0 |
ABB |
1 |
Device Type |
2 |
FEX100 |
3 |
HART Manf. ID |
4 |
Write Protection |
5 |
Date |
6 |
Descriptor |
7 |
Final Assembly No |
8 |
Manufacturer |
9 |
Message |
10 |
Device Address |
11 |
Communication Tag |
12 |
Device Revision |
13 |
HART Revision |
14 |
Current |
15 |
2.3f |
16 |
Q% |
17 |
Qmax |
18 |
6.4f |
19 |
aAditional_Diag_Information_command |
20 |
adouble_Integer_command |
21 |
aDynamic_Float_Ranges_command |
22 |
aFloat_command |
23 |
aFloat_with_unit_command |
24 |
aInteger_command |
25 |
aStrings_command |
26 |
aUnsigned_Char_command |
27 |
Trend |
28 |
Q% |
29 |
% |
30 |
Iout |
31 |
mA |
32 |
Velocity |
33 |
Q |
34 |
DO1 Pulses |
35 |
Hz |
36 |
DO2 Pulses |
37 |
Trend 1 |
38 |
Diagnostics Measurement Trend Graph |
39 |
Trend 2 |
40 |
Elec. R E1 |
41 |
kOhm |
42 |
Elec. R E2 |
43 |
DC Back Off V |
44 |
V |
45 |
Coil & Cable R |
46 |
Ohm |
47 |
Coil L |
48 |
mH |
49 |
Sensor L Shift |
50 |
TX Av. Gain Shift |
51 |
Hot Key |
52 |
Process Variables Root Menu |
53 |
View Menu |
54 |
Trend Menu |
55 |
Q |
56 |
Totalizer |
57 |
Digital Output |
58 |
Current Output |
59 |
Device Root Menu |
60 |
Identify |
61 |
Identify Menu |
62 |
Device |
63 |
Additional Device Info |
64 |
Measuring Point |
65 |
Contact And Ordering Details |
66 |
Easy Setup |
67 |
Easy Setup Menu |
68 |
System |
69 |
Digital Output |
70 |
Flow |
71 |
Mains Frequency |
72 |
Device Info. |
73 |
Sensor Menu |
74 |
Transmitter Menu |
75 |
Parameters |
76 |
TAG And ID |
77 |
Calibration |
78 |
Properties |
79 |
Details |
80 |
TX Version |
81 |
Calibration |
82 |
Device Setup |
83 |
Transmitter Menu (1) |
84 |
Transmitter Menu (2) |
85 |
Calibration Factors Menu |
86 |
Calibration Factors |
87 |
Operating Mode |
88 |
Units |
89 |
Probe |
90 |
Flow And Qmax |
91 |
Low Flow Cutoff |
92 |
User Span |
93 |
User Zero |
94 |
Display |
95 |
Display Menu |
96 |
Operator Page 1 |
97 |
Operator Page 2 |
98 |
Operator Page 3 |
99 |
Input Output |
100 |
Output Readings Menu |
101 |
Output Readings |
102 |
Output Setup Menu |
103 |
Output Setup |
104 |
Logic Setup Menu |
105 |
DO1 Logic |
106 |
DO1 Config |
107 |
DO2 Logic |
108 |
DO2 Config |
109 |
DO3 Logic |
110 |
DO3 Config |
111 |
Pulse Setup Menu |
112 |
Pulse Setup |
113 |
Current Output Menu |
114 |
Volume FWD |
115 |
Volume REV |
116 |
Volume NET |
117 |
All Volume |
118 |
Diagnostics |
119 |
Measurements Menu(1) |
120 |
Measurements Menu(2) |
121 |
Measurements Menu(3) |
122 |
View |
123 |
Limits Menu |
124 |
Limits |
125 |
Simulation Menu |
126 |
Mode |
127 |
Velocity |
128 |
Q |
129 |
Q% |
130 |
Pulse 1/2 |
131 |
Logic 1 |
132 |
Logic 2 |
133 |
Logic 3 |
134 |
Iout |
135 |
Download Variables |
136 |
Upload Variables |
137 |
Diagnostic Menu |
138 |
Alarms Summary Menu |
139 |
Alarms Summary |
140 |
Alarm Simulation |
141 |
History Summary Menu |
142 |
History Summary |
143 |
Configuration Menu |
144 |
Group Masking |
145 |
Flowrate Limits |
146 |
Individual Masking |
147 |
History |
148 |
Iout Simulated |
149 |
Alarm Counters |
150 |
Logic OP1 Simulated |
151 |
Pulse OP1 Simulated |
152 |
Logic OP2 Simulated |
153 |
Pulse OP2 Simulated |
154 |
Logic OP3 Simulated |
155 |
Min Flow Value |
156 |
Max Flow Value |
157 |
103% Reached |
158 |
Simulated Flow |
159 |
Calibrator |
160 |
Display Overrange |
161 |
Totalizer Reset |
162 |
Poor Sensor Comms |
163 |
Address Not Zero |
164 |
TX Memory Fail |
165 |
No Sensor |
166 |
Measurement Offline |
167 |
Empty Pipe |
168 |
Elec. Open Circuit |
169 |
Elec. Short Circuit |
170 |
Installation Fault |
171 |
Coil Open Circuit |
172 |
Coil Short Circuit |
173 |
Loop Resistance |
174 |
TX Hardware |
175 |
Bad Flow Data |
176 |
Electrode Voltage |
177 |
OIML Self Check |
178 |
Measurement Starting |
179 |
Iout Hardware Fault |
180 |
Not Calibrated |
181 |
Calibration Mismatch |
182 |
ROM Error |
183 |
RAM Error |
184 |
HART Simulation |
185 |
Alarm simulation active |
186 |
NV Summary Alarm |
187 |
Offline |
188 |
Clear Alarm History |
189 |
Reset |
190 |
Reset |
191 |
Reset |
192 |
|
193 |
High Alarm Value |
194 |
min: 21.0
max: 23.0 |
195 |
2.2f |
196 |
Low Alarm Value |
197 |
min: 3.5
max: 3.6 |
198 |
Function Check |
199 |
Off |
200 |
On |
201 |
Maintenance Required |
202 |
Max. Alarm |
203 |
Min. Alarm |
204 |
Out Of Specification |
205 |
Overrange 103% |
206 |
Iout For Alarm |
207 |
High Alarm |
208 |
Low Alarm |
209 |
Alarm Simulation |
210 |
None |
211 |
Totalizer Reset |
212 |
Application CRC |
213 |
Bootloader |
214 |
Cal. Status |
215 |
Incomplete |
216 |
Calibrated |
217 |
Coil I Alarm Band |
218 |
min: 0.1
max: 10.0 |
219 |
2.1f |
220 |
Drive Mode |
221 |
User |
222 |
1 |
223 |
2 |
224 |
3 |
225 |
4 |
226 |
5 |
227 |
6 |
228 |
7 |
229 |
8 |
230 |
3A |
231 |
4A |
232 |
5A |
233 |
5B |
234 |
6A |
235 |
6B |
236 |
7A |
237 |
7B |
238 |
7C |
239 |
7D |
240 |
8A |
241 |
8B |
242 |
8C |
243 |
3.1f |
244 |
Coil L |
245 |
3.2f |
246 |
Coil O/C R Limit |
247 |
min: 2.0
max: 550.0 |
248 |
4.0f |
249 |
Coil S/C R Limit |
250 |
Ohms |
251 |
Contrast |
252 |
min: 0
max: 100 |
253 |
Iout For EP Alarm |
254 |
Q = 0% |
255 |
Flowrate Format |
256 |
x |
257 |
x.x |
258 |
x.xx |
259 |
x.xxx |
260 |
x.xxxx |
261 |
x.xxxxx |
262 |
Volume Format |
263 |
Date / Time Format |
264 |
DD-MM-YYYY |
265 |
MM-DD-YYYY |
266 |
YYYY-MM-DD |
267 |
Alarm |
268 |
Display Mode |
269 |
1 x 6 |
270 |
1 x 6 + Bargraph |
271 |
1 x 9 |
272 |
1 x 9 + Bargraph |
273 |
2 x 9 |
274 |
2 x 9 + Bargraph |
275 |
3 x 9 |
276 |
DO1/DO2 Function |
277 |
Pulse F/Pulse R |
278 |
Pulse F/Logic |
279 |
Pulse FR/Logic |
280 |
Logic/Logic |
281 |
kOhms |
282 |
6.3f |
283 |
Elec. V +Limit |
284 |
1.2f |
285 |
Elec. V -Limit |
286 |
Elec. V Diff. Limit |
287 |
Elec. R Alarm Max EP |
288 |
min: 0.0
max: 1000.0 |
289 |
5.0f |
290 |
Elec. R Alarm Min |
291 |
4.2f |
292 |
mm/s |
293 |
Factory Cutoff |
294 |
Fact. Cutoff No. Av. |
295 |
Span Ss |
296 |
Zero Sz |
297 |
Flow Indication |
298 |
Normal |
299 |
Reversed |
300 |
max |
301 |
min |
302 |
Q (Flowrate) Unit |
303 |
ft3/min |
304 |
ugal/min |
305 |
l/min |
306 |
igal/min |
307 |
m3/h |
308 |
ugal/s |
309 |
Mugal/d |
310 |
l/s |
311 |
Ml/d |
312 |
ft3/s |
313 |
ft3/d |
314 |
m3/s |
315 |
m3/d |
316 |
igal/h |
317 |
igal/d |
318 |
ft3/h |
319 |
m3/min |
320 |
ugal/h |
321 |
igal/s |
322 |
l/h |
323 |
ugal/d |
324 |
bls/h |
325 |
hl/h |
326 |
Unknown |
327 |
ft/s |
328 |
m/s |
329 |
in/s |
330 |
in/min |
331 |
ft/min |
332 |
7.4f |
333 |
Velocity Unit |
334 |
Fullscale Frequency |
335 |
min: 0.25
max: 10000000.0 |
336 |
8.5f |
337 |
Classification |
338 |
Byte 0 |
339 |
Description:
Current output is set to a fixed value.
Possible Cause:
The 4 to 20 mA output is being simulated using a chosen value. This enables the current at the connection terminals to be checked with test equipment.
The HART Instrument Address is not 0 so HART Multidrop mode is active (current out fixed to 4mA).
Suggested Action:
Stop simulating 4 to 20 mA output.
Set HART address to 0. |
340 |
Description:
OP1 output state is being simulated.
Possible Cause:
Simulation mode is enabled and the OP1 logic output state is being driven with a user-selected value.
Suggested Action:
Stop simulation of OP1 logic output. |
341 |
Description:
OP1 output frequency is being simulated.
Possible Cause:
Simulation mode is enabled and the OP1 frequency output is being driven with a user-defined value.
This enables the output frequency to be checked with a counter.
Suggested Action:
Stop simulation of OP1 frequency output. |
342 |
Description:
OP2 output state is being simulated.
Possible Cause:
Simulation mode is enabled and the OP2 logic output state is being driven with a user-selected value.
Suggested Action:
Stop simulation of OP2 logic output. |
343 |
Description:
OP2 output frequency is being simulated.
Possible Cause:
Simulation mode is enabled and the OP2 frequency output is being driven with a user-defined value.
This enables the output frequency to be checked with a counter.
Suggested Action:
Stop simulation of OP2 frequency output. |
344 |
Description:
OP3 output state is being simulated.
Possible Cause:
Simulation mode is enabled and the OP3 logic output state is being driven with a user-selected value.
Suggested Action:
Stop simulation of OP3 logic output. |
345 |
Description:
Flow rate is below the 'Minimum Alarm' limit.
Possible Cause:
Low flow rate.
'Minimum Alarm' limit not configured correctly.
Suggested Action:
Increase flow rate.
Decrease the value of the 'Minimum Alarm' limit. |
346 |
Description:
Flow rate is above the 'Maximum Alarm' limit.
Possible Cause:
High flow rate.
'Maximum Alarm' limit not configured correctly.
Suggested Action:
Reduce flow rate.
Increase the value of the 'Maximum Alarm' limit. |
347 |
Byte 1 |
348 |
Description:
Flow rate is above 103 % of 'Qmax' limit.
4 to 20 mA output is saturated.
Volume totalizer still operates.
Possible Cause:
High flow rate.
'Qmax' setting too low.
Suggested Action:
Reduce flow rate.
Increase the value of 'Qmax'. |
349 |
Description:
Flow rate or flow velocity value is being simulated.
Possible Cause:
Simulation Mode is enabled and either flow rate or flow velocity is being simulated using a chosen value.
The outputs correspond to the simulated value set.
Suggested Action:
Stop simulation of flow rate or flow velocity. |
350 |
Description:
The transmitter is using a calibrator or simulator.
Possible Cause:
The calibrator or simulator sensor electronics has been configured for calibrator or simulator use.
Suggested Action:
Remove transmitter from calibrator or simulator. |
351 |
Description:
With a flow rate equal to Qmax, the 'Volume' display overruns in less than 1,600 hours.
Possible Cause:
Inappropriate 'Display Format' or 'Volume Units' choice for this meter size.
Suggested Action:
Adjust the 'Volume Display Format' setting to use less digits after the decimal point.
Select different 'Volume Units' for this meter size. |
352 |
Description:
The totalizer has been reset to zero.
Possible Cause:
The user requested a totalizer reset.
Suggested Action:
None. |
353 |
Description:
Intermittent data communications detected between the transmitter and the remote sensor electronics.
Possible Cause:
This error occurs only on remote sensor systems that have electronics housed in the remote sensor assembly.
Sensor cable defective.
Open or short-circuit.
Poor connections.
Defective sensor electronics.
Suggested Action:
Check sensor cable and its connections.
Contact local representative. |
354 |
Description:
The HART Instrument Address is not 0.
Possible Cause:
Address 1 to 15 selected.
Therefore the current output is frozen at 4mA (HART Multidrop).
Suggested Action:
Select Address 0 if a 4 to 20mA output is required. |
355 |
Description:
Communications fault detected with the on-board transmitter memory.
Possible Cause:
Memory circuit in the transmitter cartridge is defective.
Suggested Action:
Replace cartridge.
Contact local representative. |
356 |
Byte 2 |
357 |
Description:
No sensor memory detected.
Possible Cause:
No sensor connected.
Meter in 'Off-Line' mode.
Suggested Action:
Check sensor cable and its connections.
Connect a sensor.
If using an Integral meter check the backplane dip switch configuration.
Contact local representative. |
358 |
Description:
Problem with transmitter measurement system detected.
Possible Cause:
Unexpected electrical conditions detected.
Suggested Action:
Replace cartridge.
Check sensor cross-bonding, or high levels of mains pickup occurring.
Contact local representative. |
359 |
Description:
Empty pipe conditions have been detected.
Possible Cause:
The pipe is empty and the electrodes are not in contact with fluid.
If the pipe is full, the 'Electrode R Alarm Max. EP Limit' may not be configured correctly.
Suggested Action:
Ensure meter pipe is full.
Check the 'Electrode R Alarm Max.EP Limit'.
Contact local representative. |
360 |
Unused |
361 |
Description:
An open-circuit electrode has been detected.
Possible Cause:
Broken electrode wire or cable fault.
Bad connection.
Electrode 'Elec R Alarm Max EP' set too low.
Suggested Action:
Investigate/repair electrode circuit.
Check the 'Electrode R Alarm Max. EP'.
Contact local representative. |
362 |
Description:
A short-circuit electrode has been detected.
Possible Cause:
Electrode fault.
Bad connection.
'Elec R Alarm Min' set too low.
Suggested Action:
Investigate/repair electrode circuit.
Check the 'Electrode R Alarm Min.'.
Check electrode signal cables to ensure there is not a short circuit between the screen and inner cores, on terminals E1, S1, E2, S2.
Contact local representative. |
363 |
Byte 3 |
364 |
Description:
A problem with the installation's electrode potentials has been detected.
Possible Cause:
High differential electrode voltage.
Differential electrode voltage limits configuration.
Suggested Action:
Investigate/correct electrode voltage problem.
Ensure sensor is cross-bonded to pipeline.
Contact local representative. |
365 |
Description:
An open-circuit coil has been detected.
Possible Cause:
Sensor wiring or cable fault.
'Coil Open Circuit Resistance Limit' configuration.
Suggested Action:
Investigate/correct coil circuit problem.
Check the 'Coil Open Circuit Resistance Limit' configuration.
Contact local representative. |
366 |
Description:
A short-circuit coil has been detected.
Possible Cause:
Sensor wiring or cable fault.
Suggested Action:
Investigate/correct coil circuit problem.
Contact local representative. |
367 |
Description:
An out-of-range loop resistance has been detected.
Possible Cause:
Sensor wiring or cable altered or faulty.
Suggested Action:
Investigate/correct loop circuit problem.
Contact local representative. |
368 |
Description:
A problem with the transmitter electronics has been detected.
Possible Cause:
Defective transmitter cartridge electronics.
Suggested Action:
Replace cartridge.
Contact local representative. |
369 |
Description:
Problem with data obtained by the transmitter measurement system.
Possible Cause:
Out of bounds data values detected by the measurement system.
Sensor wiring or cable fault.
Suggested Action:
Investigate/repair sensor wiring and connections.
Check sensor cross-bonding or high levels of mains pickup occurring.
Contact local representative. |
370 |
Description:
Accuracy potentially affected by high electrode voltages.
Possible Cause:
High absolute electrode voltages.
Absolute electrode voltage limits configuration.
Suggested Action:
Investigate/correct electrode voltage problem.
Check sensor cross bonding is in accordance with the manual.
Consider installing an additional ABB stainless steel fluid contact ring.
Contact local representative. |
371 |
Description:
Transmitter or sensor OIML self-check values have been detected out of range.
Possible Cause:
Unexpected degradation of key transmitter or sensor measurement parts.
Suggested Action:
Contact local representative. |
372 |
Byte 4 |
373 |
Description:
The Measurement System is checking and initializing the electronics before starting flow measurements.
Possible Cause:
Power up or reset has occurred.
Suggested Action:
None: this alarm is expected to occur during device start up. |
374 |
Description:
Communications fault detected in the circuit for the current output.
Possible Cause:
Defective transmitter cartridge electronics.
Suggested Action:
Replace cartridge.
Contact local representative. |
375 |
Description:
System calibration not completed correctly.
Possible Cause:
System calibration procedure not completed correctly.
Suggested Action:
If the transmitter is a retrofit to an old sensor, contact local representative for upgrade procedure. |
376 |
Description:
Incompatible transmitter and sensor calibration modes detected.
Possible Cause:
The transmitter and sensor calibration modes are not matched and the transmitter and sensor must not be used together.
Suggested Action:
Contact local representative. |
377 |
Description:
Corrupted firmware detected in the transmitter.
Possible Cause:
A CRC failure was detected in the ROM code memory of the transmitter.
Defective transmitter cartridge electronics.
Suggested Action:
Contact local representative. |
378 |
Description:
A memory fault detected in the transmitter.
Possible Cause:
A write/read failure detected in the data memory of the transmitter.
Defective transmitter cartridge electronics.
Suggested Action:
Replace cartridge.
Contact local representative. |
379 |
Description:
The HART output is simulating one of the two signalling frequencies.
Possible Cause:
Simulation mode is enabled and the HART frequency is being driven with a user-selected value.
Suggested Action:
Stop simulation of HART output frequency. |
380 |
Description:
An alarm is being simulated.
Possible Cause:
An operator action has caused an alarm to be simulated.
Suggested Action:
Stop the alarm simulation. |
381 |
Byte 5 |
382 |
Description:
A memory fault has been detected in the transmitters non-volatile memory.
Possible Cause:
A CRC failure was detected in the non-volatile memory.
Defective transmitter cartridge electronics.
Suggested Action:
Replace cartridge.
Contact local representative. |
383 |
Error ID |
384 |
Group |
385 |
Insertion Factor |
386 |
min: 0.0
max: 3.0 |
387 |
1.4f |
388 |
Language |
389 |
English |
390 |
Deutsch |
391 |
Français |
392 |
Español |
393 |
Italiano |
394 |
Polski |
395 |
DO1 Action |
396 |
Normally Open |
397 |
Normally Closed |
398 |
DO2 Action |
399 |
DO3 Action |
400 |
No Function |
401 |
F/R Signal |
402 |
Digital Out Alarm |
403 |
Value |
404 |
Limit Frequency |
405 |
4.4f |
406 |
Loop R Max. |
407 |
min: 7.5
max: 150.0 |
408 |
Loop R Min. |
409 |
1st Line |
410 |
Volume Flowrate |
411 |
Q% |
412 |
Current Out |
413 |
Volume Forward |
414 |
Volume Reverse |
415 |
Volume Net |
416 |
2nd Line |
417 |
3rd Line |
418 |
Meter Mode |
419 |
Forward And Reverse |
420 |
Forward Only |
421 |
Reverse Only |
422 |
Excitation Current |
423 |
3.0f |
424 |
50Hz |
425 |
60Hz |
426 |
4..20 mA |
427 |
4..12..20 mA |
428 |
4..20 mA FWD/REV |
429 |
DO1 State |
430 |
Open |
431 |
Closed |
432 |
DO2 State |
433 |
DO3 State |
434 |
TX PIN |
435 |
mm |
436 |
Probe Pipe Bore |
437 |
min: 1.0
max: 5000.0 |
438 |
Profile Factor |
439 |
Pulses / Unit |
440 |
min: 0.00001
max: 10000000.0 |
441 |
Pulse Mode |
442 |
Pulse / Unit |
443 |
min: 0.0
max: 5250.0 |
444 |
ms |
445 |
Pulse Width |
446 |
min: 0.09
max: 2000.0 |
447 |
s |
448 |
Damping |
449 |
min: 0.02
max: 60.0 |
450 |
Cal. Cert. No. |
451 |
Cal. Mode |
452 |
WaterMaster |
453 |
ProcessMaster |
454 |
Sensor Cal |
455 |
Retrofit |
456 |
OIML Class 1 |
457 |
OIML Class 2 |
458 |
Special |
459 |
OIML Cert'd Class 1 |
460 |
OIML Cert'd Class 2 |
461 |
Qmax DN |
462 |
Sensor Size |
463 |
DN1 |
464 |
DN1_5 |
465 |
DN2 |
466 |
DN3 |
467 |
DN4 |
468 |
DN6 |
469 |
DN8 |
470 |
DN10 |
471 |
DN15 |
472 |
DN20 |
473 |
DN25 |
474 |
DN32 |
475 |
DN40 |
476 |
DN50 |
477 |
DN65 |
478 |
DN80 |
479 |
DN100 |
480 |
DN125 |
481 |
DN150 |
482 |
DN200 |
483 |
DN250 |
484 |
DN300 |
485 |
DN350 |
486 |
DN400 |
487 |
DN450 |
488 |
DN500 |
489 |
DN600 |
490 |
DN700 |
491 |
DN760 |
492 |
DN800 |
493 |
DN900 |
494 |
DN1000 |
495 |
DN1050 |
496 |
DN1100 |
497 |
DN1200 |
498 |
DN1400 |
499 |
DN1500 |
500 |
DN1600 |
501 |
DN1800 |
502 |
DN2000 |
503 |
Sensor Type |
504 |
Probe |
505 |
Process |
506 |
Hygienic |
507 |
WM Reduced Throat |
508 |
WM Full Bore |
509 |
DE4 |
510 |
DE2 |
511 |
Process OIML |
512 |
Hygienic OIML |
513 |
Electrode Material |
514 |
Stainless Steel |
515 |
Hastelloy C4 |
516 |
Hastelloy C276 |
517 |
Titanium |
518 |
Tantalum |
519 |
Hastelloy B3 |
520 |
Platinum Iridium |
521 |
Duplex Steel |
522 |
Nickel |
523 |
St. Steel 316TI |
524 |
Hastelloy C(DL) |
525 |
Tungsten Carbide |
526 |
First Cal. Date |
527 |
Device.sensorIdHARTForm |
528 |
Last Cal. Date |
529 |
Last Cal. Location |
530 |
Stonehouse |
531 |
Göttingen |
532 |
Warminster |
533 |
Moorebank |
534 |
Shanghai |
535 |
Burlington |
536 |
Not Specified |
537 |
Lining Material |
538 |
PTFE |
539 |
Tefzel ETFE |
540 |
PEEK |
541 |
Hard Rubber |
542 |
Linatex |
543 |
Elastomer |
544 |
Elastomer ACS |
545 |
Elastomer NSF61 |
546 |
POMC |
547 |
PFA |
548 |
PPS |
549 |
Soft Rubber |
550 |
Polyurethane |
551 |
Polypropylene |
552 |
THICK PTFE |
553 |
Ceramic Carbide |
554 |
Location TAG |
555 |
Run Hours |
556 |
Sensor SAP / ERP No. |
557 |
Sensor ID |
558 |
Sensor TAG |
559 |
ugal |
560 |
l |
561 |
igal |
562 |
m3 |
563 |
ft3 |
564 |
hl |
565 |
ml |
566 |
bls |
567 |
Ml |
568 |
Mugal |
569 |
min: 3.5
max: 23.0 |
570 |
min: -200.0
max: 200.0 |
571 |
3.3f |
572 |
Simulation Mode |
573 |
Iout |
574 |
Pulse 1 |
575 |
Pulse 2 |
576 |
Flow Velocity |
577 |
Q |
578 |
Q% |
579 |
TX Type |
580 |
HART F/W |
581 |
Trim St |
582 |
Special Size (Bore) |
583 |
4.1f |
584 |
Qmax DN (Special) |
585 |
Term Board S/W |
586 |
Volume And Pulse Unit |
587 |
H/W |
588 |
Address 1 |
589 |
Address 2 |
590 |
Contact |
591 |
Manufacturer Name |
592 |
TX SAP / ERP No. |
593 |
Software Revision |
594 |
TX TAG |
595 |
TX ID |
596 |
Hardware Revision |
597 |
TX Run Hours |
598 |
Hysteresis |
599 |
min: 0.0
max: 50.0 |
600 |
2.0f |
601 |
Flow Cutoff Level |
602 |
min: 0.0
max: 10.0 |
603 |
min: -250.0
max: 250.0 |
604 |
min: -50.0
max: 50.0 |
605 |
MID Status |
606 |
Non-MID |
607 |
Unlocked |
608 |
Locked |
609 |
Alarm Count |
610 |
Current ms |
611 |
Current Days |
612 |
Total ms |
613 |
Total Days |
614 |
pv |
615 |
sv |
616 |
Everything |
617 |
Common Tables |
618 |
Interoperable * |
619 |
Universal |
620 |
Common Practice |
621 |
Pressure Universal |
622 |
Pressure Common |
623 |
Menu |
624 |
Rosemount Magflow |
625 |
Rosemount Pressure |
626 |
Moore Products |
627 |
Siemens Pressure |
628 |
P2 Common |
629 |
PV |
630 |
Munge |
631 |
Analytical Oxygen/Combustion/Methane/CO |
632 |
Flow Totalizer - Rate Indicator |
633 |
Flow Variable Area |
634 |
Flow Coriolis Mass |
635 |
Level Ultrasonic |
636 |
Level Radar - Microwave |
637 |
Pressure Absolute |
638 |
Level Capacitance |
639 |
Pressure Differential |
640 |
Level Hydrostatic |
641 |
Level |
642 |
Pressure Absolute/Relative |
643 |
Level Microwave |
644 |
Level Radar |
645 |
Level Density - Nuclear |
646 |
Pressure Deltabar S Evolution |
647 |
Pressure Cerabar S Evolution |
648 |
Flow Electromagnetic |
649 |
Flow Vortex |
650 |
Flow Magmeter - Rack Version |
651 |
Flow High Performance Magmeter |
652 |
Flow Mass |
653 |
Flow Ultrasonic |
654 |
Flow Magnetic |
655 |
Flow Magnetic - Custody Transfer |
656 |
Flow 2-wire Magnetic |
657 |
Flow Coriolis Mass - Custody Transfer |
658 |
Flow 2-wire Vortex |
659 |
Flow Thermal |
660 |
Temperature Head Mounted |
661 |
Temperature Compact |
662 |
Temperature DIN Rail Mounted |
663 |
Analytical pH |
664 |
Analytical Conductivity - Conductive |
665 |
Analytical Conductivity - Inductive |
666 |
Temperature Sensor |
667 |
Level Servo |
668 |
Temperature DIN Rail |
669 |
Temperature |
670 |
Analytical ORP |
671 |
Analytical pION |
672 |
Analytical IConc |
673 |
Analytical Electrode Conductivity |
674 |
Analytical Toroidal Conductivity |
675 |
Valve Controller |
676 |
Pressure |
677 |
Pressure Multivariable |
678 |
Analytical pH/ORP |
679 |
Flow Coriolis |
680 |
Analytical Conductivity |
681 |
Valve Positioner/Pneumatic |
682 |
Temperature Dual Input |
683 |
Valve Actuator |
684 |
Analytical Density - Nuclear |
685 |
Level Continuous Gamma |
686 |
Level Laser Ranging |
687 |
Pressure Safety |
688 |
Pressure P, dP + Multivariable |
689 |
Temperature 2-wire |
690 |
Pressure w/ PID |
691 |
Pressure Saturated Steam |
692 |
Analytical Density - Gamma Ray |
693 |
Level Gamma Ray |
694 |
Analytical Weight - Gamma Ray |
695 |
Level w/ Density - Gamma Ray |
696 |
Analytical Motorized Density |
697 |
Flow Multivariable Mass |
698 |
Temperature Multivariable |
699 |
Specialty HART-to-Analog Signal Conv |
700 |
Flow dP |
701 |
Pressure Low Power |
702 |
Pressure Certified SIL2 |
703 |
Interoperable |
704 |
Analytical Density |
705 |
Valve Positioner/Electropneumatic |
706 |
Flow Magnetic Inductive |
707 |
Flow |
708 |
Analytical Oxygen |
709 |
Analytical |
710 |
Analytical Opacity Monitor |
711 |
Analytical Oxygen/Combustion |
712 |
Analytical 2-wire Conductivity |
713 |
Analytical 2-wire Conductivity w/ pure H20 |
714 |
Analytical 2-wire Conductivity w/ % conc |
715 |
Analytical 2-wire Oxygen/Chlorine/Ozone |
716 |
Analytical 2-wire pH/ORP |
717 |
Analytical 2-wire Contacting/Toroidal |
718 |
Analytical Oxygen - High Temperature |
719 |
Analytical Conductivity w/ % conc |
720 |
Analytical pH/ORP/ISE |
721 |
Analytical Amperometric Analyzer |
722 |
Pressure Pressure/Level |
723 |
Analytical Consistency |
724 |
Analytical Microwave-Pulp Consistency |
725 |
Valve Digital Positioner |
726 |
Valve Positioner |
727 |
Valve Smart Valve Positioner |
728 |
Temperature Differential |
729 |
Analytical Dissolved Oxygen |
730 |
Analytical pH Controller |
731 |
Analytical Conductivity/Resistivity Controller |
732 |
Analytical Conductivity/Resistivity |
733 |
Level Displacement |
734 |
Temperature w/ PID |
735 |
Valve Universal Positioner |
736 |
Level Radar - Reflex |
737 |
Valve Digital Positioner w/ PID |
738 |
Valve Intelligent Positioner |
739 |
Analytical Gas Detector |
740 |
Analytical Infrared Gas Detector |
741 |
Analytical Electrochemical Gas Detector |
742 |
Level Magnostrictive |
743 |
Valve On/Off Valve Controller |
744 |
Level Radar - Pulse |
745 |
Analytical Corrosion |
746 |
Level Continuous Capactive |
747 |
Valve Damper Actuator |
748 |
Valve Electric Damper Actuator |
749 |
Flow Electronic |
750 |
Flow Vortex - Multiparameter Mass |
751 |
Analytical Flame Detector |
752 |
Level Nuclear |
753 |
Analytical Density - Radiometric |
754 |
Level Radiometric |
755 |
Analytical Gas/Steam |
756 |
Level Nucleonic |
757 |
Analytical Blade Consistency |
758 |
Analytical Rotary Consistency |
759 |
FMU860 |
760 |
DT |
761 |
DVC |
762 |
FCX |
763 |
AS800 |
764 |
340T |
765 |
340C |
766 |
344 |
767 |
Siemens Micro K |
768 |
SITRANS L |
769 |
SIPAN PH |
770 |
SITRANS P |
771 |
75SMT |
772 |
UNIDELTA |
773 |
8320 |
774 |
SX5100 |
775 |
TSV175 |
776 |
DMU |
777 |
3780 |
778 |
BM70 |
779 |
8u |
780 |
8.3f |
781 |
.3f |
782 |
Are you sure you want to delete the data ? |
783 |
Are you sure you want to reset Volume FWD ? |
784 |
Are you sure you want to reset Volume REV ? |
785 |
Are you sure you want to reset Volume NET ? |
786 |
Are you sure you want to reset all Totalizer Values ? |