0 |
9739MVD |
1 |
Model |
2 |
Transmitter Software |
3 |
.1f |
4 |
Universal |
5 |
Field Device |
6 |
说æ |
7 |
硬件 |
8 |
A000: Undefined |
9 |
A001: EEPROM Error (CP) |
10 |
A002: RAM Error (CP) |
11 |
A003: No Sensor Response |
12 |
A004: Temperature Overrange |
13 |
A005: Mass Flow Overrange |
14 |
A006: Characterization Required |
15 |
A007: Real-Time Interrupt Failure |
16 |
A008: Density Overrange |
17 |
A009: Transmitter Initializing/Warming Up |
18 |
A010: Calibration Failure |
19 |
A011: Zero Calibration Failed: Low |
20 |
A012: Zero Calibration Failed: High |
21 |
A013: Zero Calibration Failed: Unstable |
22 |
A014: Transmitter Failure |
23 |
A015: MA Readback Error |
24 |
A016: Sensor RTD Failure |
25 |
A017: T-Series RTD Failure |
26 |
A018: EEPROM Error (Xmtr) |
27 |
A019: RAM Error (Xmtr) |
28 |
A020: No Flow Cal Value |
29 |
A021: No K1 Value |
30 |
A022: Config DB Corrupt (CP) |
31 |
A023: Internal Totals Corrupt (CP) |
32 |
A024: Program Corrupt (CP) |
33 |
A025: Boot Sector Fault (CP) |
34 |
A027: Security Breach |
35 |
A028: CP Write Failure |
36 |
A029: PIC/Daughterboard Comm Failure |
37 |
A030: Incorrect Board Type |
38 |
A031: Low Power |
39 |
A032: MV: Outputs to Fault |
40 |
A033: No LPO/RPO Signal |
41 |
A034: Meter Verification Failed |
42 |
A035: Meter Verification Aborted |
43 |
A036: Undefined |
44 |
A037: Undefined |
45 |
A038: Undefined |
46 |
A039: Undefined |
47 |
A100: MAO1 Saturated |
48 |
A101: MAO1 Fixed |
49 |
A102: Drive Overrange |
50 |
A103: Data Loss Possible |
51 |
A104: Calibration-In-Progress |
52 |
A105: Slug Flow |
53 |
A106: Burst Mode Enabled |
54 |
A107: Power Reset Occurred |
55 |
A108: Single-SP Event 1 ON |
56 |
A109: Single-SP Event 2 ON |
57 |
A110: FO Saturated |
58 |
A111: FO Fixed |
59 |
A112: Upgrade Transmitter Software |
60 |
A113: MAO2 Saturated |
61 |
A114: MAO2 Fixed |
62 |
A115: No External Data |
63 |
A116: API: Temperature Overrange |
64 |
A117: API: Density Overrange |
65 |
A118: DO1 Fixed |
66 |
A120: ED: Curve Fit Failure |
67 |
A121: ED: Extrapolation alarm |
68 |
A124: FI Saturated |
69 |
A129: PPI Display Error |
70 |
A130: Undefined |
71 |
A131: Reserved |
72 |
A132: Sensor Simulation Active |
73 |
A133: PIC UI EEPROM Error |
74 |
A134: PPI Memory Error |
75 |
A135: PPI Communication Error |
76 |
A136: Undefined |
77 |
A137: Undefined |
78 |
A138: TBR Active |
79 |
A139: Undefined |
80 |
D1 Calibration In Progress |
81 |
D2 Calibration In Progress |
82 |
D3 Calibration In Progress |
83 |
D4 Calibration In Progress |
84 |
FD Calibration In Progress |
85 |
Zero Calibration In Progress |
86 |
Temperature Slope Calibration In Progress |
87 |
Temperature Offset Calibration In Progress |
88 |
Discrete Event 1 Active |
89 |
Discrete Event 2 Active |
90 |
Discrete Event 3 Active |
91 |
Discrete Event 4 Active |
92 |
Discrete Event 5 Active |
93 |
Discrete Output 1 Active |
94 |
Discrete Input 1 Active |
95 |
Reserved |
96 |
Undefined |
97 |
Undefined |
98 |
Flow Switch Hysteresis Out of Range |
99 |
Invalid Channel A Assignment Code |
100 |
Invalid Channel B Assignment Code |
101 |
Invalid Channel C Assignment Code |
102 |
Invalid Channel D Assignment Code |
103 |
Invalid Channel E Assignment Code |
104 |
Invalid Channel F Assignment Code |
105 |
Invalid Channel A Power Source Code |
106 |
Invalid Channel B Power Source Code |
107 |
Invalid Channel C Power Source Code |
108 |
Invalid Channel D Power Source Code |
109 |
Invalid Channel E Power Source Code |
110 |
Invalid Channel F Power Source Code |
111 |
Invalid Units Code |
112 |
Invalid Milliamp Input Variable Code |
113 |
Enable Concentration Measurement Code Out of Range |
114 |
Enable Curve Lock Code Out of Range |
115 |
Invalid Concentration Units Code |
116 |
Invalid Temperature Units Code |
117 |
Invalid Density Units Code |
118 |
Transmitter-Specific Command Error (Invalid CM curve) |
119 |
Reference Temperature Out of Range |
120 |
Water Reference Temperature Out of Range |
121 |
Water Reference Density Out of Range |
122 |
Slope Trim Out of Range |
123 |
Slope Offset Out of Range |
124 |
Extrapolation Alarm Limit Out of Range |
125 |
Max Fit Order Out of Range |
126 |
Invalid Curve Index |
127 |
Invalid Data Index |
128 |
Current (mA Output 1) |
129 |
Current (mA Output 2) |
130 |
Current (mA Input) |
131 |
Offset Calibration |
132 |
Slope Calibration |
133 |
mA Output 2 Loop Test |
134 |
Trim mA Output 1 |
135 |
Trim mA Output 2 |
136 |
Resets internal totalizers. |
137 |
Display K Factor |
138 |
The number of pulses per unit of measure output via the frequency output |
139 |
|
140 |
Inputs/Outputs |
141 |
Frequency Output |
142 |
æ¹åè¦æ¥ä¸¥éçº§å« |
143 |
读å离æ£å¨ä½åé
|
144 |
审æ¥ææ离æ£å¨ä½ |
145 |
Discrete Output Test |
146 |
mA Outputs |
147 |
Additional Information for Above |
148 |
No Additional Information for Above |
149 |
Reset Matrix Data |
150 |
Load Matrix Data From Device |
151 |
Enter Matrix |
152 |
Refresh Hours Since Last Run |
153 |
读å Modbus æ°æ® |
154 |
åå
¥ Modbus æ°æ® |
155 |
mA Input |
156 |
Configure Matrix |
157 |
Trim Concentration Measurement Process Variables |
158 |
设å¤å¤ä½ |
159 |
æ¢å¤å·¥åç»æ |
160 |
æ è¯ |
161 |
Revisions |
162 |
HART Burst Mode |
163 |
Set Up mA Input |
164 |
Discrete Input |
165 |
ä¿¡æ¯åæ° |
166 |
åéå¨ä¿¡æ¯ |
167 |
Inputs/Outputs Fault Actions |
168 |
Discrete Output |
169 |
Digital Communications |
170 |
Modbus Data |
171 |
Concentration Measurement |
172 |
Concentration Measurement Configuration |
173 |
Matrix Configuration |
174 |
Isotherm 1 |
175 |
Isotherm 2 |
176 |
Isotherm 3 |
177 |
Isotherm 4 |
178 |
Isotherm 5 |
179 |
Isotherm 6 |
180 |
???? |
181 |
éç½®/æ¢å¤ |
182 |
.2f |
183 |
.3f |
184 |
.4f |
185 |
.5f |
186 |
4.2f |
187 |
Transmitter Serial Number |
188 |
8d |
189 |
8.2f |
190 |
8.3f |
191 |
8.6f |
192 |
.6f |
193 |
10.4f |
194 |
6.2f |
195 |
Sensor Flange |
196 |
Tube Lining |
197 |
Tube Wetted Material |
198 |
5.4f |
199 |
5.2f |
200 |
5d |
201 |
5.3f |
202 |
5.5f |
203 |
uSec |
204 |
6.5f |
205 |
2d |
206 |
Fault Action |
207 |
ä¸éå¼ (21.0-24.0 mA) |
208 |
ä¸éå¼ (1.0-3.6 mA) |
209 |
Fault Action |
210 |
Digital Fault Actions |
211 |
Fault Level |
212 |
Fault Level |
213 |
1d |
214 |
7.2f |
215 |
4d |
216 |
Polled Variable 1 |
217 |
Polled Variable 2 |
218 |
9.8f |
219 |
10.7f |
220 |
Meter Verify Failed |
221 |
RS485 Dual Function |
222 |
Discrete Input State |
223 |
Discrete Input State 2 |
224 |
3d |
225 |
åé |
226 |
äºä»¶ç±»å |
227 |
NLPD |
228 |
NLPH |
229 |
NLPM |
230 |
NLPS |
231 |
Nm3/day |
232 |
Nm3/hr |
233 |
Nm3/min |
234 |
Nm3/sec |
235 |
SCFD |
236 |
SCFH |
237 |
SCFM |
238 |
SCFS |
239 |
SLPD |
240 |
SLPH |
241 |
SLPM |
242 |
SLPS |
243 |
Sm3/day |
244 |
Sm3/hr |
245 |
Sm3/min |
246 |
Sm3/sec |
247 |
SL |
248 |
Sm3 |
249 |
Special |
250 |
Simulate Primary Purpose Variables |
251 |
Simulation Control |
252 |
Simulation Fixed Value |
253 |
Simulation Ramp Low Point |
254 |
Simulation Ramp High Point |
255 |
Simulation Ramp Period |
256 |
V |
257 |
mmi_current algorithm state_label |
258 |
Set Frequency Input Scaling |
259 |
4.1f |
260 |
Hours Since Last Run |
261 |
Active Matrix |
262 |
Curve 1 |
263 |
Curve 2 |
264 |
Curve 3 |
265 |
Curve 4 |
266 |
Curve 5 |
267 |
Curve 6 |
268 |
Reference Temperature |
269 |
The reference temperature of the fluid |
270 |
Water Reference Temperature |
271 |
Trim Slope |
272 |
Trim Offset |
273 |
Extrapolation Alarm Limit |
274 |
Matrix Name |
275 |
Curve Name |
276 |
Curve Fit Maximum Order |
277 |
Curve Fit Max Order |
278 |
Curve Fit Results |
279 |
Good |
280 |
Poor |
281 |
Failed |
282 |
Empty |
283 |
Concentration Units |
284 |
Accuracy |
285 |
Enabled |
286 |
Enable Concentration Measurement |
287 |
Enable ED |
288 |
Lock/Unlock Concentration Matrices |
289 |
Indicates whether the curve is locked from writing |
290 |
Not Locked |
291 |
Locked |
292 |
Derived Variable |
293 |
Standard |
294 |
Density at Ref. |
295 |
S.G. |
296 |
Mass Conc(Dens) |
297 |
Mass Conc(SG) |
298 |
Volume Conc(Dens) |
299 |
Volume Conc(SG) |
300 |
Conc(Dens) |
301 |
Conc(SG) |
302 |
Water Reference Density |
303 |
Reason for Abort |
304 |
Transmitter Running Seconds at Test |
305 |
Enable Temperature High Extrapolation Limit |
306 |
Disabled |
307 |
Enable Density Low Extrapolation Limit |
308 |
Enable Density High Extrapolation Limit |
309 |
Enable Temperature Low Extrapolation Limit |
310 |
Slope |
311 |
Offset |
312 |
2 |
313 |
3 |
314 |
4 |
315 |
5 |
316 |
Temperature Units |
317 |
Density Units |
318 |
Concentration Unit String |
319 |
Matrix Being Configured |
320 |
Channel D |
321 |
Channel E |
322 |
Channel F |
323 |
Milliampere Input |
324 |
Power Source |
325 |
Channel D Power Source |
326 |
DO Power Source |
327 |
Concentration 1 |
328 |
Concentration 2 |
329 |
Concentration 3 |
330 |
Concentration 4 |
331 |
Concentration 5 |
332 |
SpecConc0 |
333 |
SpecConc1 |
334 |
SpecConc2 |
335 |
SpecConc3 |
336 |
SpecConc4 |
337 |
SpecConc5 |
338 |
DensAtConc0 |
339 |
DensAtConc1 |
340 |
DensAtConc2 |
341 |
DensAtConc3 |
342 |
DensAtConc4 |
343 |
DensAtConc5 |
344 |
Density |
345 |
Density |
346 |
Density |
347 |
Density |
348 |
Density |
349 |
4.4f |
350 |
mA Input Upper Range Value |
351 |
mA Input Lower Range Value |
352 |
mA Input Level |
353 |
mA Input Variable Assignment |
354 |
External Pressure |
355 |
External Temperature |
356 |
None |
357 |
Milliamp Input Units |
358 |
API Vol Flow Digital Units |
359 |
API Dens Digital Units |
360 |
ED Vol Flow Digital Units |
361 |
ED Dens Digital Units |
362 |
ä¿æç°ææå®å¼ |
363 |
Configure map variables, primary and secondary output, discrete outputs, pulse output, discrete inputs, pulse input settings and RS-485 port. |
364 |
Unit Codes |
365 |
Alert Severity |
366 |
Enter an Alert number and change the Alert's severity to Fault, Information or Ignore. |
367 |
Enter an Alert number and view the current severity of the alert. |
368 |
Revision Numbers |
369 |
State is On. |
370 |
State is Off. |
371 |
æ´æ¹å®âTypeâï¼ç±»åï¼å段åï¼è¯¥å±å¹ä¸ä¼èªå¨æ´æ°ãéæ©âGuided Setupâï¼è®¾ç½®å导ï¼ï¼ç¶åè¿å该å±å¹æ¥çå½åé
ç½®ã |
372 |
Optional Setup |
373 |
Configure the Process Monitor Screens by selecting the desired process variables for each screen. |
374 |
Configure the number of decimal places for each process variable. |
375 |
Digital to analog trim of the mA output 1. |
376 |
Digital to analog trim of the mA output 2. |
377 |
Perform First Point (Air) Calibration. |
378 |
Perform Second Point (Water) Calibration. |
379 |
Perform Flowing Density Calibration. |
380 |
Perform Fourth Point (users choice) Calibration. |
381 |
Set a fixed output value for the discrete output. |
382 |
Simulation Configuration |
383 |
Mass Flow Rate Simulation Settings |
384 |
Density Simulation Settings |
385 |
Temperature Simulation Settings |
386 |
Loop Tests |
387 |
Assign variables to the first and second milliamp outputs, define upper and lower range values, cutoffs, and dampings. |
388 |
Assign variables to the discrete output, set flow switch. |
389 |
Assign variables to the discrete input. |
390 |
Assign range values to the milliamp input. |
391 |
Set up Bell-202 port (HART only) and RS-485 port. |
392 |
Set Up Bell 202 Port |
393 |
mA Output Trim |
394 |
Note: To assign action to discrete inputs go to alert setup, discrete events, assign discrete actions |
395 |
CM Configuration |
396 |
Methods |
397 |
Concentration |
398 |
Extrapolation Alert |
399 |
Reference Conditions |
400 |
建议æªæ½ï¼
1. æ£æ¥æ¯å¦åå¨å¢ç¶æµã
2. æ¥çè¯æåééªè¯ç®¡æ¯å¦å¨æ¯å¨ãå·¦å³ææå
件åºé«äº 10mVã
3. æ£æ¥ä¼ æå¨çµè·¯ã
4. æ£æ¥ä¼ æå¨ç®¡æ¯å¦å µå¡ã
5. å¦ææ¨æ³è¦æ¹åè¦æ¥ä¸¥é级å«ï¼è¯·è³ Configureï¼é
ç½®ï¼-> Alert Setupï¼è¦æ¥è®¾ç½®ï¼-> Alert Severityï¼è¦æ¥ä¸¥é级å«ï¼å±å¹ã
6. å¦æé®é¢ä»ç¶åå¨ï¼è¯·èç³»é«åå
¬å¸ã |
401 |
建议æªæ½ï¼
1. éªè¯ä¼ æå¨å·²è¿æ¥å°åéå¨ã
2. æ£æ¥ä¼ æå¨ RTD çµè·¯ã
3. éªè¯è¿ç¨æ¸©åº¦å¨ä¼ æå¨ååéå¨çèå´ä¹å
ã
4. å¦æé®é¢ä»ç¶åå¨ï¼è¯·èç³»é«åå
¬å¸ã |
402 |
建议æªæ½ï¼
1. å¦æåå¨å
¶ä»è¦æ¥ï¼å
¸åçæ A003ãA006ãA008ãA102 æ A105ï¼ï¼é¦å
解å³è¿äºè¦æ¥ãå¦æ A005 è¦æ¥ä»ç¶åå¨ï¼è¯·ç»§ç»æ§è¡ä»¥ä¸å»ºè®®ã
2. æ¥çè¯æåééªè¯ç®¡æ¯å¦å¨æ¯å¨ãå·¦å³ææå
件åºé«äº 10mVã
3. æ£æ¥ä¼ æå¨çµè·¯ã
4. éè¿éªè¯å¯åº¦ï¼æ£æ¥ä¼ æå¨ç®¡æ¯å¦è
èã
5. å¦æé®é¢ä»ç¶åå¨ï¼è¯·èç³»é«åå
¬å¸ã |
403 |
建议æªæ½ï¼
1. æ£æ¥ç¹æ§åãç¹å«è¦éªè¯ä¼ æå¨æ ç¾ä¸ç Flow FCF å K1 å¼ã
2. å¦ææ¨æ³è¦æ¹åè¦æ¥ä¸¥é级å«ï¼è¯·è³ Configureï¼é
ç½®ï¼-> Alert Setupï¼è¦æ¥è®¾ç½®ï¼-> Alert Severityï¼è¦æ¥ä¸¥é级å«ï¼å±å¹ã
3. å¦æé®é¢ä»ç¶åå¨ï¼è¯·èç³»é«åå
¬å¸ã |
404 |
建议æªæ½ï¼
1. æ£æ¥ç¹æ§åãç¹å«è¦éªè¯ä¼ æå¨æ ç¾ä¸ç FlowCal å K1 å¼ã
2. å¦ææ¨æ³è¦æ¹åè¦æ¥ä¸¥é级å«ï¼è¯·è³ Configureï¼é
ç½®ï¼-> Alert Setupï¼è¦æ¥è®¾ç½®ï¼-> Alert Severityï¼è¦æ¥ä¸¥é级å«ï¼å±å¹ã
3. å¦æé®é¢ä»ç¶åå¨ï¼è¯·èç³»é«åå
¬å¸ã |
405 |
建议æªæ½ï¼
1. å¦æåå¨å
¶ä»è¦æ¥ï¼å
¸åçæ A003ãA006ãA102 æ A105ï¼ï¼é¦å
解å³è¿äºè¦æ¥ãå¦æ A008 è¦æ¥ä»ç¶åå¨ï¼è¯·ç»§ç»æ§è¡ä»¥ä¸å»ºè®®ã
2. éªè¯è¿ç¨ãæ£æ¥æµé管æ¯å¦å¤¹æ°ãæ¯å¦å
满ã管å
æ¯å¦æå¼ç©æè
æµé管æ¯å¦ææå£ç°è±¡ã
3. æ£æ¥ä¼ æå¨çµè·¯ã
4. éªè¯å¯åº¦ç¹å¾å并éªè¯é
ç½®ä¸ä¼ æå¨æ ç¾ç¸å¹é
ã
5 æ¥çè¯æåé以éªè¯å管é¢çæ¯å¦å·²å¨æ£ç¡®çä¼ æå¨ç±»åèå´å
ã
6. å¦ææ¨æ³è¦æ¹åè¦æ¥ä¸¥é级å«ï¼è¯·è³ Configureï¼é
ç½®ï¼-> Alert Setupï¼è¦æ¥è®¾ç½®ï¼-> Alert Severityï¼è¦æ¥ä¸¥é级å«ï¼å±å¹ã
7. å¦æé®é¢ä»ç¶åå¨ï¼è¯·èç³»é«åå
¬å¸ã |
406 |
建议æªæ½ï¼
1. å
许æµé计é¢çï¼å¤§çº¦ 30 ç§ï¼ãä¸æ¦æµé计为æ£å¸¸è¿è¡å好åå¤ï¼é误è¦æ¥å°±ä¼éä¹æ¶å¤±ã
2. æ£æ¥è¾å
¥çµåç¡®ä¿å
¶å¤äº 12 è³ 15 V ä¹é´ã
3. å¦æè¦æ¥æ²¡ææ¶å¤±ï¼ç¡®ä¿ä¼ æå¨å®å
¨å
满æå®å
¨æ空ã
4. æ£æ¥ä¼ æå¨çµè·¯ã
5. å¦ææ¨æ³è¦æ¹åè¦æ¥ä¸¥é级å«ï¼è¯·è³ Configureï¼é
ç½®ï¼-> Alert Setupï¼è¦æ¥è®¾ç½®ï¼-> Alert Severityï¼è¦æ¥ä¸¥é级å«ï¼å±å¹ã |
407 |
建议æªæ½ï¼
1. å¦æå¨åéå¨è°é¶æ¶åºç°è¦æ¥ï¼ç¡®ä¿æ²¡ææµééè¿ä¼ æå¨ï¼ç¶åéè¯ã
2. éæ°ç»æµé计ä¸çµæ¥è§£é¤è¦æ¥ã
3. å¿
è¦æ¶ï¼æ¢å¤å·¥åé¶ç¹ï¼ä½¿æµé计åå°è¿è¡ç¶æã
4. å¦ææ¨æ³è¦æ¹åè¦æ¥ä¸¥é级å«ï¼è¯·è³ Configureï¼é
ç½®ï¼-> Alert Setupï¼è¦æ¥è®¾ç½®ï¼-> Alert Severityï¼è¦æ¥ä¸¥é级å«ï¼å±å¹ã
5. å¦æå¨å¯åº¦æ ¡åæé´åºç°è¦æ¥ï¼è¯·èç³»é«åå
¬å¸ã |
408 |
????:
1. ?????????????,???????????,?????
2. ??????????????
3. ???,??????,???????????
4. ?????????????,?? Configure(??)-> Alert Setup(????)-> Alert Severity(??????)???
5. ?????????????,???????? |
409 |
建议æªæ½ï¼
1. å
解å³å
¶å®æ´»å¨è¦æ¥ã
2. éæ°ç»æµé计ä¸çµã
3. å¦ææç»è¦æ¥ï¼åéå¨å¯è½éè¦ç»´ä¿®ã请èç³»é«åå
¬å¸ã |
410 |
建议æªæ½ï¼
1. æ£æ¥ä¼ æå¨ RTD çµè·¯ã
2. éªè¯è¿ç¨æ¸©åº¦å¨ä¼ æå¨ååéå¨çèå´ä¹å
ã
3. å¦ææ¨æ³è¦æ¹åè¦æ¥ä¸¥é级å«ï¼è¯·è³ Configureï¼é
ç½®ï¼-> Alert Setupï¼è¦æ¥è®¾ç½®ï¼-> Alert Severityï¼è¦æ¥ä¸¥é级å«ï¼å±å¹ã
4. å¦æé®é¢ä»ç¶åå¨ï¼è¯·èç³»é«åå
¬å¸ã |
411 |
建议æªæ½ï¼
1.éæ°ç»åéå¨ä¸çµã
2.å¦æé®é¢ä»ç¶åå¨ï¼è¯·èç³»é«åå
¬å¸ã |
412 |
建议æªæ½ï¼
1. 对ç
§ä¼ æå¨æ ç¾æ£æ¥ç¹å¾åãç¹å«æ¯éªè¯ Flow FCFãK1 å K2 å¼ã
2. å¦ææ¨æ³è¦æ¹åè¦æ¥ä¸¥é级å«ï¼è¯·è³ Configureï¼é
ç½®ï¼-> Alert Setupï¼è¦æ¥è®¾ç½®ï¼-> Alert Severityï¼è¦æ¥ä¸¥é级å«ï¼å±å¹ã
3. å¦æé®é¢ä»ç¶åå¨ï¼è¯·èç³»é«åå
¬å¸ã |
413 |
建议æªæ½ï¼
1. 对ç
§ä¼ æå¨æ ç¾æ£æ¥ç¹å¾åãç¹å«æ¯éªè¯ FlowCalãK1 å K2 å¼ã
2. å¦ææ¨æ³è¦æ¹åè¦æ¥ä¸¥é级å«ï¼è¯·è³ Configureï¼é
ç½®ï¼-> Alert Setupï¼è¦æ¥è®¾ç½®ï¼-> Alert Severityï¼è¦æ¥ä¸¥é级å«ï¼å±å¹ã
3. å¦æé®é¢ä»ç¶åå¨ï¼è¯·èç³»é«åå
¬å¸ã |
414 |
建议æªæ½ï¼
1. å¦æ A017 å¤äºæ´»å¨ç¶æï¼åå
解å³å®ã
2. 对ç
§ä¼ æå¨æ ç¾æ£æ¥ç¹å¾åãç¹å«æ¯éªè¯ Flow FCFãK1 å K2 å¼ã
3. æ£æ¥ä¼ æå¨ RTD çµè·¯ã
4. å¦æé®é¢ä»ç¶åå¨ï¼è¯·èç³»é«åå
¬å¸ã |
415 |
建议æªæ½ï¼
1. éªè¯åéå¨ä¸æ ¸å¿å¤çå¨ä¹é´çæ¥çº¿ã
2. éªè¯åéå¨ä¸æ ¸å¿å¤çå¨ççµæºã
3. éæ°ç»åéå¨ä¸çµã
4. å¦æé®é¢ä»ç¶åå¨ï¼è¯·èç³»é«åå
¬å¸ã |
416 |
建议æªæ½ï¼
1. å¯ä»¥ç±ç¨æ·éè¿å°åéå¨è®¾ç½®åå®å
¨æ¨¡å¼æ¥è§£é¤è¦æ¥ï¼ä½æ¯éè¦ç»ææçç¨åºå¯å°åéå¨ã |
417 |
建议æªæ½ï¼
1. éªè¯æ ¸å¿å¤çå¨çè¾å
¥çµåè³å°ä¸º 12Vã
2. æ£æ¥çµæºåææççµæºæ¥çº¿ã |
418 |
建议æªæ½ï¼
1. æ£æ¥æ¯å¦åå¨å¢ç¶æµã
2. æ¥çè¯æåééªè¯ç®¡æ¯å¦å¨æ¯å¨ãå·¦å³ææå
件åºé«äº 10mVã
3. æ£æ¥ä¼ æå¨çµè·¯ã
4. æ£æ¥ä¼ æå¨ç®¡æ¯å¦å µå¡ã
5. å¦ææ¨æ³è¦æ¹åè¦æ¥ä¸¥é级å«ï¼è¯·è³ Configureï¼é
ç½®ï¼-> Alert Setupï¼è¦æ¥è®¾ç½®ï¼-> Alert Severityï¼è¦æ¥ä¸¥é级å«ï¼å±å¹ã
6. å¦æé®é¢ä»ç¶åå¨ï¼è¯·èç³»é«åå
¬å¸ã |
419 |
建议æªæ½ï¼
1. éªè¯æ¯«å®è¾åºèå´å¼ç设置éå½ã
2. å¦ææ¨æ³è¦æ¹åè¦æ¥ä¸¥é级å«ï¼è¯·è³ Configureï¼é
ç½®ï¼-> Alert Setupï¼è¦æ¥è®¾ç½®ï¼-> Alert Severityï¼è¦æ¥ä¸¥é级å«ï¼å±å¹ã |
420 |
建议æªæ½ï¼
1. æ£æ¥ HART å°åãå¦æéé¶ï¼è®¾ç½®âmA Output Actionâï¼æ¯«å®è¾åºå¨ä½ï¼åæ°ï¼å¯ç¨âLive mA Outputâï¼å®æ¶æ¯«å®è¾åºï¼ï¼æè
å¦ææ³è¦å¤åæ¯æ¨¡å¼ï¼åéè¿è½¬è³ Configureï¼é
ç½®ï¼-> Alert Setupï¼è¦æ¥è®¾ç½®ï¼-> Alert Severityï¼è¦æ¥ä¸¥é级å«ï¼å±å¹æ¥å°è¦æ¥ä¸¥é级å«æ´æ¹ä¸ºå¿½ç¥ã
2. å¦ææ£å¨è¿è¡æ¯«å®è¾åºè°æ´ï¼åééåºæ¯«å®è¾åºè°æ´ã
3. å¦ææ£å¨è¿è¡æ¯«å®è¾åºåè·¯æµè¯ï¼åééåºæ¯«å®è¾åºåè·¯æµè¯ã
4. æ£æ¥æ¯å¦å·²éè¿æ°åé讯ææ¬å°æ¾ç¤ºå¨å°è¾åºè®¾ç½®ä¸ºåºå®å¼ã |
421 |
建议æªæ½ï¼
1. å
许æµé计å®ææ ¡åã
2. 对äºè°é¶æ ¡åç¨åºï¼æ¨å¯ä»¥ä¸æ¢æ ¡åï¼å¹¶å°é¶ç¹æ¶é´åæ°è®¾ç½®ä¸ºè¾ä½å¼ï¼ç¶åéæ°å¼å§æ ¡åã
3. å¦ææ¨æ³è¦æ¹åè¦æ¥ä¸¥é级å«ï¼è¯·è³ Configureï¼é
ç½®ï¼-> Alert Setupï¼è¦æ¥è®¾ç½®ï¼-> Alert Severityï¼è¦æ¥ä¸¥é级å«ï¼å±å¹ã |
422 |
建议æªæ½ï¼
1. ä¸ééåä»»ä½æªæ½ã
2. å¦éè¦ï¼è½¬è³ Configureï¼é
ç½®ï¼-> Alert Setupï¼è¦æ¥è®¾ç½®ï¼-> Alert Severityï¼è¦æ¥ä¸¥é级å«ï¼å±å¹ï¼å°è¦æ¥ä¸¥é级å«éæ°é
置为 Ignoreï¼å¿½ç¥ï¼ã |
423 |
建议æªæ½ï¼
1. æ¹åé¢çè¾åºçæ¯ä¾å åï¼å¾å°æ´åéç设置ã
2. å¦æä¸çº§åé设置为ä½ç§¯æµéï¼ä½å¯åº¦æ空管ä¼é æé¢çè¾åºé¥±åã
3. å¦ææ¨æ³è¦æ¹åè¦æ¥ä¸¥é级å«ï¼è¯·è³ Configureï¼é
ç½®ï¼-> Alert Setupï¼è¦æ¥è®¾ç½®ï¼-> Alert Severityï¼è¦æ¥ä¸¥é级å«ï¼å±å¹ã |
424 |
建议æªæ½ï¼
1. éåºé¢çè¾åºåè·¯æµè¯ã
2. å¦ææ¨æ³è¦æ¹åè¦æ¥ä¸¥é级å«ï¼è¯·è³ Configureï¼é
ç½®ï¼-> Alert Setupï¼è¦æ¥è®¾ç½®ï¼-> Alert Severityï¼è¦æ¥ä¸¥é级å«ï¼å±å¹ã |
425 |
建议æªæ½ï¼
1. éåºç¦»æ£è¾åºæµè¯ã
2. å¦ææ¨æ³è¦æ¹åè¦æ¥ä¸¥é级å«ï¼è¯·è³ Configureï¼é
ç½®ï¼-> Alert Setupï¼è¦æ¥è®¾ç½®ï¼-> Alert Severityï¼è¦æ¥ä¸¥é级å«ï¼å±å¹ã |
426 |
A119: Discrete Output 2 Fixed |
427 |
建议æªæ½ï¼
1. éè¿è½¬è³ Configureï¼é
ç½®ï¼-> Manual Setupï¼æå¨è®¾ç½®ï¼-> Measurementsï¼æµéï¼-> Concentration Measurementï¼æµåº¦æµéï¼-> Enter Matrixï¼è¿å
¥ç©éµï¼æ¥éªè¯æµåº¦æµé (CM) ç©éµé
ç½®ã |
428 |
建议æªæ½ï¼
1. ç¦ç¨è¾å
¥ä»¿çã
2. å¦ææ¨æ³è¦æ¹åè¦æ¥ä¸¥é级å«ï¼è¯·è³ Configureï¼é
ç½®ï¼-> Alert Setupï¼è¦æ¥è®¾ç½®ï¼-> Alert Severityï¼è¦æ¥ä¸¥é级å«ï¼å±å¹ã |
429 |
建议æªæ½ï¼
1. æ£æ¥ä¼ æå¨çµè·¯ã
2. å¦æè¿æ¯å¯ä¸æ¿æ´»çæ¥è¦ï¼å¯ä»¥å¿½ç¥ãå¦æéè¦ï¼å°æ¥è¦ä¸¥é级å«éæ°é
置为 Ignoreï¼å¿½ç¥ï¼ã
3. å¦ææ¨æ³è¦æ¹åè¦æ¥ä¸¥é级å«ï¼è¯·è³ Configureï¼é
ç½®ï¼-> Alert Setupï¼è¦æ¥è®¾ç½®ï¼-> Alert Severityï¼è¦æ¥ä¸¥é级å«ï¼å±å¹ã |
430 |
建议æªæ½ï¼
1. éªè¯åéå¨ä¸æ ¸å¿å¤çå¨çè¾å
¥çµåæ£ç¡®ã
2. å¦ææ¨æ³è¦æ¹åè¦æ¥ä¸¥é级å«ï¼è¯·è³ Configureï¼é
ç½®ï¼-> Alert Setupï¼è¦æ¥è®¾ç½®ï¼-> Alert Severityï¼è¦æ¥ä¸¥é级å«ï¼å±å¹ã
3. å¦æé®é¢ä»ç¶åå¨ï¼è¯·èç³»é«åå
¬å¸ã |
431 |
建议æªæ½ï¼
1. æ£æ¥ä¼ æå¨æ¯å¦å
满ã
2. æ£æ¥å¢ç¶æµéå®èå´ç设置æ¯å¦éå½ã
3. éªè¯å¯åº¦ä¸´çå¼è³å°ä¸º 0.2 g/ccã
4. å¦ææ¨æ³è¦æ¹åè¦æ¥ä¸¥é级å«ï¼è¯·è³ Configureï¼é
ç½®ï¼-> Alert Setupï¼è¦æ¥è®¾ç½®ï¼-> Alert Severityï¼è¦æ¥ä¸¥é级å«ï¼å±å¹ã |
432 |
建议æªæ½ï¼
1. ä¸ééåä»»ä½æªæ½ã
2. å¦ææ¨æ³è¦æ¹åè¦æ¥ä¸¥é级å«ï¼è¯·è³ Configureï¼é
ç½®ï¼-> Alert Setupï¼è¦æ¥è®¾ç½®ï¼-> Alert Severityï¼è¦æ¥ä¸¥é级å«ï¼å±å¹ã |
433 |
建议æªæ½ï¼
1. éªè¯è¿ç¨ã
2. éªè¯ç³æ²¹æµéåç
§è¡¨å温度çé
ç½®ã
3. å¦ææ¨æ³è¦æ¹åè¦æ¥ä¸¥é级å«ï¼è¯·è³ Configureï¼é
ç½®ï¼-> Alert Setupï¼è¦æ¥è®¾ç½®ï¼-> Alert Severityï¼è¦æ¥ä¸¥é级å«ï¼å±å¹ã |
434 |
建议æªæ½ï¼
1. å¦æåå¨å
¶ä»æ¥è¦ï¼é¦å
解å³è¿äºæ¥è¦ã
2. éªè¯è¿ç¨ã
3. éªè¯ç³æ²¹æµéåç
§è¡¨åå¯åº¦çé
ç½®ã
4. å¦ææ¨æ³è¦æ¹åè¦æ¥ä¸¥é级å«ï¼è¯·è³ Configureï¼é
ç½®ï¼-> Alert Setupï¼è¦æ¥è®¾ç½®ï¼-> Alert Severityï¼è¦æ¥ä¸¥é级å«ï¼å±å¹ã |
435 |
建议æªæ½ï¼
1. éªè¯è¿ç¨æ¸©åº¦åå¯åº¦ã
2. éªè¯æµåº¦æµé (CM) æ¨æµè¦æ¥éå®ã
3. éªè¯è¿ç¨ãå¦æ管æ¯ç©ºçæè
éªè¯è¿ç¨ä¸ææ°ä½ï¼çå¾
æ
åµèªè¡æ¶é¤ã
4. å¦ææ¨æ³è¦æ¹åè¦æ¥ä¸¥é级å«ï¼è¯·è³ Configureï¼é
ç½®ï¼-> Alert Setupï¼è¦æ¥è®¾ç½®ï¼-> Alert Severityï¼è¦æ¥ä¸¥é级å«ï¼å±å¹ã |
436 |
Frequency input from external device is too high. |
437 |
Recommended Actions:
1. Verify that frequency input parameters are set to appropriate values. |
438 |
Batch total has exceeded target:
Batch has not ended.
Flow is still being measured. |
439 |
Recommended Actions:
1. Check wiring for discrete output indicating overrun.
2. Check device connected to discrete output indicating overrun.
3. Enable batch Automatic Overshoot Compensation (AOC).
4. After cause has been diagnosed, press RESET or START to start new batch. |
440 |
A129: Internal Error (Display) |
441 |
(Custody transfer only) Readback function from transmitter display indicates error or failure. |
442 |
Recommended Actions:
1. Cycle power to the flow meter.
2. If problem persists, call Micro Motion. |
443 |
(Custody transfer only) The ticket printer is out of paper. |
444 |
Recommended Actions:
1. Add paper to the printer. |
445 |
A134: Memory Error (Display) |
446 |
Memory or checksum error in transmitter display. |
447 |
Recommended Actions:
1. Cycle power to the flow meter.
2. The flow meter might need service. Contact Micro Motion. |
448 |
A135: Transmitter/Display Communications Error |
449 |
Internal communication error with transmitter display. |
450 |
A136: Power Outage |
451 |
The power was off for at least 30 seconds. |
452 |
Recommended Actions:
1. No action required. |
453 |
A137: Measurement Paused |
454 |
Continuous mode measurements are paused. |
455 |
Recommended Actions:
1. No action required. If desired, resume measurement. |
456 |
A138: Transient Bubble Remediation (TBR) Active |
457 |
The drive gain has exceeded the configured TBR threshold and the configured TBR action has been implemented. |
458 |
A139: External Water Cut Out-of-Range |
459 |
The water cut measured by the water cut monitor is above the configured External Water Cut Limit. |
460 |
建议æªæ½ï¼
1. éªè¯è¿ç¨å¹¶æ£æ¥æ¯å¦åå¨å¢ç¶æµã
2. æ£æ¥è¯æåéã
3. æ£æ¥ä¼ æå¨çµè·¯ã
4. æ£æ¥ä¼ æå¨ç®¡æ¯å¦è
èã
5. å¦æé®é¢ä»ç¶åå¨ï¼è¯·èç³»é«åå
¬å¸ã |
461 |
Reference Condition |
462 |
Read modbus register values. |
463 |
Electronic Conditions |
464 |
Sensor Conditions |
465 |
Recommended Actions:
1. Check for slug flow.
2. Check the test points.
3. Check the sensor circuitry.
4. Check sensor tubes for plugging.
5. If the problem persists, contact Micro Motion. |
466 |
Recommended Actions:
1. Check the sensor RTD circuitry.
2. Verify that process temperature is within range of sensor and transmitter.
3. If the problem persists, contact Micro Motion. |
467 |
Process Conditions |
468 |
Recommended Actions:
1. If other alerts are present (typically, A003, A006, A008, A102, or A105), resolve those alerts first. If the A005 alert persists, continue with the suggestions below.
2. Verify process and check for slug flow.
3. Check the test points.
4. Check the sensor circuitry.
5. Check the sensor tubes for erosion.
6. If the problem persists, contact Micro Motion. |
469 |
Configuration Conditions |
470 |
Recommended Actions:
1. Check the characterization. Specifically, verify the FCF and K1 values.
2. If the problem persists, contact Micro Motion. |
471 |
Recommended Actions:
1. If other alerts are present (typically, A003, A006, A102, or A105), resolve those alerts first. If the A008 alert persists, continue with the suggestions below.
2. Verify process. Check for air in the flow tubes, tubes not filled, foreign material in tubes, or coating in tubes.
3. Check for slug flow.
4. Check the sensor circuitry.
5. Verify calibration factors in transmitter configuration.
6. Check the test points.
7. If the problem persists, contact Micro Motion. |
472 |
Recommended Actions:
1. Allow the flowmeter to warm up (approximately 30 seconds). The error should disappear once the flowmeter is ready for normal operation.
2. If alert does not clear, make sure that the sensor is completely full or completely empty.
3. Check the sensor circuitry. |
473 |
Recommended Actions:
1. If alert appears during a transmitter zero, ensure that there is no flow through the sensor, then retry.
2. Cycle power to the flowmeter, then retry.
3. If appropriate, restore the factory zero to return the flowmeter to operation. |
474 |
Recommended Actions:
1. Ensure that there is no flow through the sensor, then retry.
2. Cycle power to the flowmeter, then retry.
3. If appropriate, restore the factory zero to return the flowmeter to operation. |
475 |
Recommended Actions:
1. Remove or reduce sources of electromechanical noise, then retry. Sources of noise include mechanical pumps, pipe stress at sensor, electrical interference, or vibration effects from nearby machinery.
2. Cycle power to the flowmeter, then retry.
3. If appropriate, restore the factory zero to return the flowmeter to operation. |
476 |
Recommended Actions:
1. Cycle power to the flowmeter.
2. The transmitter might need service. Contact Micro Motion. |
477 |
Recommended Actions:
1. Check the sensor RTD circuitry.
2. Verify that process temperature is within range of sensor and transmitter.
3. Check the characterization. Specifically, verify the FCF and K1 values.
4. If the problem persists, contact Micro Motion. |
478 |
Recommended Actions:
1.Cycle power to the transmitter.
2.If problem persists, call Micro Motion. |
479 |
Recommended Actions:
1. Check the characterization. Specifically, verify the FCF and K1 values.
2. Check the sensor RTD circuitry.
3. If the problem persists, contact Micro Motion. |
480 |
Recommended Actions:
1.Cycle power to the flowmeter.
2.The transmitter might need service. Contact Micro Motion. |
481 |
Recommended Actions:
1. Verify the wiring between the Transmitter and Core Processor.
2. Cycle power to the transmitter.
3. If problem persists, call Micro Motion. |
482 |
Recommended Actions:
1. Alarm can be cleared by user, but authorized procedure is required to reestablish security. |
483 |
Recommended Actions:
1. Cycle power to the flowmeter.
2. The transmitter might need service or upgrading. Contact Micro Motion. |
484 |
Recommended Actions:
1. Cycle power to the flowmeter.
2. Contact Micro Motion. |
485 |
Recommended Actions:
1. Verify process. Check for air in the flow tubes, tubes not filled, foreign material in tubes, or coating in tubes. |
486 |
Recommended Actions:
1. Check the sensor circuitry.
2. If this is the only active alarm, it can be ignored. If desired, reconfigure the alarm severity to Ignore. |
487 |
Recommended Actions:
1. Contact Micro Motion to upgrade the transmitter software.
Note: The transmitter is still functional. |
488 |
Recommended Actions:
1. No action required.
2. If desired, reconfigure the alarm severity to Ignore. |
489 |
Recommended Actions:
1. HART polling connection to external device has failed. Ensure that external device is available:
2. Verify device operation.
3. Verify wiring.
4. Verify polling configuration. |
490 |
Recommended Actions:
1. Verify process.
2. Verify configuration for Petroleum Measurement reference table and temperature. |
491 |
Recommended Actions:
1. Verify process.
2. Verify configuration for Petroleum Measurement reference table and density. |
492 |
Recommended Actions:
1. Verify the process temperature and density.
2. Verify Concentration Measurement (CM) configuration. |
493 |
Recommended Actions:
1. Verify process and check for slug flow.
2. Check the test points.
3. Check the sensor circuitry.
4. Check the sensor tubes for erosion.
5. If the problem persists, contact Micro Motion. |
494 |
Recommended Actions:
1. Verify that mA output range values are set to appropriate values. |
495 |
Recommended Actions:
1. The first command to recognize this condition will automatically reset this flag.
2. This flag may also be set following a Master Reset or a Self Test. |
496 |
Recommended Actions:
1. Check the test points.
2. Check the sensor circuitry.
3. If the problem persists, contact Micro Motion. |
497 |
Recommended Actions:
1. Allow the flowmeter to complete calibration.
2. For zero calibration procedures, you may abort the calibration, set the zero time parameter to a lower value, and restart the calibration. |
498 |
Recommended Actions:
1. Disable output simulation. |
499 |
Recommended Actions:
1. Check the HART address. If non-zero, enable Loop Current Mode parameter.
2. Exit mA output trim.
3. Exit mA output loop test.
4. Check to see if the output has been fixed via digital communication. |
500 |
Recommended Actions:
1. Change frequency output scaling factors to more appropriate settings. |
501 |
Recommended Actions:
1. Exit frequency output loop test. |
502 |
Recommended Actions:
1. Exit mA output trim.
2. Exit mA output loop test.
3. Check to see if the output has been fixed via digital communications. |
503 |
Recommended Actions:
1. Verify Concentration Measurement (CM) configuration. |
504 |
Classic View |
505 |
mA Output 1 |
506 |
mA Output 2 |
507 |
?????? |
508 |
??????? |
509 |
??????? |
510 |
???????? |
511 |
????? |
512 |
????? |
513 |
æ å® |
514 |
æ§è¡é¶ç¹æ å®ã |
515 |
æ§è¡å¯åº¦æ å®ã |
516 |
Performs a temperature calibration. |
517 |
å
³é并éæ°æå¼è£
ç½®çµæºï¼æ¤æ¶ä¸ä¼å½±åè£
ç½®ç»æã |
518 |
使ç¨åºåç»æéè¦çç°æè£
ç½®ç»æã |
519 |
å¦æ主æºæ æ³èªå¨å¤ä½ç»ææ¹åæ è®°ï¼åå°å
¶æå¨å¤ä½ã |
520 |
FMU860 |
521 |
DT |
522 |
DVC |
523 |
FCX |
524 |
AS800 |
525 |
340T |
526 |
340C |
527 |
344 |
528 |
Siemens Micro K |
529 |
SITRANS L |
530 |
SIPAN PH |
531 |
SITRANS P |
532 |
75SMT |
533 |
UNIDELTA |
534 |
8320 |
535 |
SX5100 |
536 |
TSV175 |
537 |
DMU |
538 |
3780 |
539 |
BM70 |
540 |
8u |
541 |
low |
542 |
high |
543 |
tmp_av |
544 |
æ´æ¹ç»æå¯è½å½±ååéå¨æä½ãç¡®ä¿å°æ§å¶å路设置为æå¨æä½åå继ç»ã |
545 |
Calibration is in progress... |
546 |
Density calibration is completed. |
547 |
Frequency Output: |
548 |
Enter Meter Value: |
549 |
Selftest complete |
550 |
No Device Problems seen during Selftest |
551 |
WARN-Stopping totalizer disables frequency output |
552 |
ERROR: Totalizer reset not allowed when flow is not zero. |
553 |
Ev1 Triggered: Yes |
554 |
Ev1 Triggered: No |
555 |
Ev2 Triggered: Yes |
556 |
Ev2 Triggered: No |
557 |
Transmitter status complete |
558 |
Transmitter status OK |
559 |
NOTE-Loop may be returned to automatic control |
560 |
NOTE-Send PV assignment before modifying range values. |
561 |
NOTE-Send SV assignment before modifying range values. |
562 |
NOTE-Send TV assignment before modifying frequency scaling. |
563 |
K-Factor: %{yatemp} pulses/unit. |
564 |
floatFreqVal |
565 |
floatRateVal |
566 |
Please select Burst Mode: |
567 |
A problem was detected |
568 |
Abort;Fix and Retry |
569 |
Choose Burst Variable: |
570 |
Burst mode configuration is completed.
Note-Please return loop to automatic control. |
571 |
select |
572 |
floatPulsesPerUnit |
573 |
floatUnitsPerPulse |
574 |
Current primary variable selection is mass flow rate.
Select Primary Variable: |
575 |
Current Selection;Mass Flow Rate;Temperature;Density;Volume Flow Rate;Viscosity;Differential Pressure;Event1;Event2 |
576 |
Current primary variable selection is temperature.
Select Primary Variable: |
577 |
Current primary variable selection is density.
Select Primary Variable: |
578 |
Current primary variable selection is volume flow rate.
Select Primary Variable: |
579 |
Current primary variable selection is viscosity.
Select Primary Variable: |
580 |
Current primary variable selection is differential pressure.
Select Primary Variable: |
581 |
Current primary variable selection is event1.
Select Primary Variable: |
582 |
Current Selection;Mass Flow Rate;Temperature;Density;Volume Flow Rate;Viscosity;Differential Pressure;Differential Pressure;Event1;Event2 |
583 |
Current primary variable selection is event2.
Select Primary Variable: |
584 |
Current secondary variable selection is mass flow rate.
Select Secondary Variable: |
585 |
Current secondary variable Selection is temperature.
Select Secondary Variable: |
586 |
Current secondary variable selection is density.
Select Secondary Variable: |
587 |
Current secondary variable selection is volume flow rate.
Select Secondary Variable: |
588 |
Current secondary variable selection is viscosity
Select Secondary Variable: |
589 |
Current secondary variable selection is differential Pressure
Select Secondary Variable: |
590 |
Current secondary variable selection is event1.
Select Secondary Variable: |
591 |
Current secondary variable selection is event2.
Select Secondary Variable: |
592 |
alarmNum |
593 |
Start Sensor Zero;Reset Mass Total;Reset Volume Total;Reset Petroleum Reference Volume;Reset All Totals;Reset Concentration Reference Volume;Reset Concentration Net Mass;Reset Concentration Net Volume;Start/Stop Totals;Increment Concentration Curve;Print Screen;Print custody transfer screen;Reset Gas Standard Volume Total |
594 |
Starting meter verification, please wait. |
595 |
Meter verification completed: %{0}% |
596 |
Meter verification PASS. |
597 |
Meter verification FAILED. |
598 |
Meter verification error. |
599 |
Meter verification error.
%{0} |
600 |
Meter Verification will hold outputs at last value for about 2 minutes.
Press Next to Start or Cancel to End. |
601 |
Discrete output level is off. |
602 |
Discrete output 1 level is on. |
603 |
fValue |
604 |
Current Primary Variable Selection is %0
Select Primary Variable: |
605 |
Current Secondary Variable Selection is %0
Select Secondary Variable: |
606 |
Priority: Failed - Fix Now
Description:
Continuity failure of drive circuit, LPO, or RPO, or LPO-RPO mismatch when driving.
Recommended Actions:
1. Check for slug flow.
2. Check the test points.
3. Check the sensor circuitry.
4. Check sensor tubes for plugging.
5. If the problem persists, contact Micro Motion. |
607 |
Drive Gain:
Value %0 |
608 |
Priority: Failed - Fix Now
Description:
The value computed for the resistance of the line RTD or the Meter/Case RTD is outside limits.
Recommended Actions:
1. Check the sensor RTD circuitry.
2. Verify that process temperature is within range of sensor and transmitter.
3. If the problem persists, contact Micro Motion |
609 |
Temperature:
Value %0 |
610 |
Priority: Failed - Fix Now
Description:
The measured flow has exceeded the maximum flow rate of the sensor.
Recommended Actions:
1. If other alerts are present (typically, A003, A006, A008, A102, or A105), resolve those alerts first. If the A005 alert persists, continue with the suggestions below.
2. Verify process and check for slug flow.
3. Check the test points
4. Check the sensor circuitry.
5. Check the sensor tubes for erosion.
6. If the problem persists, contact Micro Motion. |
611 |
No Additional Information Available |
612 |
Priority: Failed - Fix Now
Description:
One or more required characterization parameters have not been entered.
Recommended Actions:
1. Check the characterization. Specifically, verify the FCF and K1 values.
2. If the problem persists, contact Micro Motion |
613 |
Flow Cal:
Value %0
K1:
Value %1 uSec
K2:
Value %2 uSec |
614 |
Flow FCF:
Value %0
K1:
Value %1 uSec
K2:
Value %2 uSec |
615 |
Priority: Failed - Fix Now
Description:
The measured density has exceeded 0-10 g/cm3.
Recommended Actions:
1. If other alerts are present (typically, A003, A006, A102, or A105), resolve those alerts first. If the A008 alert persists, continue with the suggestions below.
2. Verify process. Check for air in the flow tubes, tubes not filled, foreign material in tubes, or coating in tubes.
3. Check for slug flow.
4. Check the sensor circuitry.
5. Verify calibration factors in transmitter configuration.
6. Check the test points.
7. If the problem persists, contact Micro Motion |
616 |
Priority: Failed - Fix Now
Description:
Transmitter in power-up mode.
Recommended Actions:
XX |
617 |
Priority: Failed - Fix Now
Description:
Mechanical zero: The resulting zero was greater than 3 microseconds
Temperature or Density Calibrations: many possible causes
Recommended Actions:
1. If alert appears during a transmitter zero, ensure that there is no flow through the sensor, then retry.
2. Cycle power to the flowmeter, then retry.
3. If appropriate, restore the factory zero to return the flowmeter to operation. |
618 |
Priority: Failed - Fix Now
Description:
Mechanical zero: Calibration procedure failed due to reverse flow through the sensor.
Recommended Actions:
1. Ensure that there is no flow through the sensor, then retry.
2. Cycle power to the flowmeter, then retry.
3. If appropriate, restore the factory zero to return the flowmeter to operation. |
619 |
Priority: Failed - Fix Now
Description:
Mechanical zero: Calibration procedure failed due to flow through the sensor.The resulting zero was greater than 3 microseconds.
Recommended Actions:
1. Ensure that there is no flow through the sensor, then retry.
2. Cycle power to the flowmeter, then retry.
3. If appropriate, restore the factory zero to return the flowmeter to operation. |
620 |
Priority: Failed - Fix Now
Description:
Mechanical zero: The resulting zero was greater than 3 microseconds.
Recommended Actions:
1. Remove or reduce sources of electromechanical noise, then retry. Sources of noise include mechanical pumps, pipe stress at sensor, electrical interference, or vibration effects from nearby machinery.
2. Cycle power to the flowmeter, then retry.
3. If appropriate, restore the factory zero to return the flowmeter to operation. |
621 |
Priority: Failed - Fix Now
Description:
Many possible causes.
Recommended Actions:
1. Cycle power to the flowmeter.
2. The transmitter might need service. Contact Micro Motion. |
622 |
Priority: Failed - Fix Now
Description:
The value computed for the resistance of the Line RTD is outside limits.
Recommended Actions:
1. Check the sensor RTD circuitry.
2. Verify that process temperature is within range of sensor and transmitter.
3. Check the characterization. Specifically, verify the FCF and K1 values
4. If the problem persists, contact Micro Motion. |
623 |
Priority: Failed - Fix Now
Description:
The value computed for the resistance of the Meter/Case RTD is outside limits.
Recommended Actions:
1. Check the sensor RTD circuitry.
2. Verify that process temperature is within range of sensor and transmitter.
3. Check the characterization. Specifically, verify the FCF and K1 values
4. If the problem persists, contact Micro Motion. |
624 |
Priority: Failed - Fix Now
Description:
The transmitter has experienced an EEPROM checksum failure.
Recommended Actions:
1.Cycle power to the transmitter.
2.If problem persists, call Micro Motion. |
625 |
Priority: Failed - Fix Now
Description:
A RAM location in the transmitter cannot be written to.
Recommended Actions:
1.Cycle power to the transmitter.
2.If problem persists, call Micro Motion. |
626 |
Priority: Failed - Fix Now
Description:
The flow calibration factor and/or K1 has not been entered since the last master rese
Recommended Actions:
1. Check the characterization. Specifically, verify the FCF and K1 values.
2. If the problem persists, contact Micro Motion. |
627 |
Priority: Failed - Fix Now
Description:
The sensor is recognized as a straight tube but the K1 value indicates a curved tube, or vice versa.
Recommended Actions:
1. Check the characterization. Specifically, verify the FCF and K1 values.
2. Check the sensor RTD circuitry.
3. If the problem persists, contact Micro Motion. |
628 |
Priority: Failed - Fix Now
Description:
Uncorrectable checksum mismatch.
Recommended Actions:
1. Cycle power to the flowmeter.
2. The transmitter might need service. Contact Micro Motion. |
629 |
Priority: Failed - Fix Now
Description:
Communication errors between transmitter and core processor.
Recommended Actions:
1. Verify the wiring between the Transmitter and Core Processor.
2. Cycle power to the transmitter.
3. If problem persists, call Micro Motion. |
630 |
Priority: Failed - Fix Now
Description:
Weights and Measures security seal has been broken.
Recommended Actions:
1. Alarm can be cleared by user, but authorized procedure is required to reestablish security. |
631 |
Priority: Failed - Fix Now
Description:
An attempt to write data to the core processor has failed.
Recommended Actions:
1. Cycle power to the flowmeter.
2. The transmitter might need service or upgrading. Contact Micro Motion. |
632 |
Priority: Failed - Fix Now
Description:
The core processor is not receiving enough power.
Recommended Actions:
1. Check the power supply and all power wiring. |
633 |
Priority: Failed - Fix Now
Description:
Meter verification is in progress, with outputs set to fault.
Recommended Actions:
1. Allow the procedure to complete.
2. If desired, abort the procedure and restart with outputs set to last measured value. |
634 |
Priority: Failed - Fix Now
Description:
Meter verification is in progress, with outputs set to fault or last measured value.
Recommended Actions:
1. Allow the procedure to complete.
2. If desired, abort the procedure and restart with outputs set to continue measuring. |
635 |
Priority: Failed - Fix Now
Description:
No signal from Left Pickoff or Right Pickoff, suggesting that sensor tubes are not vibrating.
Recommended Actions:
1. Verify process. Check for air in the flow tubes, tubes not filled, foreign material in tubes, or coating in tubes. |
636 |
Priority: Failed - Fix Now
Description:
Meter Verification Failed.
Recommended Actions:
1. The test result is not within acceptable limits. Micro Motion recommends that you immediately re-run the meter verification test with outputs held at fault or last measured value. If the meter passes the second test, the fail result can be ignored. If the meter fails the second test, the flow tubes may be damaged. Use the knowledge of your process to consider the type of damage and determine the appropriate action. These actions might include removing the meter from service and physically inspecting the tubes. At a minimum, perform a flow validation and a density calibration. |
637 |
Meter Verification Run Counter: %0
Transmitter Running Hours at Test: %1
Left Pickoff Stiffness: %2 |
638 |
Right Pickoff Stiffness: %0 |
639 |
Priority: Failed - Fix Now
Description:
Meter Verification Aborted.
Reason:
User Initiated Abort
Recommended Actions:
Wait for 15 seconds before starting meter verification again. |
640 |
Priority: Failed - Fix Now
Description:
Meter Verification Aborted.
Reason:
Frequency Drift
Recommended Actions:
Ensure temperature, flow and density are stable and run meter verification again. |
641 |
Priority: Failed - Fix Now
Description:
Meter Verification Aborted.
Reason:
High Drive Gain
Recommended Actions:
Ensure flow is steady and minimize entrained gas and run meter verification again. |
642 |
Priority: Failed - Fix Now
Description:
Meter Verification Aborted.
Reason:
Unstable Flow
Recommended Actions:
Reduce flow rate and run meter verification again. |
643 |
Priority: Failed - Fix Now
Description:
Meter Verification Aborted.
Reason:
No Air Reference
Recommended Actions:
Perform factory calibration on air. |
644 |
Priority: Failed - Fix Now
Description:
Meter Verification Aborted.
Reason:
No Water Reference
Recommended Actions:
Perform factory calibration on water. |
645 |
Priority: Failed - Fix Now
Description:
Meter Verification Aborted.
Reason:
Missing Configuration
Recommended Actions:
Load verification parameter registers with proper values. |
646 |
Priority: Failed - Fix Now
Description:
Meter Verification Aborted.
Reason:
Other
Recommended Actions:
Run meter verification again. If abort persists, call Micro Motion customer support. |
647 |
Meter Verification Run Counter: %0
Transmitter Running Hours at Test: %1
Abort Code: %2 |
648 |
Left Pickoff Stiffness: %0
Right Pickoff Stiffness: %1 |
649 |
Priority: Advisory
Description:
The calculated amount of current output is outside of the linear range.
Recommended Actions:
1. Verify that mA output range values are set to appropriate values. |
650 |
Primary Variable:
%0
%0:
Value %1 %2 |
651 |
PV LRV:
Value %0 %1
PV URV:
Value %2 %3 |
652 |
Priority: Advisory
Description:
Non-zero HART address configured, or user has set the mA output to a fixed value.
Recommended Actions:
1. Check the HART address. If non-zero, set mA Output Action parameter to enable Live mA Output.
2. Exit mA output trim.
3. Exit mA output loop test.
4. Check to see if the output has been fixed via digital communications. |
653 |
HART Address:
%0
mAO Fault Action:
%1 |
654 |
Priority: Maintenance - Fix Soon
Description:
The drive power (current/voltage) is at its maximum.
Recommended Actions:
1. Check the sensor circuitry.
2. If this is the only active alarm, it can be ignored. If desired, reconfigure the alarm severity to Ignore. |
655 |
Priority: Maintenance - Fix Soon
Description:
The core processor was unable to successfully store the totalizers and inventories on the last power down and must rely on the previously saved values. These values may be up to two hours old.
Recommended Actions:
1. Contact Micro Motion to upgrade the transmitter software.
Note: The transmitter is still functional. |
656 |
Priority: Advisory
Description:
A calibration procedure is in progress.
Recommended Actions:
1. Allow the flowmeter to complete calibration.
2. For zero calibration procedures, you may abort the calibration, set the zero time parameter to a lower value, and restart the calibration. |
657 |
Priority: Maintenance - Fix Soon
Description:
The density has exceeded the user-defined slug (density) limits.
Recommended Actions:
1. Check that sensor is completely full.
2. Check that slug limits are set to appropriate values. |
658 |
Slug High Limit:
Value %0 g/Cucm
Slug Low Limit:
Value %1 g/Cucm
Slug Duration:
Value %2 sec
Left Pickoff Amplitude:
Value %3 V
Right Pickoff Amplitude:
Value %4 V
Drive Gain:
Value %5 % |
659 |
Priority: Advisory
Description:
Device is in HART burst mode.
Recommended Actions:
1. No action required.
2. If desired, reconfigure the alarm severity to Ignore. |
660 |
Priority: Maintenance - Fix Soon
Description:
Transmitter has been restarted.
Recommended Actions:
1. No action required. |
661 |
Priority: Maintenance - Fix Soon
Description:
Event 1 has been triggered.
Recommended Actions:
1. No action required.
2. If desired, reconfigure the alarm severity to Ignore. |
662 |
Event 1 Setpoint:
Value %0
Event 1 Variable:
%1
Event 1 Type:
%2 |
663 |
Priority: Maintenance - Fix Soon
Description:
Event 2 has been triggered.
Recommended Actions:
1. No action required.
2. If desired, reconfigure the alarm severity to Ignore. |
664 |
Event 2 Setpoint:
Value %0
Event 2 Variable:
%1
Event 2 Type:
%2 |
665 |
Priority: Advisory
Description:
Process variable assigned to frequency output is outside configured scale limits.
Recommended Actions:
1. Change frequency output scaling factors to more appropriate settings. |
666 |
Third Variable:
%0
%0:
Value %1 %2 |
667 |
Rate Factor:
Value %0 Hz
Pulses/Unit:
Value %1
Units/Pulse:
Value %2 |
668 |
Priority: Advisory
Description:
User has set the frequency output to a fixed value.
Recommended Actions:
1. Exit frequency output loop test. |
669 |
Tube Frequency:
Value %0 Hz |
670 |
Priority: Advisory
Description:
User has set the mA output to a fixed value.
Recommended Actions:
1. Exit mA output trim.
2. Exit mA output loop test.
3. Check to see if the output has been fixed via digital communications. |
671 |
Priority: Maintenance - Fix Soon
Description:
No response received from polled device.
Recommended Actions:
1. HART polling connection to external device has failed. Ensure that external device is available:
2. Verify device operation.
3. Verify wiring.
4. Verify polling configuration. |
672 |
Poll Control:
%0
Ext Device Tag 1:
%1
Polled Variable 1:
%2 |
673 |
Ext Device Tag 2:
%0
Polled Variable 2:
%1 |
674 |
Priority: Maintenance - Fix Soon
Description:
The process temperature is outside Petroleum Measurement defined extrapolation limits.
Recommended Actions:
1. Verify process.
2. Verify configuration for Petroleum Measurement reference table and temperature. |
675 |
Priority: Maintenance - Fix Soon
Description:
The process density is outside Petroleum Measurement defined extrapolation limits.
Recommended Actions:
1. Verify process.
2. Verify configuration for Petroleum Measurement reference table and density. |
676 |
Priority: Advisory
Description:
The user has set the discrete output to a fixed state.
Recommended Actions:
1. No action required.
2. If desired, reconfigure the alarm severity to Ignore. |
677 |
Priority: Advisory
Description:
The configured density/temperature/concentration values do not result in a proper Concentration Measurement (CM) curve.
Recommended Actions:
1. Verify Concentration Measurement (CM) configuration. |
678 |
Priority: Maintenance - Fix Soon
Description:
The process temperature or density is outside the user-defined extrapolation limits.
Recommended Actions:
1. Verify the process temperature and density.
2. Verify Concentration Measurement (CM) configuration. |
679 |
Priority: Maintenance - Fix Soon
Description:
Meter verification in progress, with outputs set to last measured value.
Recommended Actions:
1. Allow the procedure to complete.
2. If desired, abort the procedure and restart with outputs set to fault. |
680 |
Priority: Maintenance - Fix Soon
Description:
Meter verification in progress.
Recommended Actions:
1. Allow the procedure to complete. You may abort the procedure if desired. |
681 |
Priority: Advisory
Description:
Simulation mode is enabled.
Recommended Actions:
1. Disable output simulation. |
682 |
Priority: Advisory
Description:
Discrete Event 1 has been triggered.
Recommended Actions:
1. No action required. |
683 |
Discrete Event Var:
%0
Discrete Event Type:
%1 |
684 |
Setpoint A:
Value %0
Setpoint B:
Value %1 |
685 |
Priority: Advisory
Description:
Discrete Event 2 has been triggered.
Recommended Actions:
1. No action required. |
686 |
Priority: Advisory
Description:
Discrete Event 3 has been triggered.
Recommended Actions:
1. No action required. |
687 |
Priority: Advisory
Description:
Discrete Event 4 has been triggered.
Recommended Actions:
1. No action required. |
688 |
Priority: Advisory
Description:
Discrete Event 5 has been triggered.
Recommended Actions:
1. No action required. |
689 |
Priority: Advisory
Description:
Discrete Input is active.
Recommended Actions:
1. No action required. |
690 |
Priority: Maintenance - Fix Soon
Description:
Primary variable has exceeded sensor limits.
Recommended Actions:
1. Verify process and check for slug flow.
2. Check the test points.
3. Check the sensor circuitry
4. Check the sensor tubes for erosion.
5. If the problem persists, contact Micro Motion. |
691 |
Priority: Maintenance - Fix Soon
Description:
Non-primary variable has exceeded sensor limits.
Recommended Actions:
1. Verify process and check for slug flow.
2. Check the test points.
3. Check the sensor circuitry
4. Check the sensor tubes for erosion.
5. If the problem persists, contact Micro Motion. |
692 |
Priority: Maintenance - Fix Soon
Description:
The calculated amount of current output is outside of the linear range.
Recommended Actions:
1. Verify that mA output range values are set to appropriate values. |
693 |
Priority: Maintenance - Fix Soon
Description:
Power has been removed and reapplied resulting in the reinstallations of the setup information.
Recommended Actions:
1. The first command to recognize this condition will automatically reset this flag.
2. This flag may also be set following a Master Reset or a Self Test. |
694 |
Priority: Maintenance - Fix Soon
Description:
A write or set command has been executed.
Recommended Actions:
1. No action required. |
695 |
Priority: Maintenance - Fix Soon
Description:
A hardware error or failure has been detected by the device.
Recommended Actions:
1. Check the test points.
2. Check the sensor circuitry.
3. If the problem persists, contact Micro Motion. |
696 |
Priority: Failed - Fix Now
Description:
An uncorrectable checksum mismatch has been detected.
Recommended Actions:
1. Cycle power to the flow meter.
2. The flow meter might need service. Contact Micro Motion. |
697 |
Priority: Failed - Fix Now
Description:
ROM checksum error or a RAM location cannot be written to.
Recommended Actions:
1. Cycle power to the flowmeter.
2. The flow meter might need service. Contact Micro Motion. |
698 |
Test Result #%{Datalog_Index}
Test Result Number: %0
Running Hours: %1
Test Result: %2
Abort Code %3
LPO Stiffness: %4
RPO Stiffness: %5 |
699 |
Priority: Failed - Fix Now
Description:
Transmitter electronics failure has occurred.
Recommended Actions:
1. Cycle power to the flowmeter.
2. Contact Micro Motion. |
700 |
Priority: Failed - Fix Now
Description:
The loaded software is not compatible with the programmed board type.
Recommended Actions:
1. Contact Micro Motion. |
701 |
To reset all matrix press Next or press Cancel. |
702 |
All matrix data has been set to 0. |
703 |
Concentration Measurement screen needs to be refreshed. |
704 |
To reset all matrix data, press OK. Otherwise, press Abort. |
705 |
The concentration matrix is locked, please unlock the matrix to configure. |
706 |
number |
707 |
Coil Value is %0 and Exception Code is %1 |
708 |
Unsigned 16 Value is %0 and Exception Code is %1 |
709 |
Unsigned 32 Value is %0 and Exception Code is %1 |
710 |
Floating Point Value is %0 and Exception Code is %1 |
711 |
Register is read-only. |
712 |
uValue |
713 |
æ£å¨å¤ä½ç»ææ¹åæ è®°ã请ç¨åã |
714 |
ç»ææ¹åæ è®°å·²å¤ä½ã |
715 |
Select the matrix being configured: |
716 |
Curve 1;Curve 2;Curve 3;Curve 4;Curve 5;Curve 6 |
717 |
Access Restricted |
718 |
Resetting device. Please wait. |
719 |
设å¤å¤ä½æåå®æã |
720 |
æ¨å°ä½¿ç¨åºåå¼è¦ç设å¤ç»æã å¨ç»§ç»ä¹åï¼å°æ§å¶å路设置为æå¨æä½ï¼å¹¶ç¡®ä¿ç°æçç»æå¼å·²è®°å½æä¿åå¨æ件ä¸ã å¦æ设å¤è¿æ¥ä¸¢å¤±ï¼è¯·ä½¿ç¨é»è®¤è®¾ç½®éæ°è¿æ¥ã è¦ç»§ç»åï¼ |
721 |
Aborting due to field device error |
722 |
Factory values are restored successfully. |