Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
x3302_long_oi | 404A | Left Oi | Percent of calibrated Oi test signal returned by the left sensor. Reading should be 90 to 110 percent. If reading is below 90 percent, first try clean the window if the reading is still below 90 go to (Device Setup), select (Calibration) and perform Oi Calibration. If over 110% recalibrate. | R | Unsigned | 2051 |
x3302_middle_oi | 404B | Middle Oi | Percent of calibrated Oi test signal returned by the middle sensor. Reading should be 90 to 110 percent. If reading is below 90 percent, first try clean the window if the reading is still below 90 go to (Device Setup), select (Calibration) and perform Oi Calibration. If over 110% recalibrate. | R | Unsigned | 2051 |
x3302_short_oi | 404C | Right Oi | Percent of calibrated Oi test signal returned by the right sensor. Reading should be 90 to 110 percent. If reading is below 90 percent, first try clean the window if the reading is still below 90 go to (Device Setup), select (Calibration) and perform Oi Calibration. If over 110% recalibrate. | R | Unsigned | 2051 |
x3302_voltage_level | 404D | Voltage | Actual detector supply voltage. Specified operating voltage is 18 to 30 Vdc. | R | Unsigned | 2051 |
x3302_temperature | 404E | Temperature | Actual integral temperature of detector. | R | Unsigned | 2051 |
x3302_part_number | 404F | Part Number | Manufacturer's part number for this device. | R | Unsigned | 2049 |
x3302_dash_number | 4050 | Dash Number | Manufacturer's secondary part number for this device. | R | Unsigned | 2049 |
x3302_man_date | 4051 | Manufacture Date | Date of manufacture. Shown as month/day/year | R | HartDate | 2049 |
x3302_snsr_firm_ver | 4052 | Sensor Firmware | Firmware revision level of sensor module. | R | Unsigned | 2049 |
x3302_hart_firm_ver | 4053 | HART Firmware | Firmware revision level of HART interface board (HIB). | R | Unsigned | 2049 |
Name | ID | Label | Description | Type | Access | Class |