Variable Name: x3302_long_oi
Variable ID: 0x404A
Variable Label: Left Oi
Variable Help: Percent of calibrated Oi test signal returned by the left sensor. Reading should be 90 to 110 percent. If reading is below 90 percent, first try clean the window if the reading is still below 90 go to (Device Setup), select (Calibration) and perform Oi Calibration. If over 110% recalibrate.
Variable Handling: R
Variable Class: Dynamic | Diagnostic | Device
Variable Size: 2
Variable DataType: Unsigned
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
159 | 4064 | x3302_cmd_rd_long_oi |
Variable Write Command List
None