名称 | ID | 标签 | 描述 | 类型 | 访问 | 分类 |
---|---|---|---|---|---|---|
limit_enbl | 4016 | Limit Control | Limit the valve travel in certain region specified by upper and lower limits. | 读/写 | 枚举 | 1025 |
control_mode | 2772 | Control Mode | Control the valve in either normal or reverse acting mode. | 读/写 | 枚举 | 1025 |
flop_mode | 4017 | Display Mode | Show %closed or %open on positioner display. | 读/写 | 枚举 | 1025 |
digital_setpoint_mode | 4018 | Digital Mode | When enabled, the positioner will ignore 4 to 20 mA input signal, and allows control to be applied digitaly. | 读/写 | 枚举 | 1025 |
cutoff_mode | 4019 | Cutoff Mode | When enabled, the positioner will apply a larger than necessary close control signal to the valve | 读/写 | 枚举 | 1025 |
valve_type | 401A | Valve Type | Positioner can work with linear and rotary valves. | 读/写 | 枚举 | 1025 |
compensator_gain_setting | 401B | P Gain Index | Proportional gain index is from 1 to 20 (with 20 is the highest). | 读/写 | 枚举 | 8 |
compensator_derivative_gain_switch | 401C | D Gain Switch | Derivative gain switch allows finer adjustment of the compensator derivative gain. For small valves this switch should be in the LOW position. | 读/写 | 枚举 | 1024 |
compensator_derivative_gain_setting | 401D | D Gain Index | Derivative gain index is from 1 to 20 (with 20 is the highest). | 读/写 | 枚举 | 8 |
integrator_setting | 401E | Integral Time | The integral time is the time ellapsed before the valve try to offset its steady state error when the valve does not move. In each time ellapsed, the valve corrects itself in 0.2% increment. | 读/写 | 枚举 | 8 |
名称 | ID | 标签 | 描述 | 类型 | 访问 | 分类 |