名称 | ID | 标签 | 描述 | 类型 | 访问 | 分类 |
---|---|---|---|---|---|---|
valve_type | 401A | Valve Type | Positioner can work with linear and rotary valves. | 读/写 | 枚举 | 1025 |
compensator_gain_setting | 401B | P Gain Index | Proportional gain index is from 1 to 20 (with 20 is the highest). | 读/写 | 枚举 | 8 |
compensator_derivative_gain_switch | 401C | D Gain Switch | Derivative gain switch allows finer adjustment of the compensator derivative gain. For small valves this switch should be in the LOW position. | 读/写 | 枚举 | 1024 |
compensator_derivative_gain_setting | 401D | D Gain Index | Derivative gain index is from 1 to 20 (with 20 is the highest). | 读/写 | 枚举 | 8 |
integrator_setting | 401E | Integral Time | The integral time is the time ellapsed before the valve try to offset its steady state error when the valve does not move. In each time ellapsed, the valve corrects itself in 0.2% increment. | 读/写 | 枚举 | 8 |
mode_of_calibration | 401F | 读/写 | 无符号 | 4096 | ||
valve_open_slew_limit | 4020 | Opening Speed | The speed limit at which the valve opens. This index limits how fast the control input is applied to the input of the valve feedback loop when valve is opening. | 读/写 | 枚举 | 8 |
valve_close_slew_limit | 4021 | Closing Speed | The speed limit at which the valve closes. This index limits how fast the control input is applied to the input of the valve feedback loop when valve is closing. | 读/写 | 枚举 | 8 |
digital_setpoint | 4022 | Dig.Setpt | Digital Setpoint allows digital control with the percent value specified, when digital mode is enabled. | 读/写 | 无符号 | 8 |
mA_upper_limit | 4023 | Setpn FS | Indicates the setpoint upper limit in mA. | 读/写 | 无符号 | 8 |
mA_lower_limit | 4024 | Setpn Zero | Indicates the setpoint lower limit in mA. | 读/写 | 无符号 | 8 |
IFS | 4025 | Max Current | IFS is measured Full Scale Loop Current | 读/写 | 浮点 | 8 |
IMN | 4026 | Min Current | IMN is measured Minimum Loop Current | 读/写 | 浮点 | 8 |
NFS | 4027 | Full scale A/D count | Full scale A/D count returned by command 135 | 读/写 | 无符号 | 8 |
NMN | 4028 | MIN scale A/D count | Minimum scale A/D count returned by command 135 | 写 | 无符号 | 8 |
mA_slope | 4029 | mA slope | mA slope is (IFS-IMN)*2^16/(NFS-NMN) | 写 | 无符号 | 8 |
mA_offset | 402A | mA offset | mA offset is NFS-(IFS*2^16/mAslope) | 写 | 整型 | 8 |
reserved_2 | 402B | 读/写 | 枚举 | 1025 | ||
trvl_alert_enbl | 402C | Travel Alert | When enabled, the positioner will signal alert signal when upper or lower travel limits is violated. | 读/写 | 枚举 | 1025 |
cyc_alert_enbl | 402D | Cycle Alert | When enabled, the positioner will signal alert signal when cycle limits is violated. | 读/写 | 枚举 | 1025 |
acum_alert_enbl | 402E | Accum. Alert | When enabled, the positioner will signal alert signal when accumulator limits is violated. | 读/写 | 枚举 | 1025 |
int_ctrl_enbl | 402F | Integral Control | When disabled, the positioner will use intrgral control to offset the steady error. | 读/写 | 枚举 | 1025 |
dev_alert_enbl | 4030 | Deviation Alert | When enabled, the positioner will signal alert signal when deviation limits is violated. | 读/写 | 枚举 | 1025 |
close_limit_enbl | 4031 | ClsLmtSw Alert | When enabled, the positioner will signal alert signal when close limit switch is on. | 读/写 | 枚举 | 1025 |
open_limit_enbl | 4032 | OpnLmtSw Alert | When enabled, the positioner will signal alert signal when open limit switch is on. | 读/写 | 枚举 | 1025 |
名称 | ID | 标签 | 描述 | 类型 | 访问 | 分类 |