Variable Name: x3302_long_oi

Variable ID: 0x404A

Variable Label: Left Oi

Variable Help: Percent of calibrated Oi test signal returned by the left sensor. Reading should be 90 to 110 percent. If reading is below 90 percent, first try clean the window if the reading is still below 90 go to (Device Setup), select (Calibration) and perform Oi Calibration. If over 110% recalibrate.

Variable Handling: R

Variable Class: Dynamic | Diagnostic | Device

Variable Size: 2

Variable DataType: Unsigned

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
159 4064 x3302_cmd_rd_long_oi

Variable Write Command List

None