名称 | ID | 标签 | 描述 | 类型 | 访问 | 分类 |
---|---|---|---|---|---|---|
setpoint_value | 4000 | Setpoint | Refers to the requested position in terms of percent. | 读 | 浮点 | 10 |
position_value | 4001 | Position | Refers to the actual valve position in terms of percent. | 读 | 浮点 | 10 |
pressure_value | 138E | Pressure | Refers to the output pressure of OUT 1 of the positioner in terms of percent. | 读 | 浮点 | 10 |
setpoint_units | 4002 | Setpoint Units | 现场设备变量单位——使用数值表示、最小范围、范围上限、范围下限、传感器上限和传感器下限显示的工程单位。 | 读/写 | 枚举 | 8 |
position_units | 4003 | Position Units | 现场设备变量单位——使用数值表示、最小范围、范围上限、范围下限、传感器上限和传感器下限显示的工程单位。 | 读 | 枚举 | 8 |
pressure_units | 138D | Pressure Units | 现场设备变量单位——使用数值表示、最小范围、范围上限、范围下限、传感器上限和传感器下限显示的工程单位。 | 读 | 枚举 | 8 |
sensor_units | 4004 | Sensor Units | 现场设备变量单位——使用数值表示、最小范围、范围上限、范围下限、传感器上限和传感器下限显示的工程单位。 | 读 | 枚举 | 8 |
range_units | 4005 | 主变量范围单位 | 现场设备变量单位——使用数值表示、最小范围、范围上限、范围下限、传感器上限和传感器下限显示的工程单位。 | 读 | 枚举 | 8 |
analog_alarm_code | 4006 | 模拟量输出报警类型 | 模拟量输出报警类型——定义当现场设备检测到模拟量输出可能未跟踪关联现场设备变量时模拟量输出响应的方式。注意——数值表示可能不确定。 | 读 | 枚举 | 64 |
input_analog_value | 4007 | Input I | Refers to the requested position in terms of current in mA. | 读 | 浮点 | 66 |
output_analog_value | 4008 | Output I | Refers to the actual valve position in terms of current in mA. | 读 | 浮点 | 66 |
damping_val | 4009 | 主变量阻尼 | 阻尼值——同时应用至各自模拟量输出的数值表示和模拟值的阻尼时间常数。该变量的单位始终为秒钟。 | 读 | 浮点 | 8 |
input_upper_value | 400A | FS In | Refers to the input current to move the valve to full open / close position in normal / reverse operation. | 读 | 浮点 | 32 |
input_lower_value | 400B | Zero In | Refers to the input current to move the valve to full open / close position in normal / reverse operation. | 读 | 浮点 | 32 |
output_upper_value | 400C | FS Out | Refers to the output current when the valve is at full open / close position in normal / reverse operation. | 读 | 浮点 | 32 |
output_lower_value | 400D | Zero Out | Refers to the output current when the valve is at full open / close position in normal / reverse operation. | 读 | 浮点 | 32 |
sensor_serial_number | 400E | Sensor Serial | 传感器序列号——识别数值表示或现场设备变量来源的传感器。 | 读 | 无符号 | 32 |
min_sensor_span | 400F | Min_Sensor_Span | 最小范围值——定义上限值和下限值之间允许的最小差。 | 读 | 浮点 | 32 |
flow_type | 4014 | Flow Type | The positioner supports Linear, Quick Opening, and Equal Percentage flow types. | 读/写 | 枚举 | 32 |
reserved_1 | 4015 | 读/写 | 整型 | 1025 | ||
limit_enbl | 4016 | Limit Control | Limit the valve travel in certain region specified by upper and lower limits. | 读/写 | 枚举 | 1025 |
control_mode | 2772 | Control Mode | Control the valve in either normal or reverse acting mode. | 读/写 | 枚举 | 1025 |
flop_mode | 4017 | Display Mode | Show %closed or %open on positioner display. | 读/写 | 枚举 | 1025 |
digital_setpoint_mode | 4018 | Digital Mode | When enabled, the positioner will ignore 4 to 20 mA input signal, and allows control to be applied digitaly. | 读/写 | 枚举 | 1025 |
cutoff_mode | 4019 | Cutoff Mode | When enabled, the positioner will apply a larger than necessary close control signal to the valve | 读/写 | 枚举 | 1025 |
valve_type | 401A | Valve Type | Positioner can work with linear and rotary valves. | 读/写 | 枚举 | 1025 |
compensator_gain_setting | 401B | P Gain Index | Proportional gain index is from 1 to 20 (with 20 is the highest). | 读/写 | 枚举 | 8 |
compensator_derivative_gain_switch | 401C | D Gain Switch | Derivative gain switch allows finer adjustment of the compensator derivative gain. For small valves this switch should be in the LOW position. | 读/写 | 枚举 | 1024 |
compensator_derivative_gain_setting | 401D | D Gain Index | Derivative gain index is from 1 to 20 (with 20 is the highest). | 读/写 | 枚举 | 8 |
integrator_setting | 401E | Integral Time | The integral time is the time ellapsed before the valve try to offset its steady state error when the valve does not move. In each time ellapsed, the valve corrects itself in 0.2% increment. | 读/写 | 枚举 | 8 |
mode_of_calibration | 401F | 读/写 | 无符号 | 4096 | ||
valve_open_slew_limit | 4020 | Opening Speed | The speed limit at which the valve opens. This index limits how fast the control input is applied to the input of the valve feedback loop when valve is opening. | 读/写 | 枚举 | 8 |
valve_close_slew_limit | 4021 | Closing Speed | The speed limit at which the valve closes. This index limits how fast the control input is applied to the input of the valve feedback loop when valve is closing. | 读/写 | 枚举 | 8 |
digital_setpoint | 4022 | Dig.Setpt | Digital Setpoint allows digital control with the percent value specified, when digital mode is enabled. | 读/写 | 无符号 | 8 |
mA_upper_limit | 4023 | Setpn FS | Indicates the setpoint upper limit in mA. | 读/写 | 无符号 | 8 |
mA_lower_limit | 4024 | Setpn Zero | Indicates the setpoint lower limit in mA. | 读/写 | 无符号 | 8 |
IFS | 4025 | Max Current | IFS is measured Full Scale Loop Current | 读/写 | 浮点 | 8 |
IMN | 4026 | Min Current | IMN is measured Minimum Loop Current | 读/写 | 浮点 | 8 |
NFS | 4027 | Full scale A/D count | Full scale A/D count returned by command 135 | 读/写 | 无符号 | 8 |
NMN | 4028 | MIN scale A/D count | Minimum scale A/D count returned by command 135 | 写 | 无符号 | 8 |
mA_slope | 4029 | mA slope | mA slope is (IFS-IMN)*2^16/(NFS-NMN) | 写 | 无符号 | 8 |
mA_offset | 402A | mA offset | mA offset is NFS-(IFS*2^16/mAslope) | 写 | 整型 | 8 |
reserved_2 | 402B | 读/写 | 枚举 | 1025 | ||
trvl_alert_enbl | 402C | Travel Alert | When enabled, the positioner will signal alert signal when upper or lower travel limits is violated. | 读/写 | 枚举 | 1025 |
cyc_alert_enbl | 402D | Cycle Alert | When enabled, the positioner will signal alert signal when cycle limits is violated. | 读/写 | 枚举 | 1025 |
acum_alert_enbl | 402E | Accum. Alert | When enabled, the positioner will signal alert signal when accumulator limits is violated. | 读/写 | 枚举 | 1025 |
int_ctrl_enbl | 402F | Integral Control | When disabled, the positioner will use intrgral control to offset the steady error. | 读/写 | 枚举 | 1025 |
dev_alert_enbl | 4030 | Deviation Alert | When enabled, the positioner will signal alert signal when deviation limits is violated. | 读/写 | 枚举 | 1025 |
close_limit_enbl | 4031 | ClsLmtSw Alert | When enabled, the positioner will signal alert signal when close limit switch is on. | 读/写 | 枚举 | 1025 |
open_limit_enbl | 4032 | OpnLmtSw Alert | When enabled, the positioner will signal alert signal when open limit switch is on. | 读/写 | 枚举 | 1025 |
名称 | ID | 标签 | 描述 | 类型 | 访问 | 分类 |