0 |
ABB |
1 |
658T |
2 |
Tag |
3 |
Date |
4 |
Month / Day / Year |
5 |
Message |
6 |
Xmtr Serial Number |
7 |
Field Device Specific Status Byte 1- Data that has Current Field Device status information relating to: failures / warnings / status of process. |
8 |
Current Data: Transmitter failed
-> go to workshop |
9 |
Redundant sensor failed
-> check sensor |
10 |
EEPROM disturbed
-> call ABB Kent-Taylor |
11 |
PROM checksum failed
-> call ABB Kent-Taylor |
12 |
PV out of sensor limits or bad
-> check measuring
chain |
13 |
Sensor open or short
-> check sensor |
14 |
Device temp < -40 or > 85 degC
-> check device |
15 |
Config. measuring range invalid
-> check range |
16 |
Field Device Specific Status Byte 2- Data that has Historical Field Device status information relating to: failures / warnings / status of process. |
17 |
Historical Data: Transmitter had failed
-> go to workshop |
18 |
Redundant sensor had failed
-> check sensor |
19 |
EEPROM was disturbed
-> call ABB Kent-Taylor |
20 |
PROM checksum had failed
-> call ABB Kent-Taylor |
21 |
PV was out of sensor limits or bad
-> check measuring
chain |
22 |
Sensor was open or short
-> check sensor |
23 |
Device temp was < -40 or > 85 degC
-> check device |
24 |
Config. measuring range was invalid
-> check range |
25 |
Trim 4-20mA |
26 |
|
27 |
Failsafe Report |
28 |
Switches the failsafe on or off. If switched off, the analog output will notreact to a failure. |
29 |
Substitution |
30 |
a.Select the mA output to be set upon failsafe. b.Switches the latched output on or off. |
31 |
Failsafe On |
32 |
Failsafe |
33 |
In case of a failure the analog output is set to the failsafe mA value. The value can be 3.6mA or 23.0 mA. |
34 |
OFF |
35 |
LOW - 3.6mA |
36 |
HIGH - 23.0mA |
37 |
OTHER |
38 |
Failsafe mA Value |
39 |
In case of a failure the analog output is set to the failsafe mA value. Min value - 3.6, Max value - 23.0. |
40 |
5.2f |
41 |
Invalid Failsafe Control Codes |
42 |
Sensor Type |
43 |
Pt100 DIN IEC |
44 |
Pt100 SAMA |
45 |
Ni100 DIN |
46 |
SAMA Ni |
47 |
Cr228/229 10 Ohm |
48 |
MINCO Ni120 |
49 |
T/C typ C |
50 |
RTD Special |
51 |
T/C Special |
52 |
Linearization |
53 |
Sensor Connection |
54 |
Defines the sensor type and the number of wires. |
55 |
millivolts |
56 |
Thermocouple |
57 |
T/C differential |
58 |
Two Wire RTD |
59 |
Three Wire RTD |
60 |
Four Wire RTD |
61 |
Dual 2W RTD diff |
62 |
Dual 2W independ |
63 |
Dual 2W secure |
64 |
Dual 2W average |
65 |
Display Settings |
66 |
Select the value to be displayed. |
67 |
Display PV |
68 |
Display % of Range |
69 |
Display AOut in mA |
70 |
Alternate PV/AOut |
71 |
Alternate PV/% |
72 |
Sensor Fail Det. |
73 |
Indicates if the system to detect sensor failures or line breaks is ON or OFF. |
74 |
Invalid linearization mode |
75 |
Warning: Check Units and Span |
76 |
7.2f |
77 |
Special characterization not available |
78 |
Invalid number of pairs of values, 2 - 22 pairs allowed. |
79 |
Warning: Turning Sensor Offset Curve System ON |
80 |
Cold Junction Temp. Compensation |
81 |
Lowest Junct Temp |
82 |
Actual CJ Temp |
83 |
Without CJ |
84 |
Fixed CJ Temp |
85 |
External via Ni100 |
86 |
Lowest Junct Temp |
87 |
Cold Junct Temp |
88 |
5.1f |
89 |
degC |
90 |
Display Mode Setup |
91 |
Enable or disable local keys to avoid accidental use. |
92 |
Enable |
93 |
Disable |
94 |
Special Sensor Des |
95 |
Text label describing the connected sensor. |
96 |
Xmtr Assembly |
97 |
Description of the transmitter assembly. |
98 |
Basic Unit |
99 |
DIN Rail Mounted |
100 |
Head Housing |
101 |
EEx-d Housing |
102 |
Customized |
103 |
Special |
104 |
Display Label |
105 |
Label that appears on the 3-line local display, max. 7 characters. |
106 |
Display Type |
107 |
One Line Display |
108 |
Three Line Display |
109 |
none |
110 |
Display Language |
111 |
The language used by the 658T local display. |
112 |
English |
113 |
German |
114 |
French |
115 |
Spanish |
116 |
Line Frequency |
117 |
Indicates the power line frequency and filter selected. |
118 |
50Hz,High Filter |
119 |
50Hz,High Speed |
120 |
60Hz,High Filter |
121 |
60Hz,High Speed |
122 |
Validation Time |
123 |
Validation time sets the time interval for bad data suppression. Min value - 0.25, Max value - 10. |
124 |
Smart Smoothing |
125 |
Suppression of noise through averaging with fast response to 1-10 degC changes of the input. Min value - 0.25, Max value - 30. |
126 |
Validation Time too Large |
127 |
Validation Time too Small |
128 |
Smart Smoothing Time too Large |
129 |
Smart Smoothing Time too Small |
130 |
Flush |
131 |
Lead resistance |
132 |
Analog Output |
133 |
Engineering Units |
134 |
Diff AOut |
135 |
PV AOut |
136 |
Analog output in mA of the differential measurement. |
137 |
Analog Output in mA. |
138 |
mA |
139 |
Damping |
140 |
Exponential damping of input signal, maximum time constant 32 seconds. |
141 |
.2f |
142 |
4.2f |
143 |
Sensor Serial # |
144 |
7d |
145 |
Diff % |
146 |
PV % |
147 |
Differential value of channel 1 and channel 2 in percent of range. |
148 |
PV in percent of range. |
149 |
URV |
150 |
URV - Upper Range Value of the differential measurement. |
151 |
URV - Upper Range Value. |
152 |
LRV |
153 |
LRV - Lower Range Value of the differential measurement. |
154 |
LRV - Lower Range Value. |
155 |
Diff |
156 |
PV |
157 |
Differential value of channel 1 and channel 2 in Engineering Units. |
158 |
Process Variable in Engineering Units |
159 |
Internal Temp |
160 |
Internal temperature of the device. |
161 |
4.0f |
162 |
Internal Temp Unit |
163 |
Engineering units of the internal temperature of the device. |
164 |
Channel1 |
165 |
Channel 1 value in Engineering Units of a dual measurement. |
166 |
Cold Junction Temp |
167 |
Channel2 |
168 |
Cold junction temperature measured by the external Ni100 sensor. |
169 |
Channel 2 value in Engineering Units of a dual measurement. |
170 |
Temp |
171 |
Xmtr Self Test |
172 |
Commands the 658T to perform a self-test. Note: Analog output is affected during the test. |
173 |
Lead Resist Trim |
174 |
Trim the lead resistances so that the output reads zero, repectively reset the historical lead resistance value to 0. Used with 2-wire or dual RTD measurements only. |
175 |
Reset Analog Trim |
176 |
Reset the Analog Output to the factory settings. |
177 |
Select Sensor |
178 |
Define the sensor type and the sensor connection. |
179 |
Sensor Setup Info |
180 |
Displays the sensor type, linearization mode, sensor connection, and cold junction compensation. |
181 |
Enable or disable the detection of a sensor failure or line break. |
182 |
Exit Line Break Detection |
183 |
Snsr Offset Curve |
184 |
Correction or characterization of input sensor(s). 2-22 pairs of values. |
185 |
Snsr Offset Curve |
186 |
Display the status of the Sensor Offset Curve System. |
187 |
Lowest Junc Temp |
188 |
Cold Junction Comp |
189 |
Lowest of the two thermocouple junctions temperatures. |
190 |
Method used for the compensation of the thermocouple cold junction. |
191 |
Display lowest of the two thermocouple junctions temperatures. |
192 |
Show configuration used for the compensation of the thermocouple cold junction. |
193 |
Failsafe Report |
194 |
Displays current failsafe setup. |
195 |
Failsafe Report |
196 |
Configuration of the mA output upon failsafe. |
197 |
Exit Failsafe Setup |
198 |
Engineering Units |
199 |
Set the engineering unit to be displayed with the Digital Value representation, Upper Range Value, Lower Range Value, and Lower Sensor Limit. |
200 |
Exit Engineering Units Setup |
201 |
Line Freq & Filt |
202 |
Set the power line frequency and filter. |
203 |
Exit Line Freq & Filter Setup |
204 |
Smart Smoothing |
205 |
Exit Smart Smoothing Setup |
206 |
Validation Time |
207 |
Exit Validation Time Setup |
208 |
Set LRV |
209 |
Specify the Lower Range Value, (the 4ma value). |
210 |
Exit LRV Setup |
211 |
Set URV |
212 |
Specify the Upper Range Value, (the 20ma value). |
213 |
Exit URV Setup |
214 |
Apply LRV |
215 |
Perform a device rerange by applying the 4ma value to the device input. |
216 |
Apply URV |
217 |
Perform a device rerange by applying the 20ma value to the device input. |
218 |
Set Damping |
219 |
Specify exponential damping of input signal, maximum time constant 32 seconds. |
220 |
Exit DAMPING Setup |
221 |
Internal Temp Unit |
222 |
Exit Internal Temp Unit Setup |
223 |
Reset Failsafe Val |
224 |
Clear latched Failsafe. |
225 |
Clear Hist Status |
226 |
Clear the historical status information for failures. The historical status information is not automatically cleared when the failure is removed. They have to be cleared manually. |
227 |
warn |
228 |
Offline Configuration |
229 |
Offline |
230 |
Display Data |
231 |
Review Setup |
232 |
Transmitter Setup |
233 |
Input Setup |
234 |
Output Setup |
235 |
Failsafe Setup |
236 |
Output Trim |
237 |
Other Setup |
238 |
Xmtr Filtering |
239 |
Local Display |
240 |
Xmtr Identifiers |
241 |
Tag Setup |
242 |
Device Information |
243 |
Diagnostics |
244 |
Xmtr Internal Diag |
245 |
Failure Status |
246 |
Xmtr Internal Vars |
247 |
FMU860 |
248 |
DT |
249 |
DVC |
250 |
FCX |
251 |
AS800 |
252 |
340T |
253 |
340C |
254 |
344 |
255 |
Siemens Micro K |
256 |
SITRANS L |
257 |
SIPAN PH |
258 |
SITRANS P |
259 |
75SMT |
260 |
UNIDELTA |
261 |
8320 |
262 |
SX5100 |
263 |
TSV175 |
264 |
DMU |
265 |
3780 |
266 |
BM70 |
267 |
8u |
268 |
NOTE: Analog output is affected during test! Press OK to continue with test. |
269 |
Please wait. The self test will take about 10 sec. Results will be displayed on the next screen. |
270 |
Device may be stuck in self-test! |
271 |
Self test completed. No faults found |
272 |
Lead resistance should be: |
273 |
Trimmed;Reset |
274 |
Please bridge the RTD / Resistor now |
275 |
Please bridge the RTDs / Resistors now |
276 |
Have you bridged the RTD(s) ? |
277 |
No;Yes |
278 |
Lead resistance
trimmed |
279 |
Lead resistance trim aborted |
280 |
Lead resistance set to 0? |
281 |
Ok to Reset Analog Output to Factory Settings? |
282 |
Enter Sensor Offset Curve if you desire any units other than Ohms |
283 |
Sensor connection
set to: %{0} |
284 |
Enter Sensor Offset Curve if you desire any units other than mV |
285 |
Linearization Mode |
286 |
Downloading sensor configuration to the device |
287 |
Cold Junction Temp |
288 |
Lowest Junction
Temperature |
289 |
Downloading cold junction configuration to the device. |
290 |
Sensor Type:
%{0}
Connection:
%{1}
Sensor Serial Num:
%{2} |
291 |
Cold Junction Comp:
%{0}
Cold Junction Temp:
%{1}
Linearization
%{2} |
292 |
Cold Junction Comp:
%{0}
Linearization
%{2} |
293 |
Lowest Junction
Temp:
%{1}
Linearization
%{2} |
294 |
Linearization
%{2} |
295 |
Sensor Failure
Detection |
296 |
Sensor Failure Detection ON |
297 |
Sensor Failure Detection OFF |
298 |
Enter the number of pairs of values, (Min-2, Max-22) |
299 |
There must be at least 2 pairs of values. |
300 |
Point %{local_pos} Indicated Value
Unit: %{0} |
301 |
Actual Value
Unit: %{1} |
302 |
Sensor Offset Curve System OFF |
303 |
Sensor Offset Curve System ON with %{0} pairs of values. |
304 |
Cold Junction Comp:
%{0}
Cold Junction Temp:
%{1}
|
305 |
Cold Junction Comp:
%{0}
Cold Junction Temp:
%{2}
|
306 |
Cold Junction Comp:
%{0}
Cold Junction Temp:
%{3}
|
307 |
Cold Junction Comp:
%{0} |
308 |
Lowest Junction
Temp:
%{1}
|
309 |
Failsafe Report
OFF |
310 |
Failsafe Report
ON - 3.6mA |
311 |
Failsafe Report
ON - 23mA |
312 |
Failsafe Report
OTHER - %{0}mA |
313 |
Failsafe mA Value
Min-3.6, Max-23.0
Current value: |
314 |
Ohms not valid for thermocouple sensors |
315 |
mV not valid for RTD sensors |
316 |
Engineering Units set to %{0}. |
317 |
Line Freq. & Filter set to %{0}. |
318 |
Enter Smart Smoothing value
(Min-0.25, Max-30) |
319 |
Smart smoothing set to %{0} sec. |
320 |
Enter Validation Time
(Min-0.25, Max-10.0) |
321 |
Validation Time set to %{0} sec. |
322 |
Enter LRV |
323 |
LRV set to %{0} %{1} |
324 |
Enter URV |
325 |
URV set to %{0} %{1} |
326 |
PV = %{1} %{2}
LRV = %{0} %{2} |
327 |
New LRV %{1} |
328 |
Accept new value;Read new value;Abort |
329 |
Please wait. |
330 |
PV = %{1} %{2}
URV = %{0} %{2} |
331 |
New URV %{1} |
332 |
Enter Damping
(32 sec. maximum) |
333 |
Damping set to %{0} sec. |
334 |
Internal Temp Unit set to %{0} |
335 |
Clear Failsafe. Back to mode measuring if trouble is removed. |
336 |
Clear historical status? |
337 |
No;Yes |
338 |
Historical status NOT cleared. |
339 |
Historical status cleared. |