Loading…
Name ID Label Description Type Access Class
flow_damping_value 1F87 PV Damp Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. R/W Float 32
pulse_output_value 1F73 Puls outp Pulse Output Value- scaled frequency output from 0-1000 Hz, linear with input. R Float 514
net_total_value 1F8A Measure net totl Net Total Value- Resettable totalizer value. Counts frequency output pulses while total control is turned on. R Float 18
gross_total_value 1F89 Measure gross totl Gross Total Value- Non-resettable totalizer value. Counts frequency output pulses while total control is turned on. This value will be reset to 0 when the pulse scaling, line size, or units are changed. R Float 18
reverse_total_value 1F8B Measure reverse totl Reverse Total Value- Non-resettable totalizer value. Counts frequency output pulses while total control is turned on and flow is in the reverse direction. This value will be reset to 0 when the pulse scaling, line size, or units are changed. R Float 18
transfer_function 1F84 Xfer fnctn Transfer Function- Defines the transformation function that will be applied from the Field Device Variable to the Analog Output, and Percent Range. The Transfer Function does not affect the Digital Value representation. R Enum 64
flow_sensor_serial_number 1F82 PV Snsr s/n Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. R/W Unsigned 2048
coil_drive_frequency 1F4D Coil driv freq Coil Drive Frequency- Frequency that the coils operate at. R/W Enum 8
flow_alarm_select 1F83 AO Alrm typ Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. R Enum 64
flow_analog_value 1F7D AO Analog Output Value- Value that tracks the Digital Value representation, under normal operating modes R/W Float 66
Name ID Label Description Type Access Class