Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
upper_trim_count | 4027 | High Trim Count | R | Unsigned | 2048 | |
sensor_reference | 4028 | Sensor Reference | R | Unsigned | 2048 | |
gain | 4029 | Gain | GAIN is a factory set function designed to adjust the return pulse to the best possible signal to noise ratio. The GAIN setting will be optimized by the MT5xxx based on the entries from the BASIC SETUP menu. Increasing the GAIN setting will amplify the noise as well as the return pulse. Lowering the GAIN setting will decrease the return pulse as well as the noise. | R/W | Unsigned | 2048 |
range | 402A | Range | The RANGE setting is determined by the PROBE LENGTH. RANGE 1 is set for probes shorter than 100 feet. RANGE 2 is set for probes from 100 to 200 feet. Changing the RANGE setting will erase all factory trim settings and calibration values. Changing the RANGE setting is not recommended unless a commitment to changing the physical probe length has been made. | R/W | Enum | 2048 |
shape | 402B | Shape | The SHAPE function will be set based on the mounting configuration. Like the GAIN function it is designed to create the best signal to noise ratio from the return pulse. The SHAPE setting will determine how the signal is amplified. | R/W | Enum | 2048 |
unused_flag | 402C | R/W | Unsigned | 0 | ||
level_pv | 402D | PV | LEVEL PV is a function which allows the user to determine which variable the OUTPUT of the MT5100 will be based upon. Selections for OUTPUT are Total and Interface. Total and Interface are the actual linear measurements the MT5100 is interpreting from its configuration. Total is the top level of all liquids and Interface is the level of the lower liquid in the vessel. | R/W | Enum | 2048 |
measure_mode | 402E | Measure Mode | The MT5xxx can be used to measure Media Level or Ullage. Media Level refers to a Level Measurement from the end of the probe to the surface of the product level. Said differently, it is measuring the amount of product in the tank. 2Ullage refers to a Level Measurement from the face of the sensor to the surface of the product being measured. Said differently, it is measuring the amount of vapor space in the tank. 2Factory default the MEASURE MODE will be Media Level. Media Level = Level in the tank Ullage = vapor space in the tank | R/W | Enum | 2048 |
avail_levels | 402F | Available Levels | R | Enum | 2048 | |
xmitter_status_0 | 4030 | Device Status Bits 0 | R | BitEnum | 3 | |
Name | ID | Label | Description | Type | Access | Class |