Variable Name: range

Variable ID: 0x402A

Variable Label: Range

Variable Help: The RANGE setting is determined by the PROBE LENGTH. RANGE 1 is set for probes shorter than 100 feet. RANGE 2 is set for probes from 100 to 200 feet. Changing the RANGE setting will erase all factory trim settings and calibration values. Changing the RANGE setting is not recommended unless a commitment to changing the physical probe length has been made.

Variable Handling: R/W

Variable Class: Device

Variable Size: 1

Variable DataType: Enum

Variable Enum Value Variable Enum Text
0x0000 1 Short Range
0x0001 2 Long Range

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
151 4075 read_basic_device_setup
160 407B read_extended_setup

Variable Write Command List

Command Number Command ID Command Name
152 4076 write_probetype_mounting_config_flags
162 407D write_gain_and_config_flags