0 |
Event History |
1 |
The history of the 10 most recent diagnostic events. |
2 |
Event Log |
3 |
Allows for viewing of the 10 most recent diagnostic indicators. |
4 |
|
5 |
Event |
6 |
Date |
7 |
Time |
8 |
Duration |
9 |
View History |
10 |
Displays a history of most recent diagnostic events. For each event, the time when the event occurred and the duration of the event are shown. The table of history events displays the most recent event at the top with successively preceding events in descending order. |
11 |
Reset History |
12 |
Clears entries in Status History and resets the run time to zero. |
13 |
Set Clock |
14 |
Sets the Real-Time Clock in the device. |
15 |
.3f |
16 |
Runtime |
17 |
s |
18 |
h |
19 |
Date Occurred |
20 |
Time Occurred |
21 |
Runtime |
22 |
OK |
23 |
Software Error |
24 |
RAM Error |
25 |
ADC Failure |
26 |
EEPROM Error |
27 |
Analog Board Error |
28 |
Analog Output Error |
29 |
Spare Indicator 1 |
30 |
Default Parameters |
31 |
Spare Indicator 2 |
32 |
Spare Indicator 3 |
33 |
No Fiducial |
34 |
Too Many Echoes |
35 |
Safety Zone Alarm |
36 |
Echo Lost |
37 |
Spare Indicator 4 |
38 |
Config Conflict |
39 |
High Volume Alarm |
40 |
Spare Indicator 5 |
41 |
Initializing |
42 |
Config Changed |
43 |
Spare Indicator 6 |
44 |
Ramp Slope Error |
45 |
High Elec Temp |
46 |
Low Elec Temp |
47 |
Calibration Req'd |
48 |
Reject Curve Invalid |
49 |
Spare Indicator 7 |
50 |
Inferred Level |
51 |
Adjust Analog Outpt |
52 |
Low Supply Voltage |
53 |
Spare Indicator 8 |
54 |
Max Jump Exceeded |
55 |
Low Echo Margin |
56 |
Hi Surface Velocity |
57 |
Spare Indicator 9 |
58 |
Spare Indicator 10 |
59 |
Sequence Record |
60 |
Unknown |
61 |
Status |
62 |
Describes a diagnostic event. |
63 |
The date on which the event occurred. |
64 |
The time at which the event occurred. |
65 |
The system runtime at which the event occurred. |
66 |
.0f |
67 |
When a diagnostic is cleared, the difference between the present elapsed time and the time recorded when the event occurred is recorded as the duration. |
68 |
When a fault or warning is cleared, the difference between the present elapsed time and the time recorded when the event occurred is recorded as the duration. |
69 |
Trend Data |
70 |
Graph displaying real-time trend data. |
71 |
Level |
72 |
Volume |
73 |
Distance |
74 |
Loop current |
75 |
PV % Range |
76 |
Echo Strength |
77 |
Echo Margin |
78 |
mA |
79 |
Level of material in the vessel. |
80 |
.1f |
81 |
.2f |
82 |
Volume of product in the vessel. |
83 |
Distance measured from the sensor reference point downward
to the surface of the material in the vessel. |
84 |
Loop Current - loop current value as perceived by the device. |
85 |
Percent of Range - Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. |
86 |
% |
87 |
Relative strength of the level signal being detected. |
88 |
Echo Margin is a numeric value that is related to the strength of the target peak relative to competing waveform features, i.e. "noise".
Review Echo Curve to ensure the present value is based on the Level echo and not false targets in front of the Level echo. Adjust polarization of the radar beam (consult manual). Adjust gain parameters (Turbulence and Foam) to optimize the Echo Margin. The "Low Echo Margin" diagnostic is triggered with values <6. |
89 |
Data Log Setup |
90 |
Menu containing parameters for automatic capture of Trend data. To begin setup, enter Password. Set Device clock to present time. Select Parameters to record; Level, Echo Strength, Echo Margin and Loop current are typical. Set Start and Stop times. Record Interval will offer smallest time value based on memory available; set to appropriate value. |
91 |
Save Data Log Params |
92 |
|
93 |
Save Data Log Time |
94 |
Trending Variables |
95 |
Listing of Device Variables that can be selected to be saved in the internal data log feature of the device. |
96 |
Off |
97 |
On |
98 |
Time Setup |
99 |
A menu that allows the user to set the time span and sample interval for the Data Log. |
100 |
Present |
101 |
Start |
102 |
Stop |
103 |
Interval (minutes) |
104 |
Start Date |
105 |
The date on which event recording starts. |
106 |
Stop Date |
107 |
The date on which event recording stops. |
108 |
Start Time |
109 |
The time at which event recording starts. |
110 |
Stop Time |
111 |
The time at which event recording stops. |
112 |
The interval between time-based recordings. |
113 |
OKtoChangeDatalog |
114 |
Success |
115 |
Value was too high |
116 |
Value was too low |
117 |
Too few data bytes received |
118 |
Real-time clock has not been set. |
119 |
Set to nearest possible value |
120 |
Access restricted |
121 |
Echo Rejection |
122 |
Option which, when Enabled, allows for unwanted signals to be ignored.
Before enabling this feature, ensure false targets have been minimized by optimizing polarization (see manual) and Echo Margin value. |
123 |
Echo Curves |
124 |
Allows configuration of the Echo Curve option. |
125 |
Zoom |
126 |
Allows user to zoom in and out of a specific portion of the Echo Curve. |
127 |
Parameters |
128 |
Echo History |
129 |
Allows configuration of the Echo History Option. Saving an Echo Curve under a fault condition is important for accurate troubleshooting. |
130 |
Echo History Setup |
131 |
Menu for setting up the automatic capture of echoes based on Events or Time. To begin setup, enter Password. For Event-based: most critical are Echo Lost and Low Echo Margin. For Time-based: first set Device clock to present time. Set Start and Stop times. Record Interval will offer smallest time value based on memory available; set to appropriate value. |
132 |
Echo Graph |
133 |
Curve 1 |
134 |
Curve 2 |
135 |
Fiducial Position |
136 |
Top Blocking Dist |
137 |
Level Position |
138 |
Btm Blocking Dist |
139 |
Sensor Ref Position |
140 |
Tank Bottom |
141 |
Target Thresh Value |
142 |
Base Threshold |
143 |
PV Setpoints |
144 |
Distance from Sensor Ref Position |
145 |
Echo Strength |
146 |
Invalid selection |
147 |
Rejection Request Denied - Level Too Close |
148 |
Rejection Request Denied - Echo Strength Too High |
149 |
Rejection Request Denied - Echo Profile Underway |
150 |
Rejection Request Denied - Requested Locn Too Far |
151 |
Rejection Request Denied - No Fiducial |
152 |
Summary data not ready |
153 |
Waveform mismatch |
154 |
Less than 70 valid points |
155 |
Echo data not ready |
156 |
Interval too small |
157 |
Interval too large |
158 |
Refresh Echo List |
159 |
Click to refresh Echo List. |
160 |
Refresh Echo Curve Graph |
161 |
Click to refresh Echo Curve. |
162 |
Zoom Echo Curve Graph |
163 |
Refresh Echo History Graph |
164 |
Zoom Echo History Graph |
165 |
New Rejection Curve |
166 |
Echo Rejection procedure for creating a new echo rejection curve. Multiple level echos may be offered. Choose the echo that represents the actual media location, closer echos will be cancelled. Enter the correct echo number when prompted. For an empty vessel, enter '0'. If the correct location is not offered for a partially filled vessel, ensure that the tank dimensional information is correct. If the correct location is not listed, enter '0'. Enter the correct media location when prompted. For an empty vessel, accept the default value presented. |
167 |
Save Ref Echo Curve |
168 |
Method to save a reference echo curve in the device. The reference echo curve will be retained until over-written by a new reference echo curve. |
169 |
Refresh Echo History Log |
170 |
Method to re-read the echo history summary. |
171 |
Delete Echo History Log |
172 |
Allows the History information to be cleared and reset. |
173 |
Select the primary curve to display. |
174 |
Live |
175 |
Select the secondary curve to display. |
176 |
None |
177 |
Echo Rejection |
178 |
Echo Reference |
179 |
Echo History 1 |
180 |
Echo History 2 |
181 |
Echo History 3 |
182 |
Echo History 4 |
183 |
Echo History 5 |
184 |
Echo History 6 |
185 |
Echo History 7 |
186 |
Echo History 8 |
187 |
Echo History 9 |
188 |
Curve Selection |
189 |
Runtime for requested curve |
190 |
Distance between Points in Curve |
191 |
Curve Start |
192 |
Curve End |
193 |
Fiducial Position |
194 |
Sensor Reference Position |
195 |
Blocking Distance |
196 |
Level Position |
197 |
Interface Level Position |
198 |
End Of Probe Position |
199 |
4 mA Setpoint |
200 |
20 mA Setpoint |
201 |
Level Offset |
202 |
Measurement Type |
203 |
Sensor Mount |
204 |
Lvl Slope Start Value |
205 |
Ifc Slope Start Value |
206 |
Slope Start Distance |
207 |
Slope End Distance |
208 |
Level Threshold |
209 |
Interface Level Threshold |
210 |
End Of Probe Threshold |
211 |
Waveform index |
212 |
X-axis minimum |
213 |
X-axis maximum |
214 |
Ifc Level Position |
215 |
Sensor Ref Position |
216 |
EOP Position |
217 |
Lvl Slope End Value |
218 |
Ifc Slope End Value |
219 |
PV Lower Range Val |
220 |
PV Upper Range Val |
221 |
Start Index |
222 |
Tick Y-axis maximum |
223 |
Tick Y-axis minimum |
224 |
Echo Profile Maturity |
225 |
Percentage of echo profile obtained. |
226 |
Echo Reject State |
227 |
Off - Rejection Curve is not used (squelches Echo Reject Invalid).
Disabled - Rejection Curve is not used, possibly because it is Invalid.
Enabled - Rejection Curve is combined with waveform to produce Echo Curve. |
228 |
Disabled |
229 |
Enabled |
230 |
Echo History Log |
231 |
Listing of echo curves saved in the device. |
232 |
Not Saved |
233 |
Saved |
234 |
Time |
235 |
Echo History Mode |
236 |
Selection to save echo curves based on time intervals or selected diagnostic events. |
237 |
Events |
238 |
Events & Time |
239 |
Event Triggers |
240 |
Listing of diagnostic indicators that can be selected to trigger an automatic saving of an echo curve. |
241 |
Time Triggers |
242 |
Listing of parameters to control time-based automatic saving of echo curves. |
243 |
Echo List Type |
244 |
Selects whether the Live or Rejection echo data is shown. |
245 |
Live Echoes |
246 |
Rejection Echoes |
247 |
Echo List Length |
248 |
Number of echos in echo profile list. |
249 |
Echo number |
250 |
Enter the echo list number corresponding to the actual media location. Enter 0 if the correct location is not listed or for an empty vessel. |
251 |
Echo List |
252 |
1 |
253 |
2 |
254 |
3 |
255 |
4 |
256 |
5 |
257 |
6 |
258 |
7 |
259 |
8 |
260 |
9 |
261 |
10 |
262 |
11 |
263 |
12 |
264 |
13 |
265 |
14 |
266 |
15 |
267 |
Echo 1 Location |
268 |
Location of Echo 1. |
269 |
Echo 2 Location |
270 |
Location of Echo 2. |
271 |
Echo 3 Location |
272 |
Location of Echo 3. |
273 |
Echo 4 Location |
274 |
Location of Echo 4. |
275 |
Echo 5 Location |
276 |
Location of Echo 5. |
277 |
Echo 6 Location |
278 |
Location of Echo 6. |
279 |
Echo 7 Location |
280 |
Location of Echo 7. |
281 |
Echo 8 Location |
282 |
Location of Echo 8. |
283 |
Echo 9 Location |
284 |
Location of Echo 9. |
285 |
Echo 10 Location |
286 |
Location of Echo 10. |
287 |
Echo 11 Location |
288 |
Location of Echo 11. |
289 |
Echo 12 Location |
290 |
Location of Echo 12. |
291 |
Echo 13 Location |
292 |
Location of Echo 13. |
293 |
Echo 14 Location |
294 |
Location of Echo 14. |
295 |
Echo 15 Location |
296 |
Location of Echo 15. |
297 |
Echo 1 Strength |
298 |
Strength of Echo 1. |
299 |
Echo 2 Strength |
300 |
Strength of Echo 2. |
301 |
Echo 3 Strength |
302 |
Strength of Echo 3. |
303 |
Echo 4 Strength |
304 |
Strength of Echo 4. |
305 |
Echo 5 Strength |
306 |
Strength of Echo 5. |
307 |
Echo 6 Strength |
308 |
Strength of Echo 6. |
309 |
Echo 7 Strength |
310 |
Strength of Echo 7. |
311 |
Echo 8 Strength |
312 |
Strength of Echo 8. |
313 |
Echo 9 Strength |
314 |
Strength of Echo 9. |
315 |
Echo 10 Strength |
316 |
Strength of Echo 10. |
317 |
Echo 11 Strength |
318 |
Strength of Echo 11. |
319 |
Echo 12 Strength |
320 |
Strength of Echo 12. |
321 |
Echo 13 Strength |
322 |
Strength of Echo 13. |
323 |
Echo 14 Strength |
324 |
Strength of Echo 14. |
325 |
Echo 15 Strength |
326 |
Strength of Echo 15. |
327 |
Model |
328 |
Model - References the type of Field Device, usually an advertised model number, that is unique to a single manufacturer. |
329 |
Pulsar Model R96 |
330 |
Manufacturer |
331 |
Manufacturer Identification Code - References a specific manufacturer, which is usually a company name, that is responsible for the manufacture of this Field Device. |
332 |
MAGNETROL |
333 |
Distributor |
334 |
Private Label Distributor - References the company that is responsible for the distribution of this Field Device to customers. |
335 |
Loop Current Mode |
336 |
Loop Current Mode - Indicates whether the loop current is active or fixed (i.e. the device is in multi-drop). |
337 |
Disabled (Fixed) |
338 |
Enabled (PV) |
339 |
Device Status |
340 |
Field Device Status - Data indicating that the Field Device has detected condition(s) in the Field Device relating to: its hardware / the validity of a variable / its operating status / an internal process. |
341 |
PV Out of Limits |
342 |
Process applied to the primary variable is outside the operating limits of the field device. |
343 |
Non-PV Out of Limits |
344 |
Process applied to the non-primary variable is outside the operating limits of the field device. |
345 |
Loop Current Saturated |
346 |
Analog output 1 and its digital representation are outside the operating range limits, and not responding to input. |
347 |
Loop Current Fixed |
348 |
Analog output 1 and its digital representation are in fixed mode, and not responsive to input changes. |
349 |
More Status Available |
350 |
Field device has more status available. |
351 |
Cold Start |
352 |
A reset or self test of the field device has occurred, or power has been removed and reapplied. |
353 |
Configuration Changed |
354 |
A modification has been made to the configuration of the field device. |
355 |
Device Malfunction |
356 |
Field device has malfunctioned due to a hardware error or failure. |
357 |
Poll Address |
358 |
Polling Address - Address used by the Host to identify a Field Device, and changeable by the User to control: the Multidrop Mode for Analog Output 1), and the Analog Output Fixed Mode of Analog Output 1) |
359 |
Tag |
360 |
Tag - Text that is associated with the Field Device installation. This text can be used by the user in any way. A recommended use is as a unique label to a plant that correlates to a Field Device label, a plant drawing, or on a Control System. This variable is also used as a type of data link layer address handle. |
361 |
Long Tag |
362 |
Long Tag - Functions exactly like Tag except the size is larger (maximum of 32 ISO Latin 1 characters). |
363 |
Descriptor |
364 |
Descriptor - Text that is associated with the Field Device.
This text can be used by the user in any way.
There is no specific recommended use. |
365 |
Date - Gregorian calendar date that is stored in the Field Device.
This date can be used by the user in any way.
There is no specific recommended use. |
366 |
Message |
367 |
Message - Text that is associated with the Field Device.
This text can be used by the user in any way.
There is no specific recommended use. |
368 |
Dev id |
369 |
Field Device Identification - Uniquely identifies the Field Device when combined with the Manufacturer Identification and Device Type. Therefore, this variable cannot be modified
by the Host user. |
370 |
Cfg chng count |
371 |
Configuration Change Counter - This indicates the number of times the device's configuration or calibration has been changed by a host application or from a local operator interface. |
372 |
Final asmbly num |
373 |
Number that is used for identification purposes, and is associated with the overall Field Device. |
374 |
Universal Rev |
375 |
Universal Revision - Revision of the Universal Device Description, to which the Field Device conforms. |
376 |
Fld Dev Rev |
377 |
Field Device Revision - Revision of the Field Device Specific Device Description, to which the Field Device conforms. |
378 |
Software Rev |
379 |
Field Device Software Revision - This revision corresponds to the firmware that is embedded in the Field Device. |
380 |
Num Req Preams |
381 |
Number of Request Preambles - Number of Preambles required from the Host request by the Field Device. |
382 |
Ext Dev Status |
383 |
Extended Field Device Status - This provides additional Device Status information. |
384 |
Failure |
385 |
Function Check |
386 |
Out of Spec |
387 |
Maintenance required |
388 |
Device variable alert |
389 |
Critical Power Failure |
390 |
Dev Diag Status 0 |
391 |
Simulation active |
392 |
The device is in simulation mode and the level output is not representative of the process. |
393 |
Non-Volatile memory failure |
394 |
The Non-Volatile memory check is invalid or may be corrupt, or the battery of a battery-backed memory has failed. |
395 |
Volatile memory error |
396 |
The RAM memory check is invalid or may be corrupt. |
397 |
Watchdog reset executed |
398 |
A watchdog reset has been performed. |
399 |
Voltage conditions out of range |
400 |
A voltage condition is outside its allowable range. |
401 |
Environmental conditions out of range |
402 |
An internal or environmental condition is beyond acceptable limits. |
403 |
Electronic failure |
404 |
A hardware problem not related to the sensor has been detected. |
405 |
Dev Diag Status 1 |
406 |
NE 107 Simulation active |
407 |
The device is in simulation mode and the diagnostic indicators not representative of the device status. |
408 |
Data Response codes |
409 |
Data that is returned in the Field Device response, that indicates the relative success of the Command sent in the Host request.
This information may relate to the Data of the Host request or to the command itself. |
410 |
Field device specific error |
411 |
In write protect mode |
412 |
Busy |
413 |
Delayed response initiated |
414 |
Delayed response running |
415 |
Delayed response dead |
416 |
Delayed response conflict |
417 |
Command not implemented |
418 |
Status 0 |
419 |
Diagnostic indicators displaying status of the device.
Indicators are grouped in order of relative importance, with the most important first. |
420 |
Unrecoverable error occurred in stored program.
Contact Technical Support. |
421 |
RAM (read/write) memory failing.
Contact Technical Support. |
422 |
Analog-to-digital converter failing.
Contact Technical Support. |
423 |
Non-volatile parameter storage failing.
Contact Technical Support. |
424 |
Unrecoverable hardware failure.
Contact Technical Support. |
425 |
Actual loop current deviates from commanded value. Analog output is inaccurate.
Perform TRIM LOOP maintenance procedure.
Contact Technical Support. |
426 |
All saved parameters are set to default values.
Perform complete Device Setup.
Contact Technical Support. |
427 |
Status 1 |
428 |
The fiducial pulse is not located where expected, or the fiducial amplitude is not in the expected range.
Increase Fiducial Gain.
Adjust Window to result in Fiducial Ticks of 100 - 300.
Contact Technical Support. |
429 |
Excessive number of possible echoes detected.
Check settings:
Dielectric Range,
Sensitivity,
polarization direction.
View Echo Curve
Contact Technical Support. |
430 |
Risk of echo loss if liquid rises above Top Blocking Distance.
Ensure that liquid cannot reach Top Blocking Distance. |
431 |
No detectable level signal identified within the configured range.
Check settings:
Dielectric Range,
Sensitivity,
Tank Height
Increase Sensitivity.
View Echo Curve. |
432 |
Selections of Measurement Type and Primary Variable (PV) are incompatible.
Change Measurement Type and/or PV to appropriate settings. |
433 |
Status 2 |
434 |
Volume calculated from Level reading exceeds capacity of vessel or Custom Table.
Check settings:
Vessel Dimensions,
Custom Table entries. |
435 |
Distance measurement is inaccurate while internal filters are settling.
Wait for up to 10 seconds. |
436 |
A parameter has been modified from the User Interface.
If desired, reset Config Changed indicator in ADVANCED CONFIG. |
437 |
Internal signal timing out of limits causing inaccurate distance measurement.
Check accuracy of Distance reading.
Replace transmitter electronics. |
438 |
Electronics too hot. May compromise Distance measurement or damage instrument.
Shield transmitter from heat source or increase air circulation.
Locate transmitter remotely in a cooler area. |
439 |
Electronics too cold. May compromise Distance measurement or damage instrument.
Insulate transmitter.
Locate transmitter remotely in a warmer area. |
440 |
Status 3 |
441 |
Factory calibration has been lost. Measurement accuracy is diminished.
Return transmitter to factory for recalibration. |
442 |
Echo Rejection invalid.
May report erroneous Level readings.
Upr Echo may be lost near the top of the vessel.
Save a fresh Echo Rejection Curve. |
443 |
The target has been lost within the Max Level Jump distance from the Top or Bottom Blocking Distance locations. As a result, the transmitter has inferred that the level has moved into one of those two zones, and will report level measurement of full or empty along with the Inferred Level diagnostic.
Verify Level reading. If incorrect, the configuration may need to be adjusted. |
444 |
Loop current is inaccurate.
Perform ADJUST ANALOG OUTPUT maintenance procedure. |
445 |
Device starved for power due to high loop resistance or inadequate voltage.
Verify loop resistance
Check loop power supply voltage. |
446 |
A potential valid level target has been detected which is further away from the last known valid level target than the distance selected for the Max Level Jump parameter.
Check settings:
Dielectric Range,
Sensitivity.
View Echo Curve. |
447 |
Status 4 |
448 |
Target echo has low Echo Margin rating.
Check settings:
Dielectric Range,
Sensitivity.
View Echo Curve. |
449 |
The measured Surface Velocity is greater than the Max Surface Velocity value derived from the Rate of Change parameter.
Confirm actual tank rate of change.
Adjust (increase) Rate of Change parameter accordingly. |
450 |
A Sequence Record number has been stored in Event Log.
If desired, report Sequence Record number to Technical Support. |
451 |
PV |
452 |
Digital representation that tracks the Analog Output Number 1, under normal operating modes. |
453 |
SV |
454 |
Digital representation that tracks the Analog Output (if it exists) Number 2, under normal operating modes. |
455 |
TV |
456 |
Digital representation that tracks the Analog Output (if it exists) Number 3, under normal operating modes. |
457 |
QV |
458 |
Digital representation that tracks the Analog Output (if it exists) Number 4, under normal operating modes. |
459 |
Upper Range Value (20 mA setpoint) - Defines the operational endpoint from which the Analog Value and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint from which the alarms associated with the Analog Value and the alarms associated with the Digital Value representation are derived. |
460 |
Lower Range Value (4 mA setpoint) - Defines the operational endpoint from which the Analog Value and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint from which the alarms associated with the Analog Value and the alarms associated with the Digital Value representation are derived. |
461 |
PV Analog Alarm Sel |
462 |
Analog Output Alarm Type - Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. |
463 |
High |
464 |
Low |
465 |
Hold Last Output Value |
466 |
8.2f |
467 |
Variable to trim |
468 |
Device Variable Trim Code - An index that identifies a Field Device Variable that supports the trim procedure. |
469 |
PV is |
470 |
Primary Index into Dynamic Variables Array - An index location, that indicates which Field Device dynamic variable has been mapped into the Primary Variable dynamic variable. |
471 |
SV is |
472 |
Secondary Index into Dynamic Variables Array - An index location, that indicates which Field Device dynamic variable has been mapped into the Secondary Variable dynamic variable. |
473 |
TV is |
474 |
Tertiary Index into Dynamic Variables Array - An index location that indicates which Field Device dynamic variable has been mapped into the Tertiary Variable dynamic variable. |
475 |
4V is |
476 |
Fourth Index into Dynamic Variables Array - An index location that indicates which Field Device dynamic variable has been mapped into the Fourth Variable dynamic variable. |
477 |
Level Units |
478 |
Select units of measurement for the level output. |
479 |
in |
480 |
ft |
481 |
mm |
482 |
cm |
483 |
m |
484 |
Device Family |
485 |
Indicates the family (i.e, pressure, temperature, flow, etc.) to which the device variable belongs. |
486 |
Class |
487 |
Indicates the unit code expansion table used for a particular dynamic or device variable. |
488 |
PDQ |
489 |
Indicates the overall process data quality of the device variable value. |
490 |
LS |
491 |
Indicates whether the device variable is limited (i.e., not responding to a process). |
492 |
Family Status |
493 |
Indicates additional status information on a device variable for a specific device family. |
494 |
USL |
495 |
Defines the maximum usable value for the Upper Range Value. |
496 |
LSL |
497 |
Defines the minimum usable value for the Lower Range Value. |
498 |
Min Span |
499 |
Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. |
500 |
Damping |
501 |
A damping factor (0-10 seconds) may be added to smooth the output in the event of turbulence. |
502 |
Sensor S/N |
503 |
Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. |
504 |
Volume Units |
505 |
Select units of measurement for the volume output. |
506 |
ft3 |
507 |
in3 |
508 |
gal |
509 |
bbl |
510 |
mL |
511 |
L |
512 |
Device Family |
513 |
Class |
514 |
PDQ |
515 |
LS |
516 |
Family Status |
517 |
USL |
518 |
LSL |
519 |
Min Span |
520 |
LS |
521 |
Family Status |
522 |
Echo Strength Units |
523 |
Echo Margin Units |
524 |
Device Family |
525 |
Class |
526 |
PDQ |
527 |
LS |
528 |
Family Status |
529 |
USL |
530 |
LSL |
531 |
Min Span |
532 |
Temperature |
533 |
The present temperature of the electronics. |
534 |
Temperature Units |
535 |
°C |
536 |
°F |
537 |
Family Status |
538 |
1.0f |
539 |
Failure Alarm Delay |
540 |
Delay that can be added to loop failure condition.
This delay can be used to ignore nuisance, short term alarms.
Initial setting of this delay should be short, e.g., 1-2 seconds. |
541 |
Magnetrol S/N |
542 |
Serial number of the electronics contained in this transmitter. |
543 |
Date/Time/Initials |
544 |
When and by whom calibration was performed. |
545 |
Hardware Rev. |
546 |
This revision corresponds to the electronics that are used in the Field Device. |
547 |
Firmware Rev. |
548 |
This revision corresponds to the software or firmware that is embedded in the Field Device. |
549 |
Enter Password |
550 |
Certain parameters are password protected to limit access by the user. Parameters that should never be changed by the user are protected with the Factory password. Some parameters, intended for field use, that may be changed in special, controlled situations require the Advanced password. |
551 |
0 |
552 |
New User Password |
553 |
Change password that is required to access user parameters. |
554 |
5u |
555 |
NAP Value |
556 |
Advanced Password used for advanced troubleshooting. |
557 |
Lvl 4mA Set Point |
558 |
Lower Range Value (4 mA setpoint) - Defines the operational endpoint from which the Analog Value and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint from which the alarms associated with the Analog Value and the alarms associated with the Digital Value representation are derived. |
559 |
Lvl 20mA Set Point |
560 |
Upper Range Value (20 mA setpoint) - Defines the operational endpoint from which the Analog Value and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint from which the alarms associated with the Analog Value and the alarms associated with the Digital Value representation are derived. |
561 |
Vol 4mA Set Point |
562 |
Vol 20mA Set Point |
563 |
Description |
564 |
Thru-Air Radar Level Xmtr |
565 |
Antenna Model |
566 |
Type of antenna connected to the transmitter, as shown by the first four digits of the antenna model number on the nameplate. Refer to the I/O Manual for additional information regarding different Antenna Models. |
567 |
RAA-x TFE Rod |
568 |
RAB-G PolyP Rod |
569 |
RAB-L PolyP Rod |
570 |
RAB-x PolyP Rod |
571 |
RAC-x Halar Rod |
572 |
RA3-x 3" Horn |
573 |
RA4-x 4" Horn |
574 |
RA6-x 6" Horn |
575 |
RA3-x 75mm Horn |
576 |
RA4-x 100mm Horn |
577 |
RA6-x 150mm Horn |
578 |
Model 9 |
579 |
Model 10 |
580 |
Model 11 |
581 |
Model 12 |
582 |
Model 13 |
583 |
Model 14 |
584 |
Antenna Extension |
585 |
Determines maximum nozzle length that can be used with an antenna. Refer to the last three digits of the model number as shown on the antenna nameplate when making a selection. |
586 |
-0** - No Nozzle |
587 |
-1** - Nozzle <= 4" |
588 |
-2** - Nozzle <= 8" |
589 |
-3** - Nozzle <= 12" |
590 |
Extension 5 |
591 |
Extension 6 |
592 |
Extension 7 |
593 |
-1** - Nozzle <= 100mm |
594 |
-2** - Nozzle <= 200mm |
595 |
-3** - Nozzle <= 300mm |
596 |
Antenna Mount |
597 |
Mounting style of antenna process connection. |
598 |
NPT |
599 |
BSP |
600 |
Flange |
601 |
Mount 4 |
602 |
Mount 5 |
603 |
Mount 6 |
604 |
Dielectric Range |
605 |
A broad gain setting. The parameter selects the range bounding the dielectric constant of the medium being measured.
Choose range 'Below 1.7' for very light hydrocarbons such as
butane and propane. For stillwell applications only.
Choose range '1.7 - 3' for typical hydrocarbons and oils.
Choose range '3 - 10' for amines.
Choose range 'Above 10' for water-based applications.
If uncertain, chose lower range setting for additional signal strength.
(Some ranges may not be selectable depending on the antenna model.) |
606 |
Below 1.7 |
607 |
1.7 - 3.0 |
608 |
3 - 10 |
609 |
Above 10 |
610 |
Turbulence |
611 |
A gain and averaging adjustment. Increase choice if Echo Strength value is consistently < 20. Set to "Medium" initially. |
612 |
None |
613 |
Light |
614 |
Medium |
615 |
Heavy |
616 |
Rate of Change |
617 |
Select the Maximum rate of change of the level surface (rising or falling). |
618 |
< 5 in/min |
619 |
5-20 in/min |
620 |
20-60 in/min |
621 |
> 60 in/min |
622 |
< 130 mm/min |
623 |
130-500 mm/min |
624 |
500-1500 mm/min |
625 |
> 1500 mm/min |
626 |
Foam |
627 |
A secondary gain adjustment. Increase choice if Echo Strength value is consistently < 20. |
628 |
Medium |
629 |
Heavy |
630 |
Temperature Rating |
631 |
|
632 |
Standard |
633 |
High Temp |
634 |
Cryogenic |
635 |
Vibration Rating |
636 |
Vibration rating of the probe. |
637 |
Vib Resistant |
638 |
Measurement Type |
639 |
The desired measurement mode of operation.
(Selection of Measurement Type may be constrained by the Antenna Model.) |
640 |
Level Only |
641 |
Volume & Level |
642 |
Tank Height |
643 |
Distance from sensor reference point to the bottom of the vessel. Up to 40 feet maximum depending on Antenna Model. (Sensor reference point is bottom of NPT Threads, top of BSP Threads, or flange face.) |
644 |
Sensor Offset |
645 |
Distance from the Top of the Tank to the Sensor Reference Point. Required only for accurate volume calculations and for correct operation of the High Volume Alarm. |
646 |
Bottom Blocking Dist defines an area at the bottom of the vessel where reflections cannot be measured effectively due to angled bottoms, heating coils, reflections from flat metal tank bottoms in low dielectric applications, etc. It is the distance from the bottom of the tank to the lowest valid level reading. The level reading will never be lower than the Bottom Blocking Distance value. |
647 |
Stillwell ID |
648 |
Inside diameter of the stillwell in which the antenna is installed. |
649 |
Saved Reject Level |
650 |
Location of saved level used to establish an echo rejection curve. |
651 |
Saved Reject Distance |
652 |
Location of saved distance used to establish an echo rejection curve. |
653 |
Echo List Mode |
654 |
Selects whether the echo position is shown in terms of level or distance. |
655 |
Level |
656 |
Level Trim |
657 |
An offset value to be used to force the transmitter to output the exact Level or Distance. This should only be used after all parameters have been entered correctly, and it has been confirmed that the transmitter is tracking the correct level. |
658 |
Sensitivity |
659 |
Present Sensitivity (gain) of the instrument.
Default setting depends on Dielectric parameter and is suitable for most installations.
Refer to I & O manual before adjusting. |
660 |
Top Blocking Distance defines an area near the antenna where reflections cannot be measured effectively due to antenna ringing. It is measured from the Sensor Reference Point. The minimum value is set by the choice of Antenna Type and is calculated as antenna length + 2 inches (50 mm); larger values are encouraged. The level reading will be held at the value corresponding to the Blocking Distance. Do not allow liquid on the antenna. |
661 |
Safety Zone Alarm |
662 |
Defines how the Analog Output will respond when the transmitter detects a level within the Safety Zone. Enable fault to ensure safe, reliable high-level readings in critical applications. (If Latch 3.6 or Latch 22 is chosen, the unit will remain in alarm until it is manually cleared with the SZ Alarm Reset.) |
663 |
None |
664 |
3.6 mA |
665 |
22 mA |
666 |
Latch 3.6 mA |
667 |
Latch 22 mA |
668 |
Safety Zone Height |
669 |
Enter a distance that defines a safety zone just below the Blocking Distance. If Safety Zone Fault is enabled, the transmitter will report a fault if the level rises into this zone. |
670 |
Echo Loss Alarm |
671 |
Action of the loop current when the Echo Lost diagnostic is active. |
672 |
Echo Loss Delay |
673 |
Allows a time delay between the actual Loss of Echo and the transmitter reflecting the diagnostic. Enter a number, (shown in seconds) between 1 and 1000. |
674 |
s |
675 |
Target Selection |
676 |
Choose between First or Largest per application.
"First" will allow the detection of first valid target.
"Largest" will allow the detection of largest target. |
677 |
First Echo |
678 |
Largest Echo |
679 |
Target Thresh Mode |
680 |
Generally use "Auto" with Target Selection set to "First Echo". "Fixed" can be used with either Target Selection option. |
681 |
Automatic |
682 |
Fixed Value |
683 |
Threshold value used for detecting a target - in percent of actual target amplitude. |
684 |
Target Thresh Value |
685 |
Threshold value used for detecting a target - in echo strength units (0 - 100). |
686 |
Minimum allowable threshold when Target Thresh Mode is set to Automatic. |
687 |
Fixed Loop Current |
688 |
Parameter used to set the value of the fixed output current. |
689 |
Vessel Type |
690 |
Shape of vessel. (Used when Measurement Type = Volume) |
691 |
Rectangular |
692 |
Horizontal/Flat |
693 |
Horizontal/Elliptical |
694 |
Horizontal/Spherical |
695 |
Spherical |
696 |
Vertical/Flat |
697 |
Vertical/Elliptical |
698 |
Vertical/Spherical |
699 |
Vertical/Conical |
700 |
Custom Table |
701 |
Radius |
702 |
Radius of the cylindrical/spherical portion of the vessel. |
703 |
Ellipse Depth |
704 |
Depth of the elliptical portion of the vessel. |
705 |
Conical Height |
706 |
Height of the conical portion of the vessel. |
707 |
Width |
708 |
Horizontal width of the rectangular vessel. |
709 |
Length |
710 |
Horizontal length of the rectangular vessel or of the cylindrical portion of a vessel with elliptical or spherical ends. |
711 |
Custom Table Type |
712 |
Linear or Spline interpolation is performed between strapping table points. |
713 |
Linear |
714 |
Spline |
715 |
Level Input Source |
716 |
Level portion of strapping table can be entered manually from the keypad or automatically from the sensor. |
717 |
Keypad |
718 |
Sensor |
719 |
Custom Table Length |
720 |
Number of valid level-volume pairs in the volume custom table. A level-volume pair is valid if both values are greater than all preceding level-volume pairs (30 points maximum). |
721 |
Point 01 Level |
722 |
Custom table level entry corresponding to Point 01 Volume. |
723 |
Point 02 Level |
724 |
Custom table level entry corresponding to Point 02 Volume. |
725 |
Point 03 Level |
726 |
Custom table level entry corresponding to Point 03 Volume. |
727 |
Point 04 Level |
728 |
Custom table level entry corresponding to Point 04 Volume. |
729 |
Point 05 Level |
730 |
Custom table level entry corresponding to Point 05 Volume. |
731 |
Point 06 Level |
732 |
Custom table level entry corresponding to Point 06 Volume. |
733 |
Point 07 Level |
734 |
Custom table level entry corresponding to Point 07 Volume. |
735 |
Point 08 Level |
736 |
Custom table level entry corresponding to Point 08 Volume. |
737 |
Point 09 Level |
738 |
Custom table level entry corresponding to Point 09 Volume. |
739 |
Point 10 Level |
740 |
Custom table level entry corresponding to Point 10 Volume. |
741 |
Point 11 Level |
742 |
Custom table level entry corresponding to Point 11 Volume. |
743 |
Point 12 Level |
744 |
Custom table level entry corresponding to Point 12 Volume. |
745 |
Point 13 Level |
746 |
Custom table level entry corresponding to Point 13 Volume. |
747 |
Point 14 Level |
748 |
Custom table level entry corresponding to Point 14 Volume. |
749 |
Point 15 Level |
750 |
Custom table level entry corresponding to Point 15 Volume. |
751 |
Point 16 Level |
752 |
Point 17 Level |
753 |
Point 18 Level |
754 |
Custom table level entry corresponding to Point 18 Volume. |
755 |
Point 19 Level |
756 |
Custom table level entry corresponding to Point 19 Volume. |
757 |
Point 20 Level |
758 |
Custom table level entry corresponding to Point 20 Volume. |
759 |
Point 21 Level |
760 |
Custom table level entry corresponding to Point 21 Volume. |
761 |
Point 22 Level |
762 |
Custom table level entry corresponding to Point 22 Volume. |
763 |
Point 23 Level |
764 |
Custom table level entry corresponding to Point 23 Volume. |
765 |
Point 24 Level |
766 |
Custom table level entry corresponding to Point 24 Volume. |
767 |
Point 25 Level |
768 |
Custom table level entry corresponding to Point 25 Volume. |
769 |
Point 26 Level |
770 |
Custom table level entry corresponding to Point 26 Volume. |
771 |
Point 27 Level |
772 |
Custom table level entry corresponding to Point 27 Volume. |
773 |
Point 28 Level |
774 |
Custom table level entry corresponding to Point 28 Volume. |
775 |
Point 29 Level |
776 |
Custom table level entry corresponding to Point 29 Volume. |
777 |
Point 30 Level |
778 |
Custom table level entry corresponding to Point 30 Volume. |
779 |
Point 01 Volume |
780 |
Custom table volume entry corresponding to Point 01 Level. |
781 |
Point 02 Volume |
782 |
Custom table volume entry corresponding to Point 02 Level. |
783 |
Point 03 Volume |
784 |
Custom table volume entry corresponding to Point 03 Level. |
785 |
Point 04 Volume |
786 |
Custom table volume entry corresponding to Point 04 Level. |
787 |
Point 05 Volume |
788 |
Custom table volume entry corresponding to Point 05 Level. |
789 |
Point 06 Volume |
790 |
Custom table volume entry corresponding to Point 06 Level. |
791 |
Point 07 Volume |
792 |
Custom table volume entry corresponding to Point 07 Level. |
793 |
Point 08 Volume |
794 |
Custom table volume entry corresponding to Point 08 Level. |
795 |
Point 09 Volume |
796 |
Custom table volume entry corresponding to Point 09 Level. |
797 |
Point 10 Volume |
798 |
Custom table volume entry corresponding to Point 10 Level. |
799 |
Point 11 Volume |
800 |
Custom table volume entry corresponding to Point 11 Level. |
801 |
Point 12 Volume |
802 |
Custom table volume entry corresponding to Point 12 Level. |
803 |
Point 13 Volume |
804 |
Custom table volume entry corresponding to Point 13 Level. |
805 |
Point 14 Volume |
806 |
Custom table volume entry corresponding to Point 14 Level. |
807 |
Point 15 Volume |
808 |
Custom table volume entry corresponding to Point 15 Level. |
809 |
Point 16 Volume |
810 |
Custom table volume entry corresponding to Point 16 Level. |
811 |
Point 17 Volume |
812 |
Custom table volume entry corresponding to Point 17 Level. |
813 |
Point 18 Volume |
814 |
Custom table volume entry corresponding to Point 18 Level. |
815 |
Point 19 Volume |
816 |
Custom table volume entry corresponding to Point 19 Level. |
817 |
Point 20 Volume |
818 |
Custom table volume entry corresponding to Point 20 Level. |
819 |
Point 21 Volume |
820 |
Custom table volume entry corresponding to Point 21 Level. |
821 |
Point 22 Volume |
822 |
Custom table volume entry corresponding to Point 22 Level. |
823 |
Point 23 Volume |
824 |
Custom table volume entry corresponding to Point 23 Level. |
825 |
Point 24 Volume |
826 |
Custom table volume entry corresponding to Point 24 Level. |
827 |
Point 25 Volume |
828 |
Custom table volume entry corresponding to Point 25 Level. |
829 |
Point 26 Volume |
830 |
Custom table volume entry corresponding to Point 26 Level. |
831 |
Point 27 Volume |
832 |
Custom table volume entry corresponding to Point 27 Level. |
833 |
Point 28 Volume |
834 |
Custom table volume entry corresponding to Point 28 Level. |
835 |
Point 29 Volume |
836 |
Custom table volume entry corresponding to Point 29 Level. |
837 |
Point 30 Volume |
838 |
Custom table volume entry corresponding to Point 30 Level. |
839 |
Present Temperature |
840 |
Present temperature measured in the electronics compartment. |
841 |
Max Temperature |
842 |
Maximum temperature measured in the electronics compartment. |
843 |
Min Temperature |
844 |
Minimum temperature measured in the electronics compartment. |
845 |
Fiducial Gain |
846 |
Factory parameter. Displayed for diagnostic purposes only. |
847 |
Window |
848 |
TVG Start Value |
849 |
Time Variable Gain starting value in internal amplitude units determined by configuration for application conditions. |
850 |
TVG End Value |
851 |
Time Variable Gain ending value in internal amplitude units determined by configuration for application conditions. |
852 |
TVG Start Location |
853 |
Internal position for start of TVG ramp. |
854 |
TVG Divisor |
855 |
Factory parameter used to calculate TVG Start Value. |
856 |
# Run Average |
857 |
Number of radar scans included in the run-averaged waveform.
Use lower values to decrease response time.
Use higher values to reduce amplitude and position variations. |
858 |
16 |
859 |
32 |
860 |
64 |
861 |
128 |
862 |
Surface Velocity |
863 |
Rate of level change as calculated by the transmitter. |
864 |
in/min |
865 |
mm/min |
866 |
Max Level Jump |
867 |
Used to evaluate if the distance change since the last target measurement is excessive. If so, the latest target measurement will not be used. Derived from the user-selected Rate of Change parameter (in selected units). |
868 |
Max Surface Velocity |
869 |
The maximum level change as derived from the user-selected Rate of Change parameter (in selected units). |
870 |
Boundary State |
871 |
Displays the present Boundary State. |
872 |
Initial |
873 |
Empty |
874 |
Full |
875 |
Echo Missing |
876 |
Echo Lost |
877 |
Restart |
878 |
Empty State Delay |
879 |
Time Delay (0 - 1000 sec) before exiting Empty State when a valid target is found in level measurement region. |
880 |
Elec Temp Offset |
881 |
PCB temperature calibration value.
Refer to I & O manual before adjusting. |
882 |
Conversion Factor |
883 |
5d |
884 |
Scale Offset |
885 |
Factory Param 1 |
886 |
Factory Param 2 |
887 |
Factory Param 3 |
888 |
Factory Param 4 |
889 |
4mA Trim Value |
890 |
4u |
891 |
20mA Trim Value |
892 |
Fdbk 4mA Trim Value |
893 |
Fdbk 20mA Trim Value |
894 |
Fdbk Current |
895 |
8.3f |
896 |
Fiducial Ticks |
897 |
Relative fiducial (internal reference) position.
Displayed for diagnostic purposes only. |
898 |
Fiducial Strength |
899 |
Relative amplitude of fiducial signal.
Displayed for diagnostic purposes only. |
900 |
Level Ticks |
901 |
Relative location of level signal.
Displayed for diagnostic purposes only. |
902 |
Relative amplitude of the level signal.
Displayed for diagnostic purposes only. |
903 |
Language |
904 |
Enables choice of language to be displayed on the LCD. |
905 |
English |
906 |
Français |
907 |
Deutsch |
908 |
Español |
909 |
Русский |
910 |
Português |
911 |
Status Symbol |
912 |
Enables NE 107 Status symbol to be displayed on Home Screen. |
913 |
Hide |
914 |
View |
915 |
Enables Long Tag to be displayed on the Home Screen. |
916 |
PV Bar Graph |
917 |
Enables a bar graph (displaying the Primary Variable in percent) to be displayed on the Home Screen. |
918 |
A read-only screen that presents the various output values that can be displayed.
(Available outputs will depend on Measurement Type). |
919 |
Elec Temp |
920 |
NE 107 Category |
921 |
Highest priority active NE 107 category. |
922 |
Failure |
923 |
Function Check |
924 |
Out of Spec |
925 |
Maintenance req'd |
926 |
NE 107 Indicator |
927 |
Highest priority active indicator in highest active NE 107 category. |
928 |
|
929 |
NE 107 Simulation Mode |
930 |
Allows manual activation (simulation) of NE 107 indicators. |
931 |
Status 5 |
932 |
NE 107 Mapping |
933 |
Allows user-mapping of default status for all NE 107 indicators. |
934 |
Indicator |
935 |
Mapping |
936 |
No Effect |
937 |
|
938 |
Level point value too high |
939 |
Level point value too low |
940 |
Volume point value too high |
941 |
Volume point value too low |
942 |
Level and Volume values out of range |
943 |
Device Icon |
944 |
Home |
945 |
A read-only default Home screen that graphically displays the PV, Loop Current, and PV % Range, in addition to other Measured Values. |
946 |
Process Variables |
947 |
Menu containing the principal measured values of the device. |
948 |
Diagnostics |
949 |
Menu showing Diagnostic information. |
950 |
Device Setup |
951 |
Set of menus to allow full configuration of the transmitter. |
952 |
Maintenance |
953 |
Menus containing parameters for maintaining the device. |
954 |
Setup Wizard |
955 |
Measured Values |
956 |
A read-only screen that presents the various output values that can be displayed.
(Available options will depend on Measurement Type.) |
957 |
Identity |
958 |
A menu that displays user's and manufacturer's identifying information about the transmitter. |
959 |
Factory Identity |
960 |
A menu that displays detailed manufacturer's information about the transmitter, such as Serial Number and hardware/software revisions. |
961 |
Basic Config |
962 |
A menu that allows for basic configuration of the transmitter. |
963 |
System Units |
964 |
A menu that allows for setting the measurement units used by the transmitter. |
965 |
Basic Config Diagram |
966 |
Volume Config |
967 |
A menu that allows for entry of known tank shapes or custom tables for volumetric output. This menu contains various tank shapes for easy configuration for those applications requiring Volumetric output. |
968 |
Vessel Diagram |
969 |
Custom Table |
970 |
Allows for Custom Volume Strapping Table entry. |
971 |
Point |
972 |
|
973 |
I/O Config |
974 |
Allows for configuration of the 4/20mA Analog Output, which includes the lower and upper set points, Damping, and Failure Alarms. |
975 |
I/O Config Diagram |
976 |
Variable Selection |
977 |
Allows for selection of the Secondary Variable (SV), Tertiary Variable (TV), and Quaternary Variable (QV). The analog 4/20 mA output will follow the PV. |
978 |
Graph Ranges |
979 |
Defines the limits of the vertical axes in DD/DTM graphs. |
980 |
Local Display Config |
981 |
Allows for customized presentation of information on the graphic LCD. The LCD can be configured to display up to two Measured Variables, along with a Tag, Bar Graph, and NE 107 symbols. |
982 |
Display Setup Diagram |
983 |
Measured Values |
984 |
Advanced Config |
985 |
Allows for more advanced configuration and troubleshooting.
(Advanced Password may be required for access to parameters.)
Contact Technical Support. |
986 |
Adv Config Diagram |
987 |
Safety Zone Settings |
988 |
Allows for configuration of an area below the Blocking Distance called Safety Zone. Since performance within the Blocking Distance is undetermined, these parameters allow the user to program an area below the Blocking Distance where an alarm can be set. Enable fault to ensure safe, reliable high-level readings in critical applications. (If Latch 3.6 or Latch 22 is chosen (recommended), the unit will remain in alarm until it is manually cleared with the SZ Alarm Reset.) |
989 |
Echo Loss Settings |
990 |
Menu containing parameters relating to the Echo Lost diagnostic alarm. |
991 |
Threshold Settings |
992 |
Allows for configuration of the various threshold settings. Automatic Threshold is used to detect the strongest echo on the probe and should only be used when it is ensured that only one medium is present. Fixed Threshold is used to detect the first valid echo and should be used in cases where stratification can occur. For example, applications where water bottoms can occur. |
993 |
Time Variable Gain |
994 |
Menu that includes various Time Variable Gain-related parameters. |
995 |
Analog Output |
996 |
Allows for configuration of the 4/20mA Analog Output, which includes the Poll Address, Loop Current Mode, and trimming of the loop. |
997 |
Factory Config |
998 |
Allows viewing of Factory Parameters.
These parameters are protected by a factory password and are not intended to be adjusted in the field. |
999 |
Fiducial Adjustment |
1000 |
Menu that includes various fiducial-related parameters. |
1001 |
Factory Calib |
1002 |
Read-Only Menu showing Factory Calibration Parameters. |
1003 |
Present Status |
1004 |
Shows the Present Status (health) of the transmitter. |
1005 |
------------------------------ |
1006 |
NE 107 Status |
1007 |
Add'l Device Status |
1008 |
Menu containing status information specific to the device. |
1009 |
Simulated Device Status |
1010 |
Menu containing simulated status information specific to the device. Select individual diagnostic indicators to turn an indicator On or Off. |
1011 |
NAMUR NE 107 Setup |
1012 |
This menu allows for user configuration of the various NE 107 indicators. Although all of the Model R96 indicators have defaults settings, they can be re-mapped to one of four categories: Maintenance Required, Out of Specification, Function Check, and Failure. Please refer to the NE 107 standard for more information. |
1013 |
Advanced Diagnostics |
1014 |
Menu containing Advanced Diagnostic parameters. |
1015 |
Internal Values |
1016 |
Shows detailed transmitter performance-related parameters. |
1017 |
Elec Temperatures |
1018 |
This menu displays the Maximum, Minimum, and Present temperatures of the electronics. |
1019 |
Transmitter Tests |
1020 |
Menu containing various tests to determine the functioning of the device. |
1021 |
Primary Variables |
1022 |
Menu containing the primary Device Variables provided by the device. |
1023 |
Echo Str |
1024 |
Electronics |
1025 |
Sensor Input |
1026 |
Adjust Analog Output |
1027 |
Allows the calibration of a selected Analog Output with an external reference at the operating endpoints of the Analog Output. |
1028 |
Read DAC trim values |
1029 |
Reads the values for DAC trim |
1030 |
Reset Max/Min Temps |
1031 |
Reset the maximum and minimum temperatures measured in the electronics compartment to the present temperature. |
1032 |
Reset SZ Alarm |
1033 |
Clear a latched Safety Zone Alarm |
1034 |
Factory Reset |
1035 |
Reset the device to factory default settings.
If using a HART host, disconnect and then reconnect the host after performing the reset. |
1036 |
Reset Parameters |
1037 |
Reset the device to factory calibrated settings.
If using a HART host, disconnect and then reconnect the host after performing the reset. |
1038 |
Reset "Config Changed" |
1039 |
Resets the Configuration Changed bit in the Device Status |
1040 |
Reset NE 107 Mapping |
1041 |
Sets the NE 107 mapping to default values. |
1042 |
Set loop to manual |
1043 |
Aborting return to normal |
1044 |
Leaving fixed current mode |
1045 |
Takes the Analog Output out of a mode where the output was a constant value, and returns the output to a mode where the output tracks the input. |
1046 |
Trim warning |
1047 |
Analog Output Test |
1048 |
Allows the User to manually manipulate the Analog Output to a selected constant output value. |
1049 |
Current Date |
1050 |
Current Date based upon the real-time clock in the field device |
1051 |
Current Time |
1052 |
Current Time based upon the real-time clock in the field device |
1053 |
WARNING - Loop should be removed from automatic control |
1054 |
Setup Wizard - Identity |
1055 |
Setup Wizard - Basic Config |
1056 |
Setup Wizard - Volume Config |
1057 |
Setup Wizard - I/O Config |
1058 |
Setup Wizard - Local Display Config |
1059 |
Setup Wizard - Complete |
1060 |
Setup Complete |
1061 |
NOTE - Loop may be returned to automatic control |
1062 |
Saves all values |
1063 |
Saves all values from Setup Wizard values |
1064 |
PV Analog Channel Saturated |
1065 |
PV Analog Channel Fixed |
1066 |
Wireless |
1067 |
WirelessHART Device |
1068 |
IEEE 802.15.4 2.4GHz DSSS with O-QPSK Modulation |
1069 |
Primary |
1070 |
Primary Analog Channel |
1071 |
Secondary |
1072 |
Secondary Analog Channel |
1073 |
Tertiary |
1074 |
Tertiary Analog Channel |
1075 |
Quaternary |
1076 |
Quaternary Analog Channel |
1077 |
Quinary |
1078 |
Quinary Analog Channel |
1079 |
Critical Power Failure |
1080 |
Lock all |
1081 |
Trim not supported |
1082 |
Configuration cannot be changed |
1083 |
Locked by gateway |
1084 |
Analog Input Channel |
1085 |
Analog Output Channel |
1086 |
Secondary Analog Channel Saturated |
1087 |
Tertiary Analog Channel Saturated |
1088 |
Quaternary Analog Channel Saturated |
1089 |
Quinary Analog Channel Saturated |
1090 |
Secondary Analog Channel Fixed |
1091 |
Tertiary Analog Channel Fixed |
1092 |
Quaternary Analog Channel Fixed |
1093 |
Quinary Analog Channel Fixed |
1094 |
Simulation active |
1095 |
The device is in simulation mode and the level output is not representative of the process. |
1096 |
Non-Volatile memory failure |
1097 |
The Non-Volatile memory check is invalid or maybe corrupt, or the battery of a battery-backed memory has failed. |
1098 |
Volatile memory error |
1099 |
The RAM memory check is invalid or maybe corrupt |
1100 |
Watchdog reset executed |
1101 |
A watchdog reset has been performed |
1102 |
Voltage conditions out of range |
1103 |
A voltage condition is outside its allowable range |
1104 |
Environmental conditions out of range |
1105 |
An internal or environmental condition is beyond acceptable limits. |
1106 |
Electronic failure |
1107 |
A hardware problem not related to the sensor has been detected. |
1108 |
Subdevice list changed |
1109 |
Duplicate master detected |
1110 |
Capacity Denied |
1111 |
The device was unable to acquire the communication bandwidth required to support the Burst Messaging specified |
1112 |
Bandwidth allocation pending |
1113 |
Block transfer pending |
1114 |
Battery life |
1115 |
Percent range |
1116 |
Loop current |
1117 |
Primary variable |
1118 |
Secondary variable |
1119 |
Tertiary variable |
1120 |
Quaternary variable |
1121 |
Read receive time |
1122 |
Write date and time |
1123 |
Non-Volatile Clock |
1124 |
When set the device contains a battery-backed clock. In this case, the clock does not need to be reset if there is a power failure. |
1125 |
Clock Uninitialized |
1126 |
The real-time clock has never been set with the date and time. For example, the clock is volatile and power was removed from and restored to the device. |
1127 |
None |
1128 |
No restrictions |
1129 |
SI Only |
1130 |
Restricted to SI Unit codes only |
1131 |
Process automation device |
1132 |
Discrete device |
1133 |
Hybrid:Process automation+discrete |
1134 |
I/O System |
1135 |
WirelessHART Process automation device |
1136 |
WirelessHART Discrete device |
1137 |
WirelessHART Process automation+discrete |
1138 |
WirelessHART Gateway |
1139 |
WirelessHART Access point |
1140 |
WirelessHART Process adapter |
1141 |
WirelessHART Discrete adapter |
1142 |
WirelessHART enabled handheld/portable maintenance tool |
1143 |
Device Profile |
1144 |
US |
1145 |
United States of America |
1146 |
JP |
1147 |
Japan |
1148 |
DE |
1149 |
Germany |
1150 |
FR |
1151 |
France |
1152 |
ES |
1153 |
Spain |
1154 |
RU |
1155 |
Russian Federation |
1156 |
CN |
1157 |
People's Republic of China |
1158 |
Secondary Master |
1159 |
Primary Master |
1160 |
Device Diagnostic Status 0 |
1161 |
Device Diagnostic Status 1 |
1162 |
I/O and Subdevice Status |
1163 |
WirelessHART Status |
1164 |
Time Set Option |
1165 |
Real Time Clock Flags |
1166 |
Country |
1167 |
Country of intended device installation |
1168 |
SI Unit Control |
1169 |
Indicates if device should only display SI unit codes |
1170 |
Time Stamp |
1171 |
Relative time value on network |
1172 |
8u |
1173 |
Dynamic Variables Returned for Device Variables |
1174 |
Command Response Truncated |
1175 |
Configuration Change Counter Mismatch |
1176 |
Status bytes mismatch |
1177 |
Device Variable |
1178 |
Variable to trim |
1179 |
Set Clock Date |
1180 |
Date to set the real-time clock in the field device to, or date that the real-time clock was last set |
1181 |
Set Clock Time |
1182 |
Time to set the real time clock in the field device to, or time that the real-time clock was last set |
1183 |
Event History Updated |
1184 |
Are You Sure? |
1185 |
Yes;No |
1186 |
Enter Password |
1187 |
Incorrect Password |
1188 |
Time (24-hour format) |
1189 |
WARNING - Changing Data Log Setup may discard previously logged data.
Are You Sure? |
1190 |
Invalid curve 1 selection. |
1191 |
Curve 1 mismatch. |
1192 |
Unable to read Curve 1 summary. |
1193 |
Unable to read Curve 1 data. |
1194 |
Invalid curve 2 selection. |
1195 |
Echo list has been updated. |
1196 |
Curve 2 mismatch. |
1197 |
Unable to read Curve 2 summary. |
1198 |
No echo data for Curve 2. |
1199 |
Unable to read Curve 2 data. |
1200 |
selection |
1201 |
Zoom minimum greater than zoom maximum. |
1202 |
Zoom minimum greater than graph maximum. |
1203 |
Zoom maximum smaller than graph minimum. |
1204 |
echo_number |
1205 |
The echo number must be between 0 and %{echo_list_length}. |
1206 |
Enter the level (units of %{level_units}.) corresponding to the actual media location. The default value presented is the value for an empty tank. |
1207 |
new_saved_location |
1208 |
Enter the distance (units of %{level_units}.) corresponding to the actual distance from the sensor reference point to the actual media location. The default value presented is the value for an empty tank. |
1209 |
The selected media location is: %[0.3f]{new_saved_location} %{level_units}. If this is correct, press 'OK' to store a new echo rejection profile. |
1210 |
The echo rejection process is: %{maturity}% complete. |
1211 |
Enter the Custom Table point number.
Enter 0 to exit. |
1212 |
point |
1213 |
Enter the Volume at the Level of %{level_value_vol_table} %{level_units}.: |
1214 |
Invalid number. |
1215 |
Connect reference meter |
1216 |
Setting fld dev output to 4mA |
1217 |
Aborting method due to last error |
1218 |
Enter meter value |
1219 |
Field device output (4mA) equal to reference meter? |
1220 |
Setting fld dev output to 20mA |
1221 |
Field device output (20mA) equal to reference meter? |
1222 |
Returning fld dev to original output |
1223 |
WARNING - Only one of the trim values was performed.
Your device may be in an unstable state. |
1224 |
Choose analog output level |
1225 |
4mA;20mA;Other;End |
1226 |
Output |
1227 |
Fld dev output is fixed at %[0.2f]{loopCurrent}mA |
1228 |
Next > |
1229 |
select |
1230 |
< Back; Next > |
1231 |
< Back; Finish |