify the core processor input voltage is at least 12V.
2. Check the power supply and all power wiring. |
520 |
No signal from 'Left Pickoff' or 'Right Pickoff',suggesting that sensor tubes are not vibrating. |
521 |
Recommended Actions:
1. Check for 'Slug Flow'.
2. View the diagnostic variables to verify whether tubes are vibrating. Left and Right pickoffs should be above 10mV.
3. Check the sensor circuitry.
4. Check sensor tubes for plugging.
5. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
6. If the problem persists, contact Micro Motion. |
522 |
Recommended Actions:
1. Verify that Lower Range Value and Upper Range Value are set correctly for the process variable and the process.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
523 |
Non-zero 'HART Address' configured,or user has set the mA output to a fixed value. |
524 |
Recommended Actions:
1. Check the 'HART Address'. If non-zero, set 'mA Output Action' parameter to enable 'Live mA Output' or if multi-drop mode is desired change the alert severity to ignore by going to the Configure-> Alert Setup-> Alert Severity screen.
2. If mA output trim is being performed, exit mA output trim.
3. If mA output loop test is being performed, exit mA output loop test.
4. Check to see if the output has been fixed via digital communications or the local display. |
525 |
Recommended Actions:
1. Check the drive gain and pickoff voltage..
2. Check for foreign material in the process gas or fluid,coating,or other problems.
3. Check for fluid sepearation by monitoring the density value and comparing the results against expected density values.
4.Ensure that the sensor orientation is appropriate for your application.Settling from a two-phase or three-phase fluid can cause this alert.
5.Check the sensor circuitry.
6.If this is the only active alarm, it can be ignored. If desired, reconfigure the alarm severity to Ignore.
7.If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
526 |
Recommended Actions:
1. Allow the flowmeter to complete calibration.
2. For zero calibration procedures, you may abort the calibration, set the zero time parameter to a lower value, and restart the calibration.
3. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
527 |
The 'Density' has exceeded the user-defined 'Slug Flow'(density) limits. |
528 |
Recommended Actions:
1. Check that sensor tubes are completely filled.
2. Check that 'Slug Flow' limits are set to appropriate values.
3. Verify density cutoff is at least 0.2 g/cc.
4. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
529 |
Recommended Actions:
1. No action required.
2. If desired, reconfigure the alert severity to Ignore by going to the Configure-> Alert Setup-> Alert Severity screen. |
530 |
Recommended Actions:
1. No action required.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
531 |
Recommended Actions:
1. Disable output simulation.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
532 |
Recommended Actions:
1. Verify process and check for 'Slug Flow'.
2. Check the diagnostic variables.
3. Check the sensor circuitry.
4. Check the sensor tubes for erosion.
5. If the problem persists, contact Micro Motion. |
533 |
Recommended Actions:
1. Verify process and check for 'Slug Flow'.
2. Check the test points.
3. Check the sensor circuitry.
4. Check the sensor tubes for erosion.
5. If the problem persists,contact Micro Motion. |
534 |
Recommended Actions:
1. Verify that mA output range values are set to appropriate
values. |
535 |
Recommended Actions:
1. Check the 'HART Address'. If non-zero, set 'mA Output Action' parameter to enable 'Live mA Output'.
2. If mA output trim is being performed, exit mA output trim.
3. If mA output loop test is being performed, exit mA output loop test.
4. Check to see if the output has been fixed via digital communications or the local display. |
536 |
Recommended Actions:
1. This is a summary alert and is generated when one of the fault severity alerts is active. Resolve the other active alerts first. |
537 |
Density Characterization |
538 |
Slug Flow Condition |
539 |
Electronic Conditions |
540 |
Recommended Actions:
1. Cycle power to the flow meter.
2. The flow meter might need service. Contact Micro Motion. |
541 |
Sensor Conditions |
542 |
Process Conditions |
543 |
Configuration Conditions |
544 |
Recommended Actions:
1. Cycle power to the flowmeter.
2. Contact Micro Motion. |
545 |
Recommended Actions:
1. Contact Micro Motion. |
546 |
Recommended Actions:
1. The first command to recognize this condition will automatically reset this flag.
2. This flag may also be set following a Master Reset or a Self Test. |
547 |
Classic View |
548 |
Power-cycle the device without affecting device configuration. |
549 |
Overwrite the existing device configuration with the configuration set at the factory. |
550 |
Manually resets the configuration changed flag if the host is not able to reset the flag automatically. |
551 |
Performs a zero calibration. |
552 |
Performs a density calibration. |
553 |
Performs a temperature calibration. |
554 |
Offline |
555 |
FMU860 |
556 |
DT |
557 |
DVC |
558 |
FCX |
559 |
AS800 |
560 |
340T |
561 |
340C |
562 |
344 |
563 |
Siemens Micro K |
564 |
SITRANS L |
565 |
SIPAN PH |
566 |
SITRANS P |
567 |
75SMT |
568 |
UNIDELTA |
569 |
8320 |
570 |
SX5100 |
571 |
TSV175 |
572 |
DMU |
573 |
3780 |
574 |
BM70 |
575 |
8u |
576 |
low |
577 |
high |
578 |
tmp_av |
579 |
'Configuration Changed Flag' is being reset, please wait... |
580 |
'Configuration Changed Flag' has been reset. |
581 |
Changing configuration can affect transmitter operation. Ensure that the control loop is set for manual operation before continuing. |
582 |
Warning- Take the device out of process control loop. |
583 |
Device is in process control loop.;Device is out of process control loop. |
584 |
Enter 'Zero Time': |
585 |
Zero calibration is starting... |
586 |
Auto Zero failed.
Zero: %{0}
Standard Deviation: %{1} |
587 |
Factory zero has been restored. |
588 |
Enter Density: |
589 |
NOTE- Flow rate must be greater than 50% of the nominal flow for the meter. |
590 |
Specify 'mA Output Level (Adapter-Barrier)': |
591 |
Specify 'mA Output Level (Direct)': |
592 |
Output Value (mA): |
593 |
fixedValue |
594 |
'mA Output (Adapter-Barrier)' is fixed at %0 mA. |
595 |
'mA output (Direct)' is fixed at %0 mA. |
596 |
Connect reference meter to the 'mA Output' of the Adapter-Barrier. |
597 |
About to set 'mA Output' at Adapter-Barrier to 4.00 mA.
Note: The 'mA Output' at the transmitter will be set to 12.00 mA. |
598 |
Connect reference meter to the 'mA Output' of the transmitter. |
599 |
About to set 'mA Output' at transmitter to 12.00 mA. |
600 |
Enter 'Meter Value': |
601 |
Is 'mA Output' from the Adapter-Barrier equal to reference meter? |
602 |
Yes;No |
603 |
Is 'mA Output' directly from transmitter equal to reference meter? |
604 |
All totalizers have been started. |
605 |
All totalizers have been stopped. |
606 |
All totalizers have been reset. |
607 |
'Mass Total' has been reset. |
608 |
'Volume Total' has been reset. |
609 |
'Gas Standard Volume Total' has been reset. |
610 |
Event 1 Triggered: Yes |
611 |
Event 1 Triggered: No |
612 |
Event 2 Triggered: Yes |
613 |
Event 2 Triggered: No |
614 |
alarmNum |
615 |
All alerts are acknowledged. |
616 |
Selection for data type: |
617 |
Enter 'Coil Number': |
618 |
number |
619 |
Enter 'Register Number': |
620 |
'Coil Mode' is %0 and 'Exception Code' is %1. |
621 |
'Unsigned 16 Value' is %0 and 'Exception Code' is %1. |
622 |
'Unsigned 32 Value' is %0 and 'Exception Code' is %1. |
623 |
'Floating Point Value' is %[f]{0} and 'Exception Code' is %1. |
624 |
Coil Mode: |
625 |
Enter 'Unsigned 16 Value:' |
626 |
uValue |
627 |
Enter 'Unsigned 32 Value:' |
628 |
Enter 'Floating Point Value': |
629 |
fValue |
630 |
Select the 'Simulation Mode': |
631 |
select |
632 |
'Simulation Mode' is %0. |
633 |
Parameters are being updated, please wait... |
634 |
Current sensor type selection is Other (Curved Tube).
Select 'Sensor Type': |
635 |
Current sensor type selection is T-Series (Straight Tube).
Select 'Sensor Type': |
636 |
Current Primary Variable Selection is %0
Select Primary Variable: |
637 |
View 'Alert Severity' of: |
638 |
Priority: Failed - Fix Now
Description:
An uncorrectable checksum mismatch has been detected.
Recommended Actions:
1. Cycle power to the flow meter.
2. The flow meter might need service. Contact Micro Motion. |
639 |
No Additional Information Available |
640 |
Priority: Failed - Fix Now
Description:
ROM checksum error or a RAM location cannot be written to the transmitter.
Recommended Actions:
1. Cycle power to the flowmeter.
2. The flow meter might need service. Contact Micro Motion. |
641 |
Priority: Failed - Fix Now
Description:
Continuity failure of drive circuit Left Pickoff ,Right Pickoff or Left Pickoff-Right Pickoff mismatch when driving.
Recommended Actions:
1. Check for 'Slug Flow'.
2. View the diagnostic variables to verify whether tubes are vibrating.Left and Right Pickoffs should be above 10mV.
3. Check the sensor circuitry.
4. Check sensor tubes for plugging.
5. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
6. If the problem persists, contact Micro Motion. |
642 |
Drive Gain:
Value %0 |
643 |
Priority: Failed - Fix Now
Description:
The value computed for the resistance of the line RTD or the Meter/Case RTD is outside limits.
Recommended Actions:
1. Verify that a sensor is connected to the transmitter.
2. Check the sensor RTD circuitry.
3. Verify that process temperature is within range of sensor and transmitter.
4. If the problem persists, contact Micro Motion |
644 |
Temperature:
Value %0 |
645 |
Priority: Failed - Fix Now
The measured flow has exceeded the maximum flow rate of the sensor.
Recommended Actions:
1. If other alerts are present (typically A003, A006, A008, A102, or A105), resolve those alerts first. If the A005 alert persists, continue with the suggestions below.
2. View the diagnostic variables to verify whether tubes are vibrating. Left and Right pickoffs should be above 10mV.
3. Check the sensor circuitry.
4. Check the sensor tubes for erosion by verifying density.
5. If the problem persists, contact Micro Motion. |
646 |
Priority: Failed - Fix Now
Description:
One or more required characterization parameters have not been entered or incorrect.
Recommended Actions:
1. Check the characterization. Specifically, verify the 'Flow Cal' and 'K1' values with the values on the sensor tag.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
3. If the problem persists, contact Micro Motion. |
647 |
Flow Cal:
Value %0
K1:
Value %1 uSec
K2:
Value %2 uSec |
648 |
Priority: Failed - Fix Now
Description:
One or more required characterization parameters have not been entered or incorrect.
Recommended Actions:
1. Check the characterization. Specifically, verify the 'Flow FCF' and 'K1' values with the values on the sensor tag.
2. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
3. If the problem persists, contact Micro Motion. |
649 |
Flow FCF:
Value %0
K1:
Value %1 uSec
K2:
Value %2 uSec |
650 |
Priority: Failed - Fix Now
Description:
The measured 'Density' is below 0g/cm3 or above 10 g/cm3.
Recommended Actions:
1. If other alerts are present (typically A003, A006, A033, A102 or A105) resolve those alerts first. If the A008 alert persists, continue with the suggestions below.
2. Verify process. Check for air in the flow tubes, tubes not filled, foreign material in tubes, or coating in tubes.
3. Check the sensor circuitary.
4. Verify 'Density'characterization and verify configuration matches sensor tag.
5. View diagnostic variables to verify raw tubes frequency is in the proper range for the sensor type.
6. If you want to change the alert severity.go to the Configure-> Alert Setup-> Alert Severity screen.
7. If the problem persists, contact Micro Motion |
651 |
Priority: Failed - Fix Now
Description:
Transmitter in power-up mode.
Recommended Actions:
1. If'A26' also appears,resolve the 'A26' first.
2. Allow the flowmeter to warm up (approximately 30 seconds). The error should disappear once the flowmeter is ready for normal operation.
3. Make sure the transmitter is receiving sufficient power.
4. If alert does not clear, make sure that the sensor is completely full or completely empty.
5. Check the sensor circuitry.
6. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen. |
652 |
Priority: Failed - Fix Now
Description:
Mechanical zero: The resulting zero was greater than 3 microseconds
Temperature or Density Calibrations: many possible causes
Recommended Actions:
1. If alert appears during a transmitter zero, ensure that there is no flow through the sensor, then retry.
2. Cycle power to the flowmeter to clear the alert.
3. If appropriate, restore the factory zero to return the flowmeter to operation.
4. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
5. If alert appears during a density calibration, contact Micro Motion. |
653 |
Priority: Failed - Fix Now
Description:
Mechanical zero: Calibration procedure failed due to reverse flow through the sensor.
Recommended Actions:
1. If alert appears during a transmitter zero,ensure that there is no flow through the sensor, then retry.
2. Cycle power to the flowmeter to clear the alert.
3. If appropriate, restore the factory zero to return the flowmeter to operation.
4. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
5. If alert appears during a density calibration, contact Micro Motion. |
654 |
Priority: Failed - Fix Now
Description:
Mechanical zero: Calibration procedure failed due to flow through the sensor.The resulting zero was greater than 3 microseconds.
Recommended Actions:
1. If alert appears during a transmitter zero, ensure that there is no flow through the sensor, then retry.
2. Cycle power to the flowmeter to clear the alert.
3. If appropriate, restore the factory zero to return the flowmeter to operation.
4. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
5. If alert appears during a density calibration, contact Micro Motion. |
655 |
Priority: Failed - Fix Now
Description:
Mechanical zero: The resulting zero was greater than 3 microseconds.
Recommended Actions:
1. If alert appears during a transmitter zero, ensure that there is no flow through the sensor, then retry.
2. Cycle power to the flowmeter to clear the alert.
3. If appropriate, restore the factory zero to return the flowmeter to operation.
4. If you want to change the alert severity, go to the Configure-> Alert Setup-> Alert Severity screen.
5. If alert appears during a density calibration, contact Micro Motion. |
656 |
Priority: Failed - Fix Now
Description:
Internal memory or program fault has been detected.
Recommended Actions:
1. Resolve the other active alerts first.
2. Cycle power to the flowmeter.
3. If alert persists,The transmitter might need service. Contact Micro Motion. |
657 |
Priority: Failed - Fix Now
Description:
The value computed for the resistance of the Line RTD is outside limits.
Recommended Actions:
1. Check the sensor RTD circuitry.
2. Verify that process temperature is within range of sensor and transmitter.
3. If you want to change the alert severity,go to the Configure-> Alert Setup-> Alert Severity screen
4. If the problem persists, contact Micro Motion. |
658 |
Priority: Failed - Fix Now
Description:
The value computed for the resistance of the Meter/Case RTD is outside limits.
Recommended Actions:
1. Check the sensor RTD circuitry.
2. Verify that process temperature is within range of sensor and transmitter.
3. If you want to change the alert severity,go to the Configure-> Alert Setup-> Alert Severity screen.
4. If the problem persists, contact Micro Motion. |
659 |
Priority: Failed - Fix Now
Description:
The 'Flow Calibration Factor' and/or 'K1' has not been entered since the last master reset
Recommended Actions:
1. Check the characterization against the sensor tag. Specifically, verify the 'Flow Cal', 'K1' and 'K2' values.
2. If you want to change the alert severity,go to the Configure-> Alert Setup-> Alert Severity screen.
3.If the problem persists, contact Micro Motion. |
660 |
Priority: Failed - Fix Now
Description:
The 'Flow Calibration Factor' and/or 'K1' has not been entered since the last master reset
Recommended Actions:
1. Check the characterization against the sensor tag. Specifically, verify the 'Flow FCF', 'K1' and 'K2' values.
2. If you want to change the alert severity,go to the Configure-> Alert Setup-> Alert Severity screen.
3.If the problem persists, contact Micro Motion. |
661 |
Priority: Failed - Fix Now
Description:
The sensor is recognized as a straight tube but the 'K1' value indicates a curved tube, or vice versa.
Recommended Actions:
1. If'A017' is active,resolve it first.
2. Check the characterization. Specifically, verify the 'Flow FCF' and 'K1' values.
3. Check the sensor RTD circuitry.
4. If the problem persists, contact Micro Motion. |
662 |
Flow FCF:
Value %0
K1:
Value %1 uSec
K2:
Value %2 uSec |
663 |
Priority: Failed - Fix Now
Description:
Transmitter electronics failure has occurred.
Recommended Actions:
1. Cycle power to the flowmeter.
2. Contact Micro Motion. |
664 |
Priority: Failed - Fix Now
Description:
The loaded software is not compatible with the programmed board type.
Recommended Actions:
1. Contact Micro Motion. |
665 |
Priority: Failed - Fix Now
Description:
The core processor is not receiving enough power.
Recommended Actions:
1. Verify the core processor input voltage is at least 12V.
2. Check the power supply and all power wiring. |
666 |
Priority: Failed - Fix Now
Description:
No signal from 'Left Pickoff' or 'Right Pickoff', suggesting that sensor tubes are not vibrating.
Recommended Actions:
1. Check for 'Slug Flow'.
2. View the diagnostic variables to verify whether tubes are vibrating.Left and Right pickoffs should be above 10mV.
3. Check the sensor circuitry.
4. Check sensor tube for plugging.
5. If you want to change the alert severity,go to the Configure-> Alert Setup-> Alert Severity screen.
6. If the problem persists, contact Micro Motion. |
667 |
Priority: Advisory
Description:
The calculated amount of current output is outside of the linear range.
Recommended Actions:
1. Verify that Upper Range Value and Lower Range Value are set correctly for the process variable and the process.
2. If you want to change the alert severity,go to the Configure-> Alert Setup-> Alert Severity screen. |
668 |
Primary Variable:
%0
%0:
Value %1 %2 |
669 |
PV Lower Range Value:
Value %0 %1
PV Upper Range Value:
Value %2 %3 |
670 |
Priority: Advisory
Description:
Non-zero 'HART Address' configured, or user has set the mA output to a fixed value.
Recommended Actions:
1. Check the 'HART Address'. If non-zero, set 'mA Output Action' parameter to enable 'Live mA Output' or if multi-drop mode is desired change the alert severity to ignore by going to the Configure-> Alert Setup-> Alert Severity screen.
2. If mA output trim is being performed, exit mA output trim.
3. If mA output loop test is being performed, exit mA output loop test.
4. Check to see if the output has been fixed via digital communications or the local display. |
671 |
HART Address:
%0
mA Output Fault Action:
%1 |
672 |
Priority: Maintenance - Fix Soon
Description:
The drive power (current/voltage) is at its maximum.
Recommended Actions:
1. Check the sensor circuitry.
2. If this is the only active alarm, it can be ignored. If desired, reconfigure the alarm severity to Ignore. |
673 |
Priority: Advisory
Description:
A calibration procedure is in progress.
Recommended Actions:
1. Allow the flowmeter to complete calibration.
2. For zero calibration procedures, you may abort the calibration, set the zero time parameter to a lower value, and restart the calibration.
3. If you want to change the alert sverity,go to the Configure-> Alert Setup-> Alert Severity screen. |
674 |
Priority: Maintenance - Fix Soon
Description:
The 'Density' has exceeded the user-defined 'Slug Flow'(density) limits.
Recommended Actions:
1. Check that sensor tubes are completely filled.
2. Check that 'Slug Flow' limits are set to appropriate values.
3.Verify density cutoff is at least 0.2g/cc.
4. If you want to change the alert sverity,go to the Configure-> Alert Setup-> Alert Severity screen. |
675 |
Slug High Limit:
Value %0 g/Cucm
Slug Low Limit:
Value %1 g/Cucm
Slug Duration:
Value %2 sec |
676 |
Priority: Advisory
Description:
Device is in HART burst mode.
Recommended Actions:
1. No action required.
2. If desired, reconfigure the alarm severity to Ignore
3. If you want to change the alert sverity,go to the Configure-> Alert Setup-> Alert Severity screen. |
677 |
Priority: Maintenance - Fix Soon
Description:
Transmitter has been restarted.
Recommended Actions:
1. No action required.
2. If you want to change the alert sverity,go to the Configure-> Alert Setup-> Alert Severity screen. |
678 |
Priority: Advisory
Description:
Simulation mode is enabled.
Recommended Actions:
1. Disable output simulation.
2. If you want to change the alert sverity,go to the Configure-> Alert Setup-> Alert Severity screen. |
679 |
Priority: Maintenance - Fix Soon
Description:
An uncorrectable checksum mismatch has been detected.
Recommended Actions:
1. Cycle power to the flow meter.
2. The flow meter might need service. Contact Micro Motion. |
680 |
Priority: Maintenance - Fix Soon
Description:
Primary variable has exceeded sensor limits.
Recommended Actions:
1. Verify process and check for 'Slug Flow'.
2. Check the diagnostic variables.
3. Check the sensor circuitry
4. Check the sensor tubes for erosion.
5. If the problem persists, contact Micro Motion. |
681 |
Priority: Maintenance - Fix Soon
Description:
Non-primary variable has exceeded sensor limits.
Recommended Actions:
1. Verify process and check for 'Slug Flow'.
2. Check the test points.
3. Check the sensor circuitry.
4. Check the sensor tubes for erosion.
5. If the problem persists,contact Micro Motion. |
682 |
Priority: Maintenance - Fix Soon
Description:
The calculated amount of current output is outside of the linear range.
Recommended Actions:
1. Verify that mA output range values are set to appropriate values. |
683 |
Priority: Maintenance - Fix Soon
Description:
Non-zero 'HART Address' configured,or user has set the mA output to a fixed value.
Recommended Actions:
1. Check the 'HART Address'. If non-zero, set 'mA Output Action' parameter to enable 'Live mA Output'.
2. If mA output trim is being performed, exit mA output trim.
3. If mA output loop test is being performed, exit mA output loop test.
4. Check to see if the output has been fixed via digital communications or the local display. |
684 |
Priority: Maintenance - Fix Soon
Description:
Power has been removed and reapplied resulting in the reinstallations of the setup information.
Recommended Actions:
1. The first command to recognize this condition will automatically reset this flag.
2. This flag may also be set following a Master Reset or a Self Test. |
685 |
Priority: Maintenance - Fix Soon
Description:
A write or set command has been executed.
Recommended Actions:
1. No action required. |
686 |
Priority: Maintenance - Fix Soon
Description:
A hardware error or failure has been detected by the device.
Recommended Actions:
1. This is a summary alert and is generated when one of the fault severity alerts is active. Resolve the other active alerts first. |
687 |
Select 'Alert Number': |
688 |
Current severity is '%0'. |
689 |
Select 'Alert Severity': |
690 |
'%{1}' is set to '%{0}'. |
691 |
A001: EEPROM Error (CP) is set to %0. |
692 |
A002: RAM Error (CP) is set to %0. |
693 |
A003: No Sensor Response is set to %0. |
694 |
A004: Temperature Overrange is set to %0. |
695 |
A005: Mass Flow Rate Overrange is set to %0. |
696 |
A006: Characterization Required is set to %0. |
697 |
A008: Density Overrange is set to %0. |
698 |
A009: Transmitter Initializing Warming Up is set to %0. |
699 |
A010: Calibration Failure is set to %0. |
700 |
A011: Zero Calibration Failed: Low is set to %0. |
701 |
A012: Zero Calibration Failed: High is set to %0. |
702 |
A013: Zero Calibration Failed: Unstable is set to %0. |
703 |
A014: Transmitter Failure is set to %0. |
704 |
A016: Sensor RTD Failure is set to %0. |
705 |
A017: T-Series RTD Failure is set to %0. |
706 |
A020: No Flow Cal Value is set to %0. |
707 |
A021: No K1 Value is set to %0. |
708 |
A022: Config DB Corrupt (CP) is set to %0. |
709 |
A023: Internal Totals Corrupt (CP) is set to %0. |
710 |
A025: Boot Sector Fault (CP) is set to %0. |
711 |
A029: PIC Daughterboard Comm Failure is set to %0. |
712 |
A030: Incorrect Board Type is set to %0. |
713 |
A031: Low Power is set to %0. |
714 |
A033: No LPO RPO Signal is set to %0. |
715 |
A100: MAO1 Saturated is set to %0. |
716 |
A101: MAO1 Fixed is set to %0. |
717 |
A102: Drive Overrange is set to %0. |
718 |
A104: Calibration-In-Progress is set to %0. |
719 |
A105: Slug Flow is set to %0. |
720 |
A106: Burst Mode Enabled is set to %0. |
721 |
A107: Power Reset Occurred is set to %0. |
722 |
A132: Sensor Simulation Active is set to %0. |
723 |
'Write Protect' is Enabled. |
724 |
'Write Protect' is Disabled. |
725 |
Select 'Write Protect' Action: |
726 |
Enable;Disable |
727 |
Access Restricted |
728 |
Resetting device. Please wait. |
729 |
Device reset completed successfully. |
730 |
You are about to overwrite the device configuration with factory values. Before continuing, set the control loop for manual operation and ensure that existing configuration values are documented or saved to a file. If the device connection is lost, reconnect using the defaults. Proceed? |
731 |
Aborting due to field device error. |
732 |
Factory values are restored successfully. |
733 |
1f3a0105device_advisory.gif |
734 |
Proceed;Change |
735 |
Set scale- Low output value |
736 |
Set scale- High output value |
737 |
measured_low |
738 |
Setting field device output to 20mA |
739 |
measured_high |