Name | ID | Label | Description | Type | Source |
---|---|---|---|---|---|
before_poll | 4000 | Before polling | msrc_UNKNOWN | Details | |
put_in_manual | 4065 | Loop in manual | msrc_UNKNOWN | Details | |
back_to_normal | 4066 | Back to normal | msrc_UNKNOWN | Details | |
write_protect_on | 4049 | Write protect | Write protects the device, if correct password is entered | msrc_UNKNOWN | Details |
write_protect_off | 404A | Write enable | Write enables the device, if correct password is previously entered | msrc_UNKNOWN | Details |
set_new_password | 404B | New password | Sets a new password for write protection, if correct password is entered | msrc_UNKNOWN | Details |
show_serial_number | 4060 | Serial Number | 9 digit production line serial number, consisting of yybbbrrrr, where <yy> is the year of production, <bbb> is the batch number and <rrrr> is a running number for this batch. Expanded from device id | msrc_UNKNOWN | Details |
enter_sensor_configuration | 404C | Sensor config | Configures the sensor, sensor type, measurement type, CJC compensation etc. | msrc_UNKNOWN | Details |
enter_cable_resistance | 404E | Enter value | Enter new value for cable resistance. If the device setup is RTD/Ohm 3 or 4 wire, cable resistance for sensor 1 is the expected max value for the total cable resistance in 2 wires. Otherwise it is the actual total cable resistance for the selected sensor | msrc_UNKNOWN | Details |
measure_cable_resistance | 404F | Measure value | Automaticly measures the cable resistance. If the device setup is RTD/Ohm 3 or 4 wire, cable resistance for sensor 1 is the expected max value for the total cable resistance in 2 wires. Otherwise it is the actual total cable resistance for the selected sensor | msrc_UNKNOWN | Details |
restore_configuration | 4067 | restoring configuration | msrc_UNKNOWN | Details | |
broken_namur_down | 405C | NAMUR down | Enables broken sensor error detection, and sets the error output value to 3.5 mA acc. to NAMUR NE43 | msrc_UNKNOWN | Details |
broken_namur_up | 405D | NAMUR up | Enables broken sensor error detection, and sets the error output value to 23 mA acc. to NAMUR NE43 | msrc_UNKNOWN | Details |
shorted_namur_down | 405E | NAMUR down | Enables shorted sensor error detection, and sets the error output value to 3.5 mA acc. to NAMUR NE43 | msrc_UNKNOWN | Details |
shorted_namur_up | 405F | NAMUR up | Enables shorted sensor error detection, and sets the error output value to 23 mA acc. to NAMUR NE43 | msrc_UNKNOWN | Details |
override_dac_trim | 4048 | Override D/A trim | Overrides any previously D/A trimming by restoring factory calibration values | msrc_UNKNOWN | Details |
transmitter_loop_test | 1023 | ループ テスト | ループ テスト - アナログ出力をユーザーが選択した値で固定出力します | msrc_UNKNOWN | Details |
transmitter_dac_trim | 1024 | D/A トリム | D/A トリム (デジタル/アナログ トリム) - オペレーティング エンド ポイントに対するアナログ出力と外部指示計とのキャリブレーションを行います。 | msrc_UNKNOWN | Details |
leave_fixed_current_mode | 1003 | 固定電流モードを終ります | 現在の固定モードを終了 - アナログ出力を定数値のモードから移行させ, 出力が入力に応じて変わるモードに戻します。 | msrc_UNKNOWN | Details |
return_to_normal | 1016 | ノーマル モードに戻します | msrc_UNKNOWN | Details | |
Name | ID | Label | Description | Type | Source |