Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
level_sensor_value_unit | 4005 | PV units P12 | PV Units - the units that are displayed with the PV, Ullage and associated readings. | R/W | Enum | 2048 |
level_value | 4006 | Process value D10 | Process value - The digital value based on the height scaled by P13, or profiled by P11 and P13 if the curve profile is non-linear. | R | Float | 34 |
current_output | 4007 | Current output D12 | Current output - The analog value related to the PV | R/W | Float | 66 |
percent_range | 4008 | Percent range D13 | Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. | R | Float | 34 |
level_damping_value | 4009 | Smoothing time P20 | Smoothing time - the damping in seconds applied to the PV value and the analogue output. | R/W | Float | 32 |
level_sensor_serial_number | 400A | Sensor ser No P05 | Sensor serial number - usually set to the same value as the Device ID but may be changed for site use. | R/W | Unsigned | 2048 |
level_sensor_units | 400D | R/W | Unsigned | 2048 | ||
level_upper_range_value | 400B | Calibrate max P15 | Calibrate max - the PV at which the current output is 20mA and the % output is 100%. | R/W | Float | 32 |
level_lower_range_value | 400C | Calibrate min P16 | Calibrate min - the PV at which the current output is 4mA and the % output is 0%. | R/W | Float | 32 |
alarm_code | 4010 | AO Alrm typ | R | Enum | 2048 | |
Name | ID | Label | Description | Type | Access | Class |