Name | ID | Label | Description | Type | Source |
---|---|---|---|---|---|
zero_trim_at_zero | 4045 | Zero trim | Zero trim - Make the sensor input the new zero input reference. Sensor gain trim point is adjusted. | msrc_UNKNOWN | Details |
sv_upper_trim | 4047 | Temp upper trim | msrc_UNKNOWN | Details | |
sv_lower_trim | 4046 | Temp low trim | msrc_UNKNOWN | Details | |
transmitter_self_test | 400A | Self test | msrc_UNKNOWN | Details | |
master_reset | 400B | Master reset | msrc_UNKNOWN | Details | |
reset_flag | 4007 | Reset config chgd | Resets the configuration changed flag | msrc_UNKNOWN | Details |
write_protect_contrl | 401E | Write prtct cntrl | Changes the write protect setting of the transmitter | msrc_UNKNOWN | Details |
comp_mode_toggle | 403A | Comp mode on/off | Turns on/off digital compensation of input errors. | msrc_UNKNOWN | Details |
toggle_pv_damping | 4040 | Damp mode on/off | Turns on/off damping of input | msrc_UNKNOWN | Details |
select_alarm_code | 4019 | Select alarm code | This command performs the function of setting the PV Analog Output Current Failure Alarm mode of the device to allow a prespecified current condition upon a hardware failure condition as indicated by an over pressure condition, sensor malfunction or other condition requiring notification to the analog control system | msrc_UNKNOWN | Details |
restore_settings | 4009 | Restr fctry set | This command will restore all original factory settings to the slave device. It will destroy, by overwriting, any user calibration, notes, messages, tags, or other modifications which have been entered into the slave device by the user | msrc_UNKNOWN | Details |
return_to_normal | 1016 | Aborting return to normal | msrc_UNKNOWN | Details | |
warning_message | 1017 | Set loop to manual | msrc_UNKNOWN | Details | |
loop_test | 1002 | Loop test | Loop test- Allows the User to manually manipulate the Analog Output to a selected constant output value | msrc_UNKNOWN | Details |
dac_trim | 1004 | D/A trim | Digital to Analog Trim- Allows the calibration of a selected Analog Output with an external reference at the operating endpoints of the Analog Output | msrc_UNKNOWN | Details |
zero_trim | 1006 | Zero calibrate | Zero calibrate - Make the sensor input the new zero input reference. Sensor gain trim point is not adjusted. | msrc_UNKNOWN | Details |
leave_fixed_current_mode | 1003 | Leaving fixed crnt mode | Leaving Fixed Current Mode- Takes the Analog Output out of a mode where the output was a constant value, and returns the output to a mode where the output tracks the input | msrc_UNKNOWN | Details |
applied_rerange | 1007 | Apply values | Applied values- Perform a device rerange by applying the desired Upper Range Value and Lower Range Values to the device input | msrc_UNKNOWN | Details |
sensor_a_upper_sensor_trim | 1789 | Gain trim | Pressure Sensor Upper Trim- Calibrate the pressure sensor. | msrc_UNKNOWN | Details |