0 |
LMT Magnetostrictive Level Transmitter |
1 |
Level Sensor Failure |
2 |
液位传感器故障
可能原因:液位传感器故障
推荐操作:联系 ABB 服务部门进行更换。 |
3 |
Temperature Sensor Failure |
4 |
温度传感器故障
可能原因:温度传感器故障
推荐操作:联系 ABB 服务部门进行更换。 |
5 |
Illegal Memory Access |
6 |
非法访问内存
可能原因:非法访问内存。
推荐操作:重置设备并重新检查 |
7 |
Safety Function Flow Failure |
8 |
安全功能流量错误
可能原因:安全功能流量故障
推荐操作:重置设备并重新检查 |
9 |
Level Sensor Out of Limits |
10 |
液位传感器超限
可能原因:液位传感器超限。
推荐操作:验证信号质量和波形设置。 |
11 |
Temperature Sensor Out of Limits |
12 |
温度传感器超限
可能原因:温度传感器超限。
推荐操作:验证工艺温度。如果读数与实际工艺温度不匹配,请联系 ABB 服务部门。 |
13 |
Self Test Failure |
14 |
可能原因:自检失败。
推荐操作:重置设备并重新检查 |
15 |
Level Sensor Out of Range |
16 |
主值超出范围
可能原因:液位传感器超出范围。
推荐操作:检查工艺条件。液位高于 URV 或低于 LRV。如果读数与实际工艺不匹配,请联系 ABB 服务部门。 |
17 |
Sensor Board Memory Failure |
18 |
传感器非易失性内存故障
可能原因:传感器板内存故障。
推荐操作:重置设备并重新检查 |
19 |
Sensor Board Non-Volatile Write Error |
20 |
传感器板非易失性写入错误
可能原因:传感器板非易失性内存故障。
推荐操作:重置设备并重新检查 |
21 |
Device Reset Required |
22 |
需要重置设备
可能原因:设备配置不完整。
推荐操作:重置设备并重新检查 |
23 |
Communication Error |
24 |
传感器通信错误
可能原因:传感器通信故障。
推荐操作:重置设备并重新检查 |
25 |
Electronics Non-Volatile Failure |
26 |
电子设备非易失性内存故障
可能原因:电子设备板非易失性内存故障
推荐操作:重置设备并重新检查 |
27 |
Electronics Non-Volatile Syncing Information |
28 |
电子设备非易失性同步
可能原因:电子设备非易失性内存同步。
推荐操作:无需任何操作。 |
29 |
HMI Validation Test Failure |
30 |
HMI 验证测试失败
可能原因:HMI 验证测试失败。
推荐操作:更换 HMI。 |
31 |
Sensor Board Fault |
32 |
传感器板故障
可能原因:传感器板发生故障
推荐操作:重置设备并重新检查 |
33 |
Electronics Power Supply Insufficient Voltage to operate device |
34 |
电子设备输入电压不足
可能原因:使用了不适合设备正确运行的错误电压
推荐操作:检查 4-20 mA 回路中的电源和串联电阻。 |
35 |
Ambient Temp Out of Range |
36 |
环境温度超出范围
可能原因:环境条件超出了可接受的设备运行条件。
推荐操作:纠正错误的环境条件。 |
37 |
Process Temp Warning |
38 |
工艺温度警告
可能原因:工艺温度警告。
推荐操作:工艺温度超出警告限值。如果读数与实际工艺不匹配,请联系 ABB 服务部门。 |
39 |
Process Temp Alarm |
40 |
工艺温度警报
可能原因:工艺温度警报。
推荐操作:工艺温度超出警告限值。如果读数与实际工艺不匹配,请联系 ABB 服务部门。 |
41 |
Data Simulation Warning |
42 |
工艺数据处于模拟模式
可能原因:一个或多个测量值处于模拟模式。
推荐操作:确认测量值处于模拟模式。 |
43 |
Alarm Simulation Warning |
44 |
警报处于模拟模式
可能原因:一个或多个警报条件处于模拟模式。
推荐操作:测试完成后,退出模拟模式。 |
45 |
Current Output in Fixed Mode |
46 |
电流以固定模式输出
可能原因:电流输出设为固定模式
推荐操作:测试完成后,退出固定输出模式。 |
47 |
Primary Current Uncertain |
48 |
一次电流不确定
可能原因:当前输出电路发生故障。
推荐操作:重置设备并重新检查 |
49 |
Electronics ROM Failure |
50 |
电子设备 ROM 故障
可能原因:内存自检失败。
推荐操作:重置设备并重新检查 |
51 |
Electronics RAM Failure |
52 |
电子设备 RAM 故障
可能原因:内存自检失败。
推荐操作:重置设备并重新检查 |
53 |
Non-Volatile Replace Error |
54 |
非易失性内存更换错误
可能原因:更换非易失性内存时发生错误。
推荐操作:按照手册验证指拨开关设置,然后重新尝试更换操作。 |
55 |
Primary Current Saturated |
56 |
一次电流饱和
可能原因:电流处于饱和水平。
推荐操作:监控工艺条件。 |
57 |
Current Output Failure |
58 |
电流输出回读失败
可能原因:电流输出回读失败。
推荐操作:重置设备并重新检查 |
59 |
Process Media Warning |
60 |
工艺介质警告
可能原因:工艺介质警告。
推荐操作:工艺测量结果超出警告限值。如果读数与实际工艺不匹配,请联系 ABB 服务部门。 |
61 |
Process Media Alarm |
62 |
工艺介质警报
可能原因:工艺介质警报。
推荐操作:工艺测量结果超出警报限值。如果读数与实际工艺不匹配,请联系 ABB 服务部门。 |
63 |
Sensor Config Warning |
64 |
可能原因:传感器需要微调。
推荐操作:恢复出厂设置,如果问题仍然存在,请联系 ABB 服务部门。 |
65 |
CheckFunction |
66 |
Off Specification |
67 |
Maintenance |
68 |
**Failure** |
69 |
Electronics status |
70 |
Sensor status |
71 |
Configuration status |
72 |
Operating conditions |
73 |
Process operating conditions |
74 |
Diagnostics Simulation |
75 |
.3f |
76 |
QV |
77 |
Force Loop Current |
78 |
D/A Trim |
79 |
Self Test |
80 |
液位 |
81 |
容器中产品的高度。 |
82 |
液位单位 |
83 |
距离测量的工程单位。 |
84 |
液位数据质量 |
85 |
液位限值状态 |
86 |
液位状态 |
87 |
液位分类 |
88 |
液位设备系列 |
89 |
液位最小量程 |
90 |
阻尼 |
91 |
.2f |
92 |
模拟 |
93 |
液位值模拟状态。 |
94 |
OFF |
95 |
ON |
96 |
Level Update Period |
97 |
传感器序列号 |
98 |
7d |
99 |
Simulate |
100 |
Update Period |
101 |
LIN 0 数据质量 |
102 |
LIN 0 限值状态 |
103 |
LIN 0 液位状态 |
104 |
输出类型 |
105 |
线性化输出类型。 |
106 |
流量 |
107 |
体积 |
108 |
液位 |
109 |
LIN 0 传感器上限 |
110 |
LIN 0 传感器下限 |
111 |
LIN 0 最小量程 |
112 |
线性化液位最小量程 |
113 |
LIN 0 Update Period |
114 |
流量 |
115 |
线性化流量值 |
116 |
流量单位 |
117 |
流量分类 |
118 |
LIN 阻尼 |
119 |
8.2f |
120 |
线性化液位值模拟状态。 |
121 |
Linearized Level-Flow |
122 |
体积 |
123 |
线性化体积值 |
124 |
体积单位 |
125 |
体积分类 |
126 |
Linearized Level-Volume |
127 |
缺量 |
128 |
缺量值 |
129 |
Ullage Data Quality |
130 |
Ullage Limit Status |
131 |
Ullage Status |
132 |
缺量分类 |
133 |
缺量传感器上限 |
134 |
缺量传感器下限 |
135 |
缺量最小量程 |
136 |
缺量阻尼 |
137 |
缺量值模拟状态。 |
138 |
Ullage Update Period |
139 |
界面 |
140 |
界面是表面在构成两种不混溶液体之间的共同界线时所处的高度。 |
141 |
Interface Data Quality |
142 |
Interface Limit Status |
143 |
Interface Status |
144 |
Interface Classification |
145 |
Interface Device Family |
146 |
界面传感器上限 |
147 |
界面传感器下限 |
148 |
界面最小量程 |
149 |
界面阻尼 |
150 |
界面值模拟状态。 |
151 |
Interface Update Period |
152 |
LIN 1 值 |
153 |
线性化界面值 |
154 |
LIN 1 Data Quality |
155 |
LIN 1 Limit Status |
156 |
LIN 1 Status |
157 |
LIN 1 传感器上限 |
158 |
LIN 1 传感器下限 |
159 |
LIN 1 最小量程 |
160 |
线性化界面最小量程 |
161 |
模拟设备的线性化界面读数。 |
162 |
LIN 1 Update Period |
163 |
LIN 界面单位 |
164 |
线性化界面值模拟状态。 |
165 |
Linearized Interface-Volume |
166 |
温度 |
167 |
温度单位 |
168 |
传感器温度单位 — 用于显示传感器温度的工程单位。 |
169 |
Temperature Data Quality |
170 |
Temperature Limit Status |
171 |
Temperature Status |
172 |
温度分类 |
173 |
温度传感器上限 |
174 |
温度传感器下限 |
175 |
最小量程 |
176 |
阻尼值 — 应用于温度值的阻尼时间常数。此变量的单位始终为秒。 |
177 |
温度值模拟状态。 |
178 |
Temperature Update Period |
179 |
温度传感器序列号 |
180 |
Loop Warning Variables |
181 |
Loop Warning Variables- Variables that display a warning message before new values are sent. |
182 |
Write Variables |
183 |
List of variables that can be edited Offline and written to the device |
184 |
Read Variables |
185 |
List of variables that can be read from the device |
186 |
Select Display Type |
187 |
Select the type of display graph |
188 |
Analog |
189 |
BarGraph |
190 |
Polling Address |
191 |
Polling Address- Address used by the Host to identify a Field Device. |
192 |
Number of Response Preambles |
193 |
Device ID |
194 |
Field Device Revision |
195 |
Universal Revision |
196 |
Final Assembly Number |
197 |
AO Alarm Type |
198 |
Loop Current Mode |
199 |
Long Tag |
200 |
Write Protect |
201 |
PV Loop Current |
202 |
清除表 |
203 |
选择“清除表”将完全擦除线性化表中的所有值。 |
204 |
恢复表 |
205 |
选择“恢复表”将恢复已存储在设备备份文件中的线性化表值。 |
206 |
保存表 |
207 |
选择“保存表”将把线性化表中的所有值保存到设备 EPROM 中的备份文件。 |
208 |
Linearization Table |
209 |
Displays the Linearization Input points, Output points and points status. |
210 |
No. |
211 |
Input Value |
212 |
Output Value |
213 |
Point Status |
214 |
1 |
215 |
2 |
216 |
3 |
217 |
4 |
218 |
5 |
219 |
6 |
220 |
7 |
221 |
8 |
222 |
9 |
223 |
10 |
224 |
11 |
225 |
12 |
226 |
13 |
227 |
14 |
228 |
15 |
229 |
16 |
230 |
17 |
231 |
18 |
232 |
19 |
233 |
20 |
234 |
21 |
235 |
Set LIN Points |
236 |
若要配置线性化点模式 |
237 |
软件写入保护 |
238 |
指示变量是否可写入现场设备 |
239 |
安装方向 |
240 |
设备既可安装在顶部,也可安装在底部。 |
241 |
Bottom |
242 |
Top |
243 |
服务代码注销 |
244 |
偏移 |
245 |
偏移从探针底部处 RTD 读取的温度值。 |
246 |
运行总时间 |
247 |
以天数表示的自上次设备重置以来的运行总时间。 |
248 |
CPU 负载 |
249 |
CPU 负载百分比。 |
250 |
% |
251 |
警报延迟 |
252 |
只有当信号至少在警报延迟持续时间内一直丢失时,输出才会进入警报状态。 |
253 |
脉冲宽度 |
254 |
用于液位测量的能量 |
255 |
设备配置 |
256 |
选项包括 1 级或 2 级以及带温度或不带温度。 |
257 |
Single Level without Temperature |
258 |
Single Level with Temperature |
259 |
Dual Level without Temperature |
260 |
Dual Level with Temperature |
261 |
消隐距离 |
262 |
消隐是 LMT 被设置为忽略的一片测量区域,包括喷嘴距离。为了忽略来自探针顶部的反射,可能需要进一步扩大消隐至超过喷嘴。消隐根据单位进行设置。若要调整消隐 |
263 |
状态 |
264 |
允许远程访问的硬件开关。 |
265 |
软件版本 |
266 |
电子设备软件版本。 |
267 |
硬件版本 |
268 |
电子设备硬件版本。 |
269 |
传感器软件版本。 |
270 |
传感器硬件版本。 |
271 |
1.1.0 |
272 |
FPGA Revision |
273 |
Field Programmable Gate Array revision. |
274 |
Transducer ID |
275 |
sim points |
276 |
index sim |
277 |
警报 |
278 |
液位警报启用/禁用 |
279 |
禁用 |
280 |
使能 |
281 |
警报 |
282 |
缺量警报启用/禁用 |
283 |
禁用 |
284 |
使能 |
285 |
界面警报启用/禁用 |
286 |
使能 |
287 |
温度警报启用/禁用 |
288 |
Array Alarm Enable |
289 |
Index Alarm Enable |
290 |
单极 |
291 |
信号既可是标准信号,也可是反向信号。 |
292 |
标准 |
293 |
Reversed |
294 |
阈值 |
295 |
阈值电压提供了一种沿波形检测信号的方法。来自工艺反射的信号必须越过此屏障才能被检测为信号。LMT 旨在检测超过阈值的第一个脉冲。可能需要提高阈值来避开基线干扰,或降低阈值来检测正确脉冲。 |
296 |
警报源 |
297 |
警报选择源可以是软件 |
298 |
Software |
299 |
Hardware-Low |
300 |
Hardware-High |
301 |
低饱和 |
302 |
模拟输出电流饱和下限。 |
303 |
高饱和 |
304 |
模拟输出电流饱和上限。 |
305 |
低警报 |
306 |
模拟输出电流的警报下限。(NAMUR 标准 = 3.6 mA) |
307 |
高警报 |
308 |
模拟输出电流的警报上限。(NAMUR 标准 = 21.0 mA) |
309 |
失效模式 |
310 |
故障模式指示错误条件下设备回路电流所采取的措施。 |
311 |
高 |
312 |
低 |
313 |
访问级别 |
314 |
访问级别可以是“只读”、“标准”、“高级”或“服务”用户 |
315 |
Read Only |
316 |
Advanced |
317 |
Service |
318 |
HART 服务代码 |
319 |
|
320 |
密码错误;访问级别降级为“只读”。 |
321 |
LIN 输入点 1 |
322 |
线性化输入点 1 |
323 |
LIN 输入点 2 |
324 |
线性化输入点 2 |
325 |
LIN 输入点 3 |
326 |
线性化输入点 3 |
327 |
LIN 输入点 4 |
328 |
线性化输入点 4 |
329 |
LIN 输入点 5 |
330 |
线性化输入点 5 |
331 |
LIN 输入点 6 |
332 |
线性化输入点 6 |
333 |
LIN 输入点 7 |
334 |
线性化输入点 7 |
335 |
LIN 输入点 8 |
336 |
线性化输入点 8 |
337 |
LIN 输入点 9 |
338 |
线性化输入点 9 |
339 |
LIN 输入点 10 |
340 |
线性化输入点 10 |
341 |
LIN 输入点 11 |
342 |
线性化输入点 11 |
343 |
LIN 输入点 12 |
344 |
线性化输入点 12 |
345 |
LIN 输入点 13 |
346 |
线性化输入点 13 |
347 |
LIN 输入点 14 |
348 |
线性化输入点 14 |
349 |
LIN 输入点 15 |
350 |
线性化输入点 15 |
351 |
LIN 输入点 16 |
352 |
线性化输入点 16 |
353 |
LIN 输入点 17 |
354 |
线性化输入点 17 |
355 |
LIN 输入点 18 |
356 |
线性化输入点 18 |
357 |
LIN 输入点 19 |
358 |
线性化输入点 19 |
359 |
LIN 输入点 20 |
360 |
线性化输入点 20 |
361 |
LIN 输入点 21 |
362 |
线性化输入点 21 |
363 |
LIN 输出点 1 |
364 |
线性化输出点 1 |
365 |
LIN 输出点 2 |
366 |
线性化输出点 2 |
367 |
LIN 输出点 3 |
368 |
线性化输出点 3 |
369 |
LIN 输出点 4 |
370 |
线性化输出点 4 |
371 |
LIN 输出点 5 |
372 |
线性化输出点 5 |
373 |
LIN 输出点 6 |
374 |
线性化输出点 6 |
375 |
LIN 输出点 7 |
376 |
线性化输出点 7 |
377 |
LIN 输出点 8 |
378 |
线性化输出点 8 |
379 |
LIN 输出点 9 |
380 |
线性化输出点 9 |
381 |
LIN 输出点 10 |
382 |
线性化输出点 10 |
383 |
LIN 输出点 11 |
384 |
线性化输出点 11 |
385 |
LIN 输出点 12 |
386 |
线性化输出点 12 |
387 |
LIN 输出点 13 |
388 |
线性化输出点 13 |
389 |
LIN 输出点 14 |
390 |
线性化输出点 14 |
391 |
LIN 输出点 15 |
392 |
线性化输出点 15 |
393 |
LIN 输出点 16 |
394 |
线性化输出点 16 |
395 |
LIN 输出点 17 |
396 |
线性化输出点 17 |
397 |
LIN 输出点 18 |
398 |
线性化输出点 18 |
399 |
LIN 输出点 19 |
400 |
线性化输出点 19 |
401 |
LIN 输出点 20 |
402 |
线性化输出点 20 |
403 |
LIN 输出点 21 |
404 |
线性化输出点 21 |
405 |
LIN 点状态 1 |
406 |
线性化点状态 1 |
407 |
禁用 |
408 |
使能 |
409 |
LIN 点状态 2 |
410 |
线性化点状态 2 |
411 |
LIN 点状态 3 |
412 |
线性化点状态 3 |
413 |
LIN 点状态 4 |
414 |
线性化点状态 4 |
415 |
LIN 点状态 5 |
416 |
线性化点状态 5 |
417 |
LIN 点状态 6 |
418 |
线性化点状态 6 |
419 |
LIN 点状态 7 |
420 |
线性化点状态 7 |
421 |
LIN 点状态 8 |
422 |
线性化点状态 8 |
423 |
LIN 点状态 9 |
424 |
线性化点状态 9 |
425 |
LIN 点状态 10 |
426 |
线性化点状态 10 |
427 |
LIN 点状态 11 |
428 |
线性化点状态 11 |
429 |
LIN 点状态 12 |
430 |
线性化点状态 12 |
431 |
LIN 点状态 13 |
432 |
线性化点状态 13 |
433 |
LIN 点状态 14 |
434 |
线性化点状态 14 |
435 |
LIN 点状态 15 |
436 |
线性化点状态 15 |
437 |
LIN 点状态 16 |
438 |
线性化点状态 16 |
439 |
LIN 点状态 17 |
440 |
线性化点状态 17 |
441 |
LIN 点状态 18 |
442 |
线性化点状态 18 |
443 |
LIN 点状态 19 |
444 |
线性化点状态 19 |
445 |
LIN 点状态 20 |
446 |
线性化点状态 20 |
447 |
LIN 点状态 21 |
448 |
线性化点状态 21 |
449 |
array points |
450 |
index array points |
451 |
输入单位 |
452 |
线性化液位值的输入单位。 |
453 |
输入模式 |
454 |
要确定如何分配表中的值,可手动输入输入值,或提升罐体液位并自动输入值。
“手动模式”允许将输入值连同所需的各输出液位一起输入。
“自动模式”要求产品液位为设置各输出值时的测量液位。
注意:与自动模式相比,手动模式将产生更精确的线性化轮廓。 |
455 |
Automatic |
456 |
手动 |
457 |
LIN 输入模式 1 |
458 |
LIN 输入模式 2 |
459 |
LIN 输入模式 3 |
460 |
LIN 输入模式 4 |
461 |
LIN 输入模式 5 |
462 |
LIN 输入模式 6 |
463 |
LIN 输入模式 7 |
464 |
LIN 输入模式 8 |
465 |
LIN 输入模式 9 |
466 |
LIN 输入模式 10 |
467 |
LIN 输入模式 11 |
468 |
LIN 输入模式 12 |
469 |
LIN 输入模式 13 |
470 |
LIN 输入模式 14 |
471 |
LIN 输入模式 15 |
472 |
LIN 输入模式 16 |
473 |
LIN 输入模式 17 |
474 |
LIN 输入模式 18 |
475 |
LIN 输入模式 19 |
476 |
LIN 输入模式 20 |
477 |
LIN 输入模式 21 |
478 |
array write points |
479 |
index array write points |
480 |
Output value too large |
481 |
Output value too small |
482 |
Input value too large |
483 |
Input value too small |
484 |
LIN Table Clear |
485 |
LIN Table Reload |
486 |
LIN Table Backup |
487 |
输出最大值 |
488 |
此值分配给探针长度沿线的最高可测量点。 |
489 |
输出最小值 |
490 |
此值分配给探针长度沿线的最低可测量点。它通常会被设置为 0 |
491 |
输出单位 |
492 |
线性化输出单位允许为线性化表选择所需的输出单位。线性化输出单位可以为液位 |
493 |
Invalid Unit Type |
494 |
LIN 输出单位 |
495 |
线性化流量单位 |
496 |
线性化体积单位 |
497 |
线性化液位单位 |
498 |
Array Linearization Units |
499 |
Linearization_Units |
500 |
线性化状态 |
501 |
如果线性化状态为“活动” |
502 |
位置 |
503 |
波形位置 |
504 |
Sensor Reference Point |
505 |
界面 |
506 |
User Distance |
507 |
End of Probe |
508 |
距离 |
509 |
距离单位 |
510 |
设置波形 X 轴距离单位。 |
511 |
波形起点 |
512 |
波形起始位置 |
513 |
Increment |
514 |
Distance between each point of the waveform data. |
515 |
上限 |
516 |
液位测量的上限值。 |
517 |
下限 |
518 |
液位测量的下限值。 |
519 |
线性化流量测量的上限值。 |
520 |
线性化流量测量的下限值。 |
521 |
线性化体积测量的上限值。 |
522 |
线性化体积测量的下限值。 |
523 |
缺量测量的上限值。 |
524 |
缺量测量的下限值。 |
525 |
界面测量的上限值。 |
526 |
界面测量的下限值。 |
527 |
温度测量的上限值。 |
528 |
温度测量的下限值。 |
529 |
array range |
530 |
index array range |
531 |
Invalid span |
532 |
Span too small |
533 |
Horizontal Scale |
534 |
0.25 ft/div |
535 |
0.5 ft/div |
536 |
1 ft/div |
537 |
2 ft/div |
538 |
0.05 m/div |
539 |
0.1 m/div |
540 |
0.2 m/div |
541 |
0.4 m/div |
542 |
3 in/div |
543 |
6 in/div |
544 |
12 in/div |
545 |
24 in/div |
546 |
5 cm/div |
547 |
10 cm/div |
548 |
20 cm/div |
549 |
40 cm/div |
550 |
50 mm/div |
551 |
100 mm/div |
552 |
200 mm/div |
553 |
400 mm/div |
554 |
显示模式 |
555 |
设置此页面中的行数和每行的字符数。此外 |
556 |
Graph |
557 |
1 row x 6 char |
558 |
1 row x 6 char+Bar |
559 |
1 row x 9 char |
560 |
1 row x 9 char+Bar |
561 |
2 rows x 9 char |
562 |
2 rows x 9 char+Bar |
563 |
3 rows x 9 char |
564 |
关闭 |
565 |
第 1 行 |
566 |
设置第 1 行中显示的设备变量。 |
567 |
Raw Level |
568 |
缺量 |
569 |
Current Output % |
570 |
Current Output mA |
571 |
Linearized Level-Flow |
572 |
Linearized Level-Volume |
573 |
温度 |
574 |
Raw Interface |
575 |
Linearized Interface-Volume |
576 |
第 2 行 |
577 |
设置第 2 行(如有)中显示的设备变量。 |
578 |
第 3 行 |
579 |
设置第 3 行(如有)中显示的设备变量。 |
580 |
条形图 |
581 |
设置条形图(如有)中显示的设备变量。 |
582 |
Array Operator Pages |
583 |
Index Operator Pages |
584 |
本地操作 |
585 |
使用按钮启用本地操作。 |
586 |
语言 |
587 |
LMT 配备了数种不同操作语言,以便对设备进行设置。当选中某一语言时 |
588 |
英语 |
589 |
德语 |
590 |
法语 |
591 |
西班牙语 |
592 |
意大利语 |
593 |
Russian |
594 |
Chinese |
595 |
Portuguese |
596 |
对比度 |
597 |
调整设备 HMI 的对比度。 |
598 |
自动滚动 |
599 |
使操作者页面在 HMI 上能够自动滚动。 |
600 |
日期格式 |
601 |
DD-MM-YYYY |
602 |
MM-DD-YYYY |
603 |
YYYY-MM-DD |
604 |
显示器版本 |
605 |
显示器版本。 |
606 |
Diagnosis Condition Number |
607 |
Diagnosis Condition Details Class |
608 |
Diagnosis Condition Details Group |
609 |
Diagnosis Condition Details Priority |
610 |
Diagnosis Condition Details Alarm Counter |
611 |
Diagnosis Condition Details Alarm Time Counter Day |
612 |
Diagnosis Condition Details Alarm Time Counter Msec |
613 |
Diagnosis Condition Details Time Stamp Last Alarm Day |
614 |
Diagnosis Condition Details Time Stamp Last Alarm Msec |
615 |
Extended Diagnostics 0 |
616 |
Diagnosis Condition Details Code |
617 |
Data in Simulation Mode |
618 |
警报处于模拟模式 |
619 |
电子设备非易失性内存故障 |
620 |
Sensor Non-Volatile Memory Write Failure |
621 |
Electronics Non-Volatile Memory Write Failure |
622 |
Replace Sensor to Electronics Blocked |
623 |
Replace Required Sensor to Electronics Blocked |
624 |
Replace Required Both Directions Enabled |
625 |
安全功能流量错误 |
626 |
HMI 验证测试失败 |
627 |
Electronics Temperature Too Low |
628 |
Electronics Temperature Too High |
629 |
Invalid Input Value |
630 |
Fail-Safe Low |
631 |
Span Limit High |
632 |
Span Limit Low |
633 |
Hardware Limit Low |
634 |
Hardware Limit High |
635 |
System Limit Low |
636 |
System in Fixed Curent Mode |
637 |
Power Supply Too Low (<10.5 VDC) |
638 |
Power Supply Too High (>40.5 VDC) |
639 |
Current Readback Failed High |
640 |
Current Readback Failed Low |
641 |
电子设备 RAM 故障 |
642 |
电子设备 ROM 故障 |
643 |
Ambient Temperature Too High |
644 |
Ambient Temperature Too Low |
645 |
Illegal Memory Access Failure |
646 |
Memory Test Failure |
647 |
Electronics Self Test Failure |
648 |
液位传感器故障 |
649 |
Level Sensor Warning |
650 |
Level Out of Limits |
651 |
Interface Out of Limits |
652 |
Level Sensor Trim Needed |
653 |
温度传感器故障 |
654 |
温度传感器超限 |
655 |
Temperature Sensor Trim Needed |
656 |
Sensor Non-Volatile Write Active |
657 |
Sensor Non-Volatile Write Failure |
658 |
Sensor Non-Volatile Failure |
659 |
Sensor Non-Volatile Busy |
660 |
传感器通信错误 |
661 |
需要重置设备 |
662 |
PV Value Out of Range |
663 |
Level Low Low Alarm |
664 |
Level Low Warning |
665 |
Level High Warning |
666 |
Level High High Alarm |
667 |
Ullage Low Low Alarm |
668 |
Ullage Low Warning |
669 |
Ullage High Warning |
670 |
Ullage High High Alarm |
671 |
Interface Low Low Alarm |
672 |
Interface Low Warning |
673 |
Interface High Warning |
674 |
Interface High High Alarm |
675 |
Level in Simulation Mode |
676 |
Interface in Simulation Mode |
677 |
Ullage in Simulation Mode |
678 |
Temperature in Simulation Mode |
679 |
Volume-Level in Simulation Mode |
680 |
Volume-Interface in Simulation Mode |
681 |
Flow in Simulation Mode |
682 |
Temperature Low Low Alarm |
683 |
Temperature Low Warning |
684 |
Temperature High Warning |
685 |
Temperature High High Alarm |
686 |
Extended Diagnostics 1 |
687 |
Extended Diagnostics 2 |
688 |
Extended Diagnostics 3 |
689 |
Extended Diagnostics 4 |
690 |
Extended Diagnostics 5 |
691 |
Extended Diagnostics 6 |
692 |
Extended Diagnostics 7 |
693 |
Extended Diagnostics 8 |
694 |
Extended Diagnostics 9 |
695 |
Extended Diagnostics 10 |
696 |
Extended Diagnostics 11 |
697 |
Extended Diagnostics 12 |
698 |
Extended Diagnostics 13 |
699 |
Ext. Diagnostics 1 |
700 |
Ext. Diagnostics 2 |
701 |
Extended Diag. 1 |
702 |
Extended Diag. 2 |
703 |
Extended Diag. 3 |
704 |
Extended Diag. 4 |
705 |
Extended Diag. 5 |
706 |
Extended Diag. 6 |
707 |
Extended Diag. 7 |
708 |
Masking |
709 |
非法访问内存 |
710 |
液位传感器超限 |
711 |
自检失败 |
712 |
主值超出范围 |
713 |
传感器非易失性内存故障 |
714 |
传感器板非易失性写入错误 |
715 |
传感器通信错误 |
716 |
电子设备非易失性内存故障 |
717 |
电子设备非易失性同步 |
718 |
传感器板故障 |
719 |
电子设备输入电压不足 |
720 |
环境温度超出范围 |
721 |
工艺温度警告 |
722 |
工艺温度警报 |
723 |
工艺数据处于模拟模式 |
724 |
警报处于模拟模式 |
725 |
电流以固定模式输出 |
726 |
一次电流不确定 |
727 |
非易失性内存更换错误 |
728 |
一次电流饱和 |
729 |
Current Output Failure |
730 |
工艺介质警告 |
731 |
工艺介质警报 |
732 |
需要微调传感器 |
733 |
Diagnostics simulation status |
734 |
模拟 |
735 |
System in Fixed Current Mode |
736 |
液位传感器故障 |
737 |
Sensor Board Fault |
738 |
Temperature Sensor Trim Needed |
739 |
Sensor Non-Volatile Write Error |
740 |
Flow in simulation mode |
741 |
Process Temperature Low Low Alarm |
742 |
Process Temperature Low Warning |
743 |
Process Temperature High Warning |
744 |
Process Temperature High High Alarm |
745 |
温度传感器超限 |
746 |
低低 |
747 |
“温度低低警报”状态位设置在此温度值之下。 |
748 |
‘“温度低警报”状态位设置在此温度值之下。 |
749 |
“温度高警报”状态位设置在此温度值之上。 |
750 |
高高 |
751 |
“温度高高警报”状态位设置在此温度值之上。 |
752 |
Array T Alarm |
753 |
Index Array T Alarm |
754 |
电子设备温度 |
755 |
设备周围的环境温度。 |
756 |
工艺最低温度 |
757 |
工艺的最低记录温度。 |
758 |
工艺最高温度 |
759 |
工艺的最高记录温度。 |
760 |
设置标准密码 |
761 |
更改标准访问级别密码。 |
762 |
65535 |
763 |
设置高级密码 |
764 |
更改高级访问级别密码。 |
765 |
Array Write Password |
766 |
Index Write Passowrd |
767 |
传感器 ID |
768 |
设备传感器 ID |
769 |
Array Alarm Non Media Level Points |
770 |
index array alarm Non Media Level points |
771 |
array alarm limit low low |
772 |
index array alarm limit low low |
773 |
array alarm limit low |
774 |
index array alarm limit low |
775 |
array alarm limit high |
776 |
index array alarm limit high |
777 |
array alarm limit high high |
778 |
index array alarm limit high high |
779 |
Sensor Status Byte 0 |
780 |
Sensor defect |
781 |
Sensor Unknown |
782 |
Sensor Value Invalid |
783 |
Sensor Signal Lost |
784 |
Sensor Signal Interface |
785 |
Critical Siganl to Noise Ratio |
786 |
New Sensor Settings Necessary |
787 |
Sensor Status Byte 1 |
788 |
Additional Sensor defect |
789 |
Additional Sensor Value Invalid |
790 |
Level Status Byte 0 |
791 |
Level below Level Alarm Low Low |
792 |
Level below Low Alarm Low |
793 |
Level below Level Alarm High |
794 |
Level above Level Alarm High High |
795 |
Distance in Blocking Distance Low |
796 |
Distance in Blocking Distance High |
797 |
Level Status Byte 1 |
798 |
New Calibration necessary |
799 |
Incorrect Calibration |
800 |
New Level Settings Necessary |
801 |
Interface Status Byte 0 |
802 |
Interface below Level Alarm Low Low |
803 |
Interface below Low Alarm Low |
804 |
Interface below Level Alarm High |
805 |
Interface above Level Alarm High High |
806 |
Interface Status Byte 1 |
807 |
Array Status |
808 |
Index Array Status |
809 |
Family revision |
810 |
Additional Sensor Availability |
811 |
Additional Sensor Device Variable Availability |
812 |
Not Available |
813 |
Available |
814 |
Ullage Available |
815 |
Ullage Device Variable Available |
816 |
传感器技术代码 |
817 |
现场设备中传感器的类型。 |
818 |
Magnetostrictive |
819 |
Num of Calibration Points |
820 |
Maximum number of Calibration Points |
821 |
Sensor Compensation Availbility |
822 |
Blocking Distances Availbility |
823 |
No Blocking Distance |
824 |
Only Blocking Distance High |
825 |
Only Blocking Distance Low |
826 |
Both Blocking Distances |
827 |
未知 |
828 |
Special |
829 |
Array Level Family Capability |
830 |
Index Level Family Capability |
831 |
Device Variable Code Media Level |
832 |
Device Variable Code of the Media Level |
833 |
Device Variable Code Ullage Level |
834 |
Device Variable Code of the Ullage Level |
835 |
Device Variable Code Additional Sensor |
836 |
Device Variable Code of the Additional Sensor |
837 |
Additional Sensor Not Used |
838 |
Classification Additional Sensor |
839 |
Array Read Level Family Device Variable Values |
840 |
Index Read Level Family Device Variable Values |
841 |
Additional Sensor Unit |
842 |
Additional Sensor Value |
843 |
Sensor Unit Type |
844 |
Sensor Units Type |
845 |
Measured Level Value |
846 |
The level of the product in the vessel before Level Offset |
847 |
Measured Interface Value |
848 |
The interface of the product in the vessel before Interface Offset |
849 |
Sensor Value |
850 |
Raw Sensor Value |
851 |
Array Read Level Family Internal Variable Values |
852 |
Index Read Level Family Internal Variable Values |
853 |
传感器偏移(液位) |
854 |
可用于补偿探针下方的不可测量区域,或使 LMT 的测量与其他设备保持一致。 |
855 |
传感器偏移(界面) |
856 |
Sensor Compensation |
857 |
液位偏移 |
858 |
添加至测量电平以给出介质电平的值 |
859 |
界面偏移 |
860 |
添加至测量界面以给出介质界面的值 |
861 |
缺量参考点 |
862 |
缺量液位为 0 的液位。 |
863 |
“液位低低警报”状态位设置在此液位值之下。 |
864 |
“液位低警报”状态位设置在此液位值之下。 |
865 |
“液位高警报”状态位设置在此液位值之下。 |
866 |
高高 |
867 |
“液位高高警报”状态位设置在此液位值之下。 |
868 |
“缺量低低警报”状态位设置在此缺量值之下。 |
869 |
“缺量低警报”状态位设置在此缺量值之下。 |
870 |
“缺量高警报”状态位设置在此缺量值之上。 |
871 |
“缺量高高警报”状态位设置在此缺量值之上。 |
872 |
“界面低低警报”状态位设置在此界面值之下。 |
873 |
“界面低警报”状态位设置在此界面值之下。 |
874 |
“界面高警报”状态位设置在此界面值之上。 |
875 |
“界面高高警报”状态位设置在此界面值之上。 |
876 |
Array Alarm Points |
877 |
index array alarm points |
878 |
探针长度 |
879 |
设备电位最高参考点与传感器参考点之间的距离。 |
880 |
Blocking Distance Low |
881 |
Blocking Distance High |
882 |
Calibration Index |
883 |
Index A |
884 |
Index B |
885 |
Calibration Function Code |
886 |
Change |
887 |
传感器上限 |
888 |
校准时的传感器上限。它对应于液位上限(LMT 校准表中使用 2 个液位点)。 |
889 |
传感器下限 |
890 |
校准时的传感器下限。它对应于液位下限(LMT 校准表中使用 2 个液位点)。 |
891 |
液位上限 |
892 |
校准时的液位上限。它对应于传感器上限(LMT 校准表中使用 2 个液位点)。 |
893 |
液位下限 |
894 |
校准时的液位下限。它对应于传感器下限(LMT 校准表中使用 2 个液位点)。 |
895 |
校准时的传感器上限。它对应于界面上限(LMT 校准表中使用 2 个界面点)。 |
896 |
校准时的传感器下限。它对应于界面下限(LMT 校准表中使用 2 个界面点)。 |
897 |
界面上限 |
898 |
校准时的界面上限。它对应于传感器上限(LMT 校准表中使用 2 个界面点)。 |
899 |
界面下限 |
900 |
校准时的界面下限。它对应于传感器下限(LMT 校准表中使用 2 个界面点)。 |
901 |
警报限值选择 |
902 |
警报限值选择代码 |
903 |
Level Point too large |
904 |
Level Point too small |
905 |
Identical Sensor Point already specified |
906 |
Non-Monotonic Calibration |
907 |
Delete calibration point not supported |
908 |
Gain |
909 |
Service Account |
910 |
Disable |
911 |
Enable |
912 |
标准登录 |
913 |
登录至标准访问级别。 |
914 |
高级登录 |
915 |
登录至高级访问级别。 |
916 |
服务登录 |
917 |
登录至服务访问级别。 |
918 |
注销访问级别 |
919 |
返回至最低访问级别。 |
920 |
更改标准密码 |
921 |
更改标准访问级别密码 |
922 |
更改高级密码 |
923 |
更改高级访问级别密码 |
924 |
重置 D/A 微调 |
925 |
重置设备 D/A 微调点为出厂设置。 |
926 |
重置密码为默认值 |
927 |
重置标准和高级密码为出厂默认值。 |
928 |
设置液位下限 |
929 |
通过将液位下限值写入设备并使用设备测量和存储相关传感器值来执行校准。 |
930 |
设置液位上限 |
931 |
通过将液位上限值写入设备并使用设备测量和存储相关传感器值来执行校准。 |
932 |
设置界面下限 |
933 |
通过将界面下限值写入设备并使用设备测量和存储相关传感器值来执行校准。 |
934 |
设置界面上限 |
935 |
通过将界面上限值写入设备并使用设备测量和存储相关传感器值来执行校准。 |
936 |
清除诊断历史记录 |
937 |
清除设备中的诊断历史记录。 |
938 |
清除工艺温度历史记录 |
939 |
重置记录的最高和最低工艺温度。 |
940 |
模拟设备的液位读数。 |
941 |
模拟设备的线性化液位读数。 |
942 |
模拟设备的缺量读数。 |
943 |
模拟设备的界面读数。 |
944 |
模拟设备的温度读数。 |
945 |
Clear Diagnostics Simulated |
946 |
Clear all diagnostics simulated. |
947 |
Reset Level Trim |
948 |
Reset the device level trim points to factory settings. |
949 |
Reset Interface Trim |
950 |
Reset the device interface trim points to factory settings. |
951 |
Reset Temperature Trim |
952 |
Reset the device temperature trim points to factory settings. |
953 |
DeviceHealthVariable |
954 |
Click for Updated Diagnostics |
955 |
Change Display Mode |
956 |
command 3 |
957 |
Change Device Configuration |
958 |
Change Linearization State |
959 |
Change Output Type |
960 |
Process Variables |
961 |
Device Settings |
962 |
Diagnostics |
963 |
设备 |
964 |
Additional device revisions |
965 |
Electronics Revision |
966 |
Sensor Revision |
967 |
Device Data |
968 |
Additional Info |
969 |
LMT Device Image |
970 |
Device image |
971 |
Easy Setup |
972 |
Waveform |
973 |
Device Setup |
974 |
Basic Setup |
975 |
General |
976 |
PV Setup |
977 |
Device Characteristics |
978 |
Input/Output |
979 |
HRT Mapping |
980 |
Analog Output |
981 |
温度传感器 |
982 |
Current Output Limits |
983 |
Current Saturation Limits |
984 |
Alarm Limits |
985 |
Current Output Alarm |
986 |
Communication |
987 |
Linearization |
988 |
Setup |
989 |
Configure Table |
990 |
Device Variables |
991 |
Display |
992 |
Display Settings |
993 |
Operator Page 1 |
994 |
Operator Page 2 |
995 |
Operator Page 3 |
996 |
Operator Page 4 |
997 |
校准 |
998 |
PV Range Values |
999 |
Current Output |
1000 |
Simulation |
1001 |
Output Current |
1002 |
Diagnostics Monitoring |
1003 |
Displays the current device diagnostics. |
1004 |
Device Status |
1005 |
Device Status : OK |
1006 |
Failure |
1007 |
Function Check |
1008 |
Out of Specification |
1009 |
Maintenance Required |
1010 |
OK |
1011 |
Electronics |
1012 |
Operating Conditions |
1013 |
Diagnostics History |
1014 |
Displays the history of device diagnostics. |
1015 |
Sensor |
1016 |
Configuration |
1017 |
Diagnostics Masking |
1018 |
To mask the device diagnostics. |
1019 |
To simulate the device diagnostics. |
1020 |
Level out of limits |
1021 |
Interface out of limits |
1022 |
Interface in simulation mode |
1023 |
Temperature in simulation mode |
1024 |
Volume-Level in simulation mode |
1025 |
Volume-Interface in simulation mode |
1026 |
Temperature sensor trim needed |
1027 |
Temperature sensor out of limits |
1028 |
Temperature low warning |
1029 |
Temperature high warning |
1030 |
Temperature low low alarm |
1031 |
Temperature high high alarm |
1032 |
Interface low warning |
1033 |
Interface high warning |
1034 |
Interface low low alarm |
1035 |
Interface high high alarm |
1036 |
Process Temperature History |
1037 |
Process Alarms |
1038 |
在传感器参考点处 |
1039 |
在液位 |
1040 |
在界面 |
1041 |
在探针末端处 |
1042 |
在用户距离处 |
1043 |
Device Self Test |
1044 |
Sensor Info |
1045 |
Sensor Setup |
1046 |
Sensor Limits |
1047 |
Access |
1048 |
Access Level Status |
1049 |
登录访问级别 |
1050 |
Read Only Switch |
1051 |
Clear Temperature History |
1052 |
Factory Trimming |
1053 |
Change Password |
1054 |
Calibrated Points |
1055 |
Dry Calibration |
1056 |
用于执行干态校准,此时传感器点和液位点均由用户提交。 |
1057 |
湿态校准 |
1058 |
通过将液位值写入设备并使用设备测量和存储相关传感器值来执行校准。 |
1059 |
用于执行干态校准,此时传感器点和界面点均由用户提交。 |
1060 |
通过将界面值写入设备并使用设备测量和存储相关传感器值来执行校准。 |
1061 |
www.abb.com |
1062 |
Image of Transmitter |
1063 |
Gauge |
1064 |
轻松设置 |
1065 |
Offline |
1066 |
Detailed Setup |
1067 |
General |
1068 |
Linearization |
1069 |
Configuration |
1070 |
设置线性化点 |
1071 |
校准 |
1072 |
Login |
1073 |
Sensor Trim Factory Reset |
1074 |
Diagnostics |
1075 |
Overview |
1076 |
Possible Cause:
An error occurred in the sensor module. Possible cause could be a failed component in the sensor electronics or an error changing the configuration.
Suggested Action:
Restart the device. If the condition persists contact service for a replacement. |
1077 |
Error Code: F198.000 |
1078 |
Possible Cause:
An error occurred in the sensor module. Possible cause could be a failed component in the sensor electronics or an error changing the configuration. |
1079 |
Suggested Action:
Restart the device. If the condition persists contact service for a replacement. |
1080 |
Possible Cause:
A temperature measurement has resulted in a value outside of the operating range.
Suggested Action:
Restart the device. If the condition persists contact service for a replacement. |
1081 |
Error Code: S098.001 |
1082 |
Possible Cause:
A temperature measurement has resulted in a value outside of the operating range. |
1083 |
Possible Cause:
Illegal memory access.
Suggested Action:
Restart device and recheck, contact ABB if problem persists. |
1084 |
Error Code: F245.002 |
1085 |
Possible Cause:
Illegal memory access. |
1086 |
Suggested Action:
Restart device and recheck, contact ABB if problem persists. |
1087 |
Possible Cause:
Calculation of safety function did not occur in the proper sequence.
Suggested Action:
Restart the device. If the condition persists contact service for a replacement. |
1088 |
Error Code: F244.003 |
1089 |
Possible Cause:
Calculation of safety function did not occur in the proper sequence. |
1090 |
Possible Cause:
Result of the Level measurement is outside of the valid and expected range.
Suggested Action:
Using the HART configurator (DTM - Handheld) or the local HMI, navigate to the Diagnostics -> Waveform display and confirm the quality of the signal. The signal peak should visibly cross the threshold line and should measure approximately 2 Volts. Contact ABB service for additional support or a replacement if the condition persists. |
1091 |
Error Code: F215.004 |
1092 |
Possible Cause:
Result of the Level measurement is outside of the valid and expected range. |
1093 |
Suggested Action:
Using the HART configurator (DTM - Handheld) or the local HMI, navigate to the Diagnostics -> Waveform display and confirm the quality of the signal. The signal peak should visibly cross the threshold line and should measure approximately 2 Volts. Contact ABB service for additional support or a replacement if the condition persists. |
1094 |
Possible Cause:
Suggested Action:
Restart the device. If the condition persists contact service for a replacement. |
1095 |
Error Code: F248.006 |
1096 |
Possible Cause:
|
1097 |
Possible Cause:
Writing to the sensor non-volatile memory was not successful.
Suggested Action:
The sensor should be replaced as soon as possible. |
1098 |
Error Code: F212.017 |
1099 |
Possible Cause:
Writing to the sensor non-volatile memory was not successful. |
1100 |
Suggested Action:
The sensor should be replaced as soon as possible. |
1101 |
Possible Cause:
An error occurred in communication between the sensor and electronics modules.
Suggested Action:
Restart the device. If the condition persists contact service for a replacement. |
1102 |
Error Code: F196.020 |
1103 |
Possible Cause:
An error occurred in communication between the sensor and electronics modules. |
1104 |
Possible Cause:
Electronics memory is corrupted.
Suggested Action:
The electronics must be replaced. |
1105 |
Error Code: F218.023 |
1106 |
Possible Cause:
Electronics memory is corrupted. |
1107 |
Suggested Action:
The electronics must be replaced. |
1108 |
Possible Cause:
An error occurred in the sensor module. Possible causes could be a failed component in the sensor electronics, a configuration error, or the sensor assembly.
Suggested Action:
Using a HART configuration (DTM - Hand held) or the local HMI, navigate to the Diagnostics -> Waveform display and confirm the quality of the signal. The signal peak should visibly cross the threshold line and should measure approximately 2 volts. Contact ABB service for additional support or a replacement if the condition persists. |
1109 |
Error Code: F194.031 |
1110 |
Possible Cause:
An error occurred in the sensor module. Possible causes could be a failed component in the sensor electronics, a configuration error, or the sensor assembly. |
1111 |
Suggested Action:
Using a HART configuration (DTM - Hand held) or the local HMI, navigate to the Diagnostics -> Waveform display and confirm the quality of the signal. The signal peak should visibly cross the threshold line and should measure approximately 2 volts. Contact ABB service for additional support or a replacement if the condition persists. |
1112 |
Possible Cause:
The D to A convert is not properly calibrated or trimmed.
Suggested Action:
A DAC(digital to output converter) trimming should be performed and if the error persists the communication board must be replaced.
Possible Cause:
The device is not properly configured.
Suggested Action:
Check the device configuration. |
1113 |
Error Code: F228.039 |
1114 |
Possible Cause:
The D to A convert is not properly calibrated or trimmed. |
1115 |
Suggested Action:
A DAC(digital to output converter) trimming should be performed and if the error persists the communication board must be replaced. |
1116 |
Possible Cause:
The device is not properly configured. |
1117 |
Suggested Action:
Check the device configuration. |
1118 |
Possible Cause:
Program memory test failed.
Suggested Action:
Restart the device. If condition persists contact service for a replacement. |
1119 |
Error Code: F247.040 |
1120 |
Possible Cause:
Program memory test failed. |
1121 |
Suggested Action:
Restart the device. If condition persists contact service for a replacement. |
1122 |
Possible Causes:
1)Electronics memory test failed.
2)Process data memory check failed (dynamic duplicated error).
Suggested Action:
Restart the device. If condition persists contact service for a replacement. |
1123 |
Error Code: F246.041 |
1124 |
Possible Causes:
1)Electronics memory test failed.
2)Process data memory check failed (dynamic duplicated error). |
1125 |
Possible Cause:
The electronics or the sensor have been changed but the replacement operation has not been executed.
Suggested Actions:
1)The replacement operation must be executed. Set the SW1 of the electronics to the position 1 to enable the replace mode. Set SW2 accordingly depending on which component (Electronics or Sensor) has been replaced. Power cycle the device. Move the SW1 of the electronics to position 0.
2)The replacement operation must be executed. Only the data of the electronics can be copied to the sensor. Set the SW1 of the electronics to position 1 to enable the replace mode. Set SW2 to New Sensor position 1. Power cycle of the device. Move the SW1 of the electronics to position 0.
Possible Cause:
The Electronics of the Sensor have been changed. The replacement has been enabled but with the wrong direction (SW2 = 0).
Suggested Action:
Change the replacement direction (if possible). The SW1 is already set to Enable replace mode. Set SW2 to New Sensor (1). Power cycle the device. Move the SW1 of the electronics to position 0. |
1126 |
Error Code: F210.042 |
1127 |
Possible Cause:
The electronics or the sensor have been changed but the replacement operation has not been executed. |
1128 |
Suggested Actions:
1)The replacement operation must be executed. Set the SW1 of the electronics to the position 1 to enable the replace mode. Set SW2 accordingly depending on which component (Electronics or Sensor) has been replaced. Power cycle the device. Move the SW1 of the electronics to position 0.
2)The replacement operation must be executed. Only the data of the electronics can be copied to the sensor. Set the SW1 of the electronics to position 1 to enable the replace mode. Set SW2 to New Sensor position 1. Power cycle of the device. Move the SW1 of the electronics to position 0. |
1129 |
Possible Cause:
The Electronics of the Sensor have been changed. The replacement has been enabled but with the wrong direction (SW2 = 0). |
1130 |
Suggested Action:
Change the replacement direction (if possible). The SW1 is already set to Enable replace mode. Set SW2 to New Sensor (1). Power cycle the device. Move the SW1 of the electronics to position 0. |
1131 |
Possible Cause:
The output circuit could be broken or not correctly calibrated.
Suggested Action:
A DAC(digital to output converter) trimming should be performed and if the error persists the communication board must be replaced. |
1132 |
Error Code: F226.044 |
1133 |
Possible Cause:
The output circuit could be broken or not correctly calibrated. |
1134 |
Suggested Action:
A DAC (digital to output converter) trimming should be performed and if the error persists the communication board must be replaced. |
1135 |
Possible Cause:
An attempt to save data to the sensor module is failed.
Suggested Action:
Restart the device. If the condition persists contact service. |
1136 |
Error Code: C211.018 |
1137 |
Possible Cause:
An attempt to save data to the sensor module is failed. |
1138 |
Suggested Action:
Restart the device. If the condition persists contact service. |
1139 |
Possible Cause:
Device change require restart.
Suggested Action:
Restart device. |
1140 |
Error Code: C200.019 |
1141 |
Possible Cause:
Device change require restart. |
1142 |
Suggested Action:
Restart device. |
1143 |
Possible Cause:
The Level Value produced in output is derived by the value simulated in input.
Suggested Action:
Using a HART configurator(DTM - Hand held) place device back in normal operating mode (Remove input simulation). |
1144 |
Error Code: C138.036 |
1145 |
Possible Cause:
The Level Value produced in output is derived by the value simulated in input. |
1146 |
Suggested Action:
Using a HART configurator(DTM - Hand held) place device back in normal operating mode (Remove input simulation). |
1147 |
Possible Cause:
An alarm condition is being simulated by the device.
Suggested Action:
Using a HART configurator(DTM - Hand held) place device back in normal operating mode (Remove input simulation). |
1148 |
Error Code: C139.037 |
1149 |
Possible Cause:
An alarm condition is being simulated by the device. |
1150 |
Possible Cause:
Output current is in fixed mode. This could be due to the device being used in multidrop mode or a simulation.
Suggested Action:
Using a HART configuration (DTM - Haand held) place device back in normal operating mode (Remove inputs simulation). |
1151 |
Error Code: C220.038 |
1152 |
Possible Cause:
Output current is in fixed mode. This could be due to the device being used in multidrop mode or a simulation. |
1153 |
Suggested Action:
Using a HART configuration (DTM - Haand held) place device back in normal operating mode (Remove inputs simulation). |
1154 |
Possible Causes:
1)The Level sensor trim is set to a default value.
2)The Temperature trimming configured is corrupted.
Suggested Action:
Contact service to perform a factory level sensor trim. |
1155 |
Error Code: C154.047 |
1156 |
Possible Causes:
1)The Level sensor trim is set to a default value.
2)The Temperature trimming configured is corrupted. |
1157 |
Suggested Action:
Contact service to perform a factory level sensor trim. |
1158 |
Possible Cause:
Result of temperature measurement above or below process range.
Suggested Action:
Restart the device. If condition persists contact service for a replacement.
The Compatibility of level transmitter model and process condition has to be checked. Probably a different transmitter type is required. |
1159 |
Error Code: S096.005 |
1160 |
Possible Cause:
Result of temperature measurement above or below process range. |
1161 |
Suggested Action:
Restart the device. If condition persists contact service for a replacement.
The Compatibility of level transmitter model and process condition has to be checked. Probably a different transmitter type is required. |
1162 |
Possible Cause:
Primary sensor reading above or below range values.
Suggested Action:
Check process conditions and/or device configuration. The compatibility of level transmitter model and process condition has to be checked. Probably a different transmitter type is required. |
1163 |
Error Code: S148.010 |
1164 |
Possible Cause:
Primary sensor reading above or below range values. |
1165 |
Suggested Action:
Check process conditions and/or device configuration. The compatibility of level transmitter model and process condition has to be checked. Probably a different transmitter type is required. |
1166 |
Possible Cause:
Power supply too high or too low.
Suggested Action:
Check power supply voltage at the device terminal is at least 12 Vdc. |
1167 |
Error Code: S238.032 |
1168 |
Possible Cause:
Power supply too high or too low. |
1169 |
Suggested Action:
Check power supply voltage at the device terminal is at least 12 Vdc. |
1170 |
Possible Causes:
1)Ambient temperature too high or too low.
2)Temperature compenstaion saturated high or low.
Suggested Action:
Check ambient temperature. |
1171 |
Error Code: S222.033 |
1172 |
Possible Causes:
1)Ambient temperature too high or too low.
2)Temperature compenstaion saturated high or low. |
1173 |
Suggested Action: Check ambient temperature. |
1174 |
Possible Cause:
Process temperature above or below warning limits.
Suggested Action:
Check process condition. The compatibility of level transmitter model and process condition has to be checked. Probably a different transmitter type is required. |
1175 |
Error Code: S044.034 |
1176 |
Possible Cause:
Process temperature above or below warning limits. |
1177 |
Suggested Action:
Check process condition. The compatibility of level transmitter model and process condition has to be checked. Probably a different transmitter type is required. |
1178 |
Error Code: S046.035 |
1179 |
Possible Cause:
Current saturated high or low.
Suggested Action:
Check process condition and/or device configuration. The compatibility of the level transmitter model and process condition has to be checked. Probably a different transmitter type is required. |
1180 |
Error Code: S244.043 |
1181 |
Possible Cause:
Current saturated high or low. |
1182 |
Suggested Action:
Check process condition and/or device configuration. The compatibility of the level transmitter model and process condition has to be checked. Probably a different transmitter type is required. |
1183 |
Possible Cause:
Process value above high limit or below low limit.
Suggested Action:
Check process condition and/or device configuration. The compatibility of level transmitter model and process condition has to be checked. Probably a different transmitter type is required. |
1184 |
Error Code: S140.045 |
1185 |
Possible Cause:
Process value above high limit or below low limit. |
1186 |
Suggested Action:
Check process condition and/or device configuration. The compatibility of level transmitter model and process condition has to be checked. Probably a different transmitter type is required. |
1187 |
Possible Cause:
Process value above high high limit or below low low limit.
Suggested Action:
Check process condition and/or device configuration. The compatibility of level transmitter model and process condition has to be checked. Probably a different transmitter type is required. |
1188 |
Error Code: S146.046 |
1189 |
Possible Cause:
Process value above high high limit or below low low limit. |
1190 |
Possible Cause:
HMI failed validation test.
Suggested Action:
Replace HMI. |
1191 |
Error Code: M130.030 |
1192 |
Possible Cause:
HMI failed validation test. |
1193 |
Suggested Action:
Replace HMI. |
1194 |
Possible Causes:
1)Write Non-Volatile command received from CB.
2)Non-volatile Storage in progress.
Suggested Action:
. |
1195 |
Error Code: _156.025 |
1196 |
Possible Causes:
1)Write Non-Volatile command received from CB.
2)Non-volatile Storage in progress. |
1197 |
Suggested Action:
|
1198 |
Note : To change access level, navigate to access menu in detailed setup |
1199 |
Process variable |
1200 |
Diagnostics status |
1201 |
**Maintenance required** |
1202 |
**OK** |
1203 |
NAMUR NE107 |
1204 |
One or more device variables (i.e. measurement or control values) are invalid due to a malfunction in the field device or ist peripherals |
1205 |
One or more device variables are temporarily invalid (e.g. frozen) due to ongoing work on the device |
1206 |
There are deviations from the permissible ambient or process conditions detected that may compromise measurement or control accuracy (i.e. device performance may be degraded) |
1207 |
The field device requires maintenance |
1208 |
No Active Alarm exists |
1209 |
好的 |
1210 |
Process Value[mA] |
1211 |
Loop Current(mA) |
1212 |
Detailed Setup |
1213 |
**Function Check** |
1214 |
**Out of Specification** |
1215 |
**要求维护** |
1216 |
过程变量 |
1217 |
Percent range(%) |
1218 |
Percent range |
1219 |
FEHWExtract |
1220 |
feHW_MajVer |
1221 |
feHW_MinVer |
1222 |
TH Level Scaled |
1223 |
Blanking Scaled |
1224 |
零点 |
1225 |
零点线 |
1226 |
显示传感器参考点处的波形数据。
图例
波形 — 蓝色
消隐距离 — 紫色
阈值 — 绿色
零点 — 红色 |
1227 |
显示液位处的波形数据。
图例
波形 — 蓝色
消隐距离 — 紫色
阈值 — 绿色
零点 — 红色 |
1228 |
显示界面处的波形数据。
图例
波形 — 蓝色
消隐距离 — 紫色
阈值 — 绿色
零点 — 红色 |
1229 |
显示用户距离处的波形数据。
图例
波形 — 蓝色
消隐距离 — 紫色
阈值 — 绿色
零点 — 红色 |
1230 |
显示探针末端处的波形数据。
图例
波形 — 蓝色
消隐距离 — 紫色
阈值 — 绿色
零点 — 红色 |
1231 |
PV Analog Channel Saturated |
1232 |
PV Analog Channel Fixed |
1233 |
Wireless |
1234 |
WirelessHART Device |
1235 |
IEEE 802.15.4 2.4GHz DSSS with O-QPSK Modulation |
1236 |
Primary |
1237 |
Primary Analog Channel |
1238 |
Secondary |
1239 |
Secondary Analog Channel |
1240 |
Tertiary |
1241 |
Tertiary Analog Channel |
1242 |
Quaternary |
1243 |
Quaternary Analog Channel |
1244 |
Quinary |
1245 |
Quinary Analog Channel |
1246 |
Critical Power Failure |
1247 |
Lock all |
1248 |
Trim not supported |
1249 |
Configuration cannot be changed |
1250 |
Locked by gateway |
1251 |
Analog Input Channel |
1252 |
Analog Output Channel |
1253 |
Secondary Analog Channel Saturated |
1254 |
Tertiary Analog Channel Saturated |
1255 |
Quaternary Analog Channel Saturated |
1256 |
Quinary Analog Channel Saturated |
1257 |
Secondary Analog Channel Fixed |
1258 |
Tertiary Analog Channel Fixed |
1259 |
Quaternary Analog Channel Fixed |
1260 |
Quinary Analog Channel Fixed |
1261 |
Simulation active |
1262 |
The device is in simulation mode and the level output is not representative of the process. |
1263 |
Non-Volatile memory failure |
1264 |
The Non-Volatile memory check is invalid or maybe corrupt, or the battery of a battery-backed memory has failed. |
1265 |
Volatile memory error |
1266 |
The RAM memory check is invalid or maybe corrupt |
1267 |
Watchdog reset executed |
1268 |
A watchdog reset has been performed |
1269 |
Voltage conditions out of range |
1270 |
A voltage condition is outside its allowable range |
1271 |
Environmental conditions out of range |
1272 |
An internal or environmental condition is beyond acceptable limits. |
1273 |
Electronic failure |
1274 |
A hardware problem not related to the sensor has been detected. |
1275 |
Subdevice list changed |
1276 |
Duplicate master detected |
1277 |
Capacity Denied |
1278 |
The device was unable to acquire the communication bandwidth required to support the Burst Messaging specified |
1279 |
Bandwidth allocation pending |
1280 |
Block transfer pending |
1281 |
Battery life |
1282 |
Percent range |
1283 |
Loop current |
1284 |
Primary variable |
1285 |
Secondary variable |
1286 |
Tertiary variable |
1287 |
Quaternary variable |
1288 |
Read receive time |
1289 |
Write date and time |
1290 |
Non-Volatile Clock |
1291 |
When set the device contains a battery-backed clock. In this case, the clock does not need to be reset if there is a power failure. |
1292 |
Clock Uninitialized |
1293 |
The real-time clock has never been set with the date and time. For example, the clock is volatile and power was removed from and restored to the device. |
1294 |
None |
1295 |
No restrictions |
1296 |
SI Only |
1297 |
Restricted to SI Unit codes only |
1298 |
Process automation device |
1299 |
Discrete device |
1300 |
Hybrid:Process automation+discrete |
1301 |
I/O System |
1302 |
WirelessHART Process automation device |
1303 |
WirelessHART Discrete device |
1304 |
WirelessHART Process automation+discrete |
1305 |
WirelessHART Gateway |
1306 |
WirelessHART Access point |
1307 |
WirelessHART Process adapter |
1308 |
WirelessHART Discrete adapter |
1309 |
WirelessHART enabled handheld/portable maintenance tool |
1310 |
Device Profile |
1311 |
US |
1312 |
United States of America |
1313 |
JP |
1314 |
Japan |
1315 |
DE |
1316 |
Germany |
1317 |
FR |
1318 |
France |
1319 |
ES |
1320 |
Spain |
1321 |
RU |
1322 |
Russian Federation |
1323 |
CN |
1324 |
People's Republic of China |
1325 |
Secondary Master |
1326 |
Primary Master |
1327 |
Device Diagnostic Status 0 |
1328 |
Device Diagnostic Status 1 |
1329 |
I/O and Subdevice Status |
1330 |
WirelessHART Status |
1331 |
Time Set Option |
1332 |
Real Time Clock Flags |
1333 |
Country |
1334 |
Country of intended device installation |
1335 |
SI Unit Control |
1336 |
Indicates if device should only display SI unit codes |
1337 |
Time Stamp |
1338 |
Relative time value on network |
1339 |
8u |
1340 |
Dynamic Variables Returned for Device Variables |
1341 |
Command Response Truncated |
1342 |
Configuration Change Counter Mismatch |
1343 |
Status bytes mismatch |
1344 |
8.3f |
1345 |
Device Variable |
1346 |
Variable to trim |
1347 |
Are you sure you want to clear the linearization table to factory defaults? |
1348 |
Clearing linearization table in progress... |
1349 |
Clearing linearization table completed. |
1350 |
Are you sure you want to restore the linearization table from backup? |
1351 |
Linearization table reload in progress... |
1352 |
Linearization table reload completed. |
1353 |
Are you sure you want to save the linearization table to backup? |
1354 |
Linearization table backup completed. |
1355 |
Please select the point to configure |
1356 |
Point 1;Point 2;Point 3;Point 4;Point 5;Point 6;Point 7;Point 8;Point 9;Point 10;Point 11;Point 12;Point 13;Point 14;Point 15;Point 16;Point 17;Point 18;Point 19;Point 20;Point 21;Exit |
1357 |
Linearization Input Point 1 Mode |
1358 |
Level Value is: %{0} %{1}.
Press OK when stable. |
1359 |
Level Value is: %{Level_Obj_value_0} %{Level_Obj_unit}
Enter Linearization Output Point 1: |
1360 |
Linearization Point 1 status |
1361 |
Linearization Point 1 Saved. |
1362 |
Enter Linearization Input Point 1 |
1363 |
Enter Linearization Output Point 1 |
1364 |
Linearization Input Point 2 Mode |
1365 |
Level Value is: %{Level_Obj_value_0} %{Level_Obj_unit}
Enter Linearization Output Point 2: |
1366 |
Linearization Point 2 status |
1367 |
Linearization Point 2 Saved. |
1368 |
Enter Linearization Input Point 2 |
1369 |
Enter Linearization Output Point 2 |
1370 |
Linearization Input Point 3 Mode |
1371 |
Level Value is: %{Level_Obj_value_0} %{Level_Obj_unit}
Enter Linearization Output Point 3: |
1372 |
Linearization Point 3 status |
1373 |
Linearization Point 3 Saved. |
1374 |
Enter Linearization Input Point 3 |
1375 |
Enter Linearization Output Point 3 |
1376 |
Linearization Input Point 4 Mode |
1377 |
Level Value is: %{Level_Obj_value_0} %{Level_Obj_unit}
Enter Linearization Output Point 4: |
1378 |
Linearization Point 4 status |
1379 |
Linearization Point 4 Saved. |
1380 |
Enter Linearization Input Point 4 |
1381 |
Enter Linearization Output Point 4 |
1382 |
Linearization Input Point 5 Mode |
1383 |
Level Value is: %{Level_Obj_value_0} %{Level_Obj_unit}
Enter Linearization Output Point 5: |
1384 |
Linearization Point 5 status |
1385 |
Linearization Point 5 Saved. |
1386 |
Enter Linearization Input Point 5 |
1387 |
Enter Linearization Output Point 5 |
1388 |
Linearization Input Point 6 Mode |
1389 |
Level Value is: %{Level_Obj_value_0} %{Level_Obj_unit}
Enter Linearization Output Point 6: |
1390 |
Linearization Point 6 status |
1391 |
Linearization Point 6 Saved. |
1392 |
Enter Linearization Input Point 6 |
1393 |
Enter Linearization Output Point 6 |
1394 |
Linearization Input Point 7 Mode |
1395 |
Level Value is: %{Level_Obj_value_0} %{Level_Obj_unit}
Enter Linearization Output Point 7: |
1396 |
Linearization Point 7 status |
1397 |
Linearization Point 7 Saved. |
1398 |
Enter Linearization Input Point 7 |
1399 |
Enter Linearization Output Point 7 |
1400 |
Linearization Input Point 8 Mode |
1401 |
Level Value is: %{Level_Obj_value_0} %{Level_Obj_unit}
Enter Linearization Output Point 8: |
1402 |
Linearization Point 8 status |
1403 |
Linearization Point 8 Saved. |
1404 |
Enter Linearization Input Point 8 |
1405 |
Enter Linearization Output Point 8 |
1406 |
Linearization Input Point 9 Mode |
1407 |
Level Value is: %{Level_Obj_value_0} %{Level_Obj_unit}
Enter Linearization Output Point 9: |
1408 |
Linearization Point 9 status |
1409 |
Linearization Point 9 Saved. |
1410 |
Enter Linearization Input Point 9 |
1411 |
Enter Linearization Output Point 9 |
1412 |
Linearization Input Point 10 Mode |
1413 |
Level Value is: %{Level_Obj_value_0} %{Level_Obj_unit}
Enter Linearization Output Point 10: |
1414 |
Linearization Point 10 status |
1415 |
Linearization Point 10 Saved. |
1416 |
Enter Linearization Input Point 10 |
1417 |
Enter Linearization Output Point 10 |
1418 |
Linearization Input Point 11 Mode |
1419 |
Level Value is: %{Level_Obj_value_0} %{Level_Obj_unit}
Enter Linearization Output Point 11: |
1420 |
Linearization Point 11 status |
1421 |
Linearization Point 11 Saved. |
1422 |
Enter Linearization Input Point 11 |
1423 |
Enter Linearization Output Point 11 |
1424 |
Linearization Input Point 12 Mode |
1425 |
Level Value is: %{Level_Obj_value_0} %{Level_Obj_unit}
Enter Linearization Output Point 12: |
1426 |
Linearization Point 12 status |
1427 |
Linearization Point 12 Saved. |
1428 |
Enter Linearization Input Point 12 |
1429 |
Enter Linearization Output Point 12 |
1430 |
Linearization Input Point 13 Mode |
1431 |
Level Value is: %{Level_Obj_value_0} %{Level_Obj_unit}
Enter Linearization Output Point 13: |
1432 |
Linearization Point 13 status |
1433 |
Linearization Point 13 Saved. |
1434 |
Enter Linearization Input Point 13 |
1435 |
Enter Linearization Output Point 13 |
1436 |
Linearization Input Point 14 Mode |
1437 |
Level Value is: %{Level_Obj_value_0} %{Level_Obj_unit}
Enter Linearization Output Point 14: |
1438 |
Linearization Point 14 status |
1439 |
Linearization Point 14 Saved. |
1440 |
Enter Linearization Input Point 14 |
1441 |
Enter Linearization Output Point 14 |
1442 |
Linearization Input Point 15 Mode |
1443 |
Level Value is: %{Level_Obj_value_0} %{Level_Obj_unit}
Enter Linearization Output Point 15: |
1444 |
Linearization Point 15 status |
1445 |
Linearization Point 15 Saved. |
1446 |
Enter Linearization Input Point 15 |
1447 |
Enter Linearization Output Point 15 |
1448 |
Linearization Input Point 16 Mode |
1449 |
Level Value is: %{Level_Obj_value_0} %{Level_Obj_unit}
Enter Linearization Output Point 16: |
1450 |
Linearization Point 16 status |
1451 |
Linearization Point 16 Saved. |
1452 |
Enter Linearization Input Point 16 |
1453 |
Linearization Input Point 17 Mode |
1454 |
Level Value is: %{Level_Obj_value_0} %{Level_Obj_unit}
Enter Linearization Output Point 17: |
1455 |
Linearization Point 17 status |
1456 |
Linearization Point 17 Saved. |
1457 |
Enter Linearization Input Point 17 |
1458 |
Enter Linearization Output Point 17 |
1459 |
Linearization Input Point 18 Mode |
1460 |
Level Value is: %{Level_Obj_value_0} %{Level_Obj_unit}
Enter Linearization Output Point 18: |
1461 |
Linearization Point 18 status |
1462 |
Linearization Point 18 Saved. |
1463 |
Enter Linearization Input Point 18 |
1464 |
Enter Linearization Output Point 18 |
1465 |
Linearization Input Point 19 Mode |
1466 |
Level Value is: %{Level_Obj_value_0} %{Level_Obj_unit}
Enter Linearization Output Point 19: |
1467 |
Linearization Point 19 status |
1468 |
Linearization Point 19 Saved. |
1469 |
Enter Linearization Input Point 19 |
1470 |
Enter Linearization Output Point 19 |
1471 |
Linearization Input Point 20 Mode |
1472 |
Level Value is: %{Level_Obj_value_0} %{Level_Obj_unit}
Enter Linearization Output Point 20: |
1473 |
Linearization Point 20 status |
1474 |
Linearization Point 20 Saved. |
1475 |
Enter Linearization Input Point 20 |
1476 |
Enter Linearization Output Point 20 |
1477 |
Linearization Input Point 21 Mode |
1478 |
Level Value is: %{Level_Obj_value_0} %{Level_Obj_unit}
Enter Linearization Output Point 21: |
1479 |
Linearization Point 21 status |
1480 |
Linearization Point 21 Saved. |
1481 |
Enter Linearization Input Point 21 |
1482 |
Enter Linearization Output Point 21 |
1483 |
Please enter the standard password to login |
1484 |
Enter standard password |
1485 |
mHServiceCode |
1486 |
Login successful |
1487 |
Please enter the advanced password to login |
1488 |
Enter advanced password |
1489 |
Please enter the service password to login |
1490 |
Enter service password |
1491 |
Are you sure you want to logout? |
1492 |
Logout successful |
1493 |
Are you sure you want to change standard password? |
1494 |
更改标准密码 |
1495 |
mHSetPassword_StandardLevel_L |
1496 |
Standard password changed |
1497 |
Are you sure you want to change advanced password? |
1498 |
更改高级密码 |
1499 |
mHSetPassword_AdvancedLevel_L |
1500 |
Advanced password changed |
1501 |
Are you sure you want to reset the device D/A trim points to factory settings? |
1502 |
Resetting to factory D/A trim values done. |
1503 |
Are you sure you want to reset the passwords to defaults? |
1504 |
Resetting the passwords to factory defaults successful. |
1505 |
Set Liquid Level (float) to desired Level Point (Lower).
Level Value is: %{Level_Obj_value_0} %{Level_Obj_unit}.
Press OK when stable. |
1506 |
Level Value is: %{Level_Obj_value_0} %{Level_Obj_unit}. Enter Lower Level Point |
1507 |
Wet calibration - Writing Lower Level point completed. |
1508 |
Set Liquid Level (float) to desired Level Point (Upper).
Level Value is: %{Level_Obj_value_0} %{Level_Obj_unit}.
Press OK when stable. |
1509 |
Level Value is: %{Level_Obj_value_0} %{Level_Obj_unit}. Enter Upper Level Point |
1510 |
Wet calibration - Writing Upper Level point completed. |
1511 |
Set Liquid Interface (float) to desired Interface Point (Lower).
Interface Value is: %{Interface_Obj_value_0} %{Level_Obj_unit}.
Press OK when stable. |
1512 |
Interface Value is: %{Interface_Obj_value_0} %{Level_Obj_unit}. Enter Lower Interface Point |
1513 |
Wet calibration - Writing Lower Interface point completed. |
1514 |
Set Liquid Interface (float) to desired Interface Point (Upper).
Interface Value is: %{Interface_Obj_value_0} %{Level_Obj_unit}.
Press OK when stable. |
1515 |
Interface Value is: %{Interface_Obj_value_0} %{Level_Obj_unit}. Enter Upper Interface Point |
1516 |
Wet calibration - Writing Upper Interface point completed. |
1517 |
Are you sure you want to clear diagnositcs history? |
1518 |
Clearing diagnostics history completed. |
1519 |
Are you sure you want to clear process minimum and maximum temperature history? |
1520 |
Clearing process minimum and maximum temperature history completed. |
1521 |
Please select to ON/OFF simulation |
1522 |
Level value simulation disabled. |
1523 |
Please enter the value to simulate |
1524 |
Level value simulated. |
1525 |
Linearized Level value simulation disabled. |
1526 |
Linearized Level value simulated. |
1527 |
Linearized Level value simulation disabled. |
1528 |
Ullage value simulation disabled. |
1529 |
Ullage value simulated. |
1530 |
Interface value simulation disabled. |
1531 |
Interface value simulated. |
1532 |
Linearized Interface value simulation disabled. |
1533 |
Linearized Interface value simulated. |
1534 |
Are you sure you want to simulate Temperature value? |
1535 |
Temperature value simulation disabled. |
1536 |
Temperature value simulated. |
1537 |
Are you sure you want to reset the device level trim points to factory settings? |
1538 |
Resetting to factory level trim values done. |
1539 |
Are you sure you want to reset the device interface trim points to factory settings? |
1540 |
Resetting to factory interface trim values done. |
1541 |
Are you sure you want to reset the device temperature trim points to factory settings? |
1542 |
Resetting to factory temperature trim values done. |
1543 |
01.00.00 |
1544 |
01.01.00 |
1545 |
01.02.00 |
1546 |
02.00.00 |
1547 |
Select the display mode: |
1548 |
Display mode changed successfully |
1549 |
Select Device Configuration |
1550 |
Device Configuration changed successfully |
1551 |
Select Linearization State: |
1552 |
Linearization state changed successfully |
1553 |
Select Output Type: |
1554 |
Changing output type in progress.. |
1555 |
Please enable the linearization |
1556 |
Please wait,loading the waveform... |