Loading…
Loading…
Name | ID | Label | Description | Type | Source |
---|---|---|---|---|---|
return_drive_to_normal | 40B6 | Abortar retorno para normal | msrc_UNKNOWN | Details | |
return_from_method | 40B7 | Abortar retorno para normal | msrc_UNKNOWN | Details | |
restore_to_factory_settings_method | 409C | Restore to factory | Restore to Factory Settings: This function overwrites all control drive configuration and calibration with factory settings. Use this option to restore a control drive to original factory operation. | msrc_UNKNOWN | Details |
select_position_calibration_method | 40B8 | Select cal source | Select Position Calibration Source: This function selects the Position calibration in use. Factory calibration can not be overwritten by the user. User calibration is initially set by the factory but can be changed by the user. | msrc_UNKNOWN | Details |
write_factory_position_calibration_method | 40A9 | Restore cal | Restore Position Calibration: This function overwrites the user Position calibration with the factory supplied Position calibration. | msrc_UNKNOWN | Details |
calibrate_position_method | 40A8 | Calibrate | Calibrate Position: This procedure calibrates the control drive's Position sensor. Two methods are available; an automatic routine that finds each limit switch, or manual user selection of a known lower and upper Position point. | msrc_UNKNOWN | Details |
select_feedback_calibration_method | 40B9 | Select cal source | Select Feedback Calibration Source: This function selects the Feedback calibration in use. Factory calibration can not be overwritten by the user. User calibration is initially set by the factory but can be changed by the user. | msrc_UNKNOWN | Details |
write_factory_feedback_calibration_method | 40AB | Restore cal | Restore Feedback Calibration: This function overwrites the user Feedback calibration with the factory supplied Feedback calibration. | msrc_UNKNOWN | Details |
calibrate_feedback_method | 40AA | Calibrate | Calibrate Feedback: This procedure calibrates the control drive's Feedback output. | msrc_UNKNOWN | Details |
select_demand_calibration_method | 40BA | Select cal source | Select Demand Calibration Source: This function selects the Demand calibration in use. Factory calibration can not be overwritten by the user. User calibration is initially set by the factory but can be changed by the user. | msrc_UNKNOWN | Details |
write_factory_demand_calibration_method | 40AD | Restore cal | Restore Demand Calibration: This function overwrites the user Demand calibration with the factory supplied Demand calibration. | msrc_UNKNOWN | Details |
calibrate_demand_method | 40AC | Calibrate | Calibrate Demand: This procedure calibrates the control drive's Demand circuit. | msrc_UNKNOWN | Details |
select_torque_calibration_method | 40BB | Select cal source | Select Torque Calibration Source: This function selects the Torque sensor calibration in use. Factory calibration can not be overwritten by the user. User calibration is initially set by the factory but can be changed by the user. | msrc_UNKNOWN | Details |
write_factory_torque_calibration_method | 40AF | Restore cal | Restore Torque Calibration: This function overwrites the user Torque sensor calibration with the factory supplied Torque sensor calibration. | msrc_UNKNOWN | Details |
calibrate_torque_method | 40AE | Calibrate | Calibrate Torque: This procedure calibrates the control drive's Torque sensor. Two methods are available; one that requires temporarily removing torque from the control drive output shaft and entering a torque sensor gauge factor, and another that requires creating and entering a known output shaft torque. | msrc_UNKNOWN | Details |
edit_drive_operating_mode_method | 4030 | Operating mode | msrc_UNKNOWN | Details | |
reset_stall_method | 40B0 | Reset Stall | Reset Stall: This function resets the control drive to normal operation after a Stall condition has been set. Clear the cause of the Stall condition before selecting Reset Stall. Also see Stall time. | msrc_UNKNOWN | Details |
fb_out_test_method | 40B3 | FB out test | Feedback Output Test: Allows the user to manually manipulate the Feedback output to a selected constant output value. | msrc_UNKNOWN | Details |
board_self_test_method | 40B4 | Board self-test | Board Self-Test: This function instructs the ESR-D to run self diagnostic tests and report any problem found. | msrc_UNKNOWN | Details |
board_reset_method | 40B5 | Board reset | Board Reset: This function instructs the ESR-D to perform a power-on reset. This has the same affect as removing and restoring power to the control drive. A Board reset does not change drive configuration or calibration, but does clear the state of special conditions such as fixed Feedback or Stall. | msrc_UNKNOWN | Details |
torque_sensor_enable_method | 4006 | Trq view | Torque Display: Defines whether the optional Torque Sensing function is enabled in the ESR-D. When using a ESR-D equipped with Torque Sensing in a control drive without a torque sensor, you must disable this feature. | msrc_UNKNOWN | Details |
position_sensor_direction_method | 40BE | Snsr dir | msrc_UNKNOWN | Details | |
setup_assistant_method | 4098 | Setup Assistant | Setup Assistant: This procedure assists the user in setup and calibration of an existing control drive with an ESR-D. | msrc_UNKNOWN | Details |
drive_model_method | 40BC | Drive Model | Drive Model: Displays the Beck drive model; this is also used to determine the availablity of some drive features. | msrc_UNKNOWN | Details |
warning_message | 1017 | Ajustar malha para manual | msrc_UNKNOWN | Details | |
Name | ID | Label | Description | Type | Source |