名称 ID 标签 描述 类型 访问 分类
Pulse_width_value 400E 脉冲宽度 Pulse Width 读/写 无符号 512
Low_flow_cutoff 400C 小流量切除 Lo flo cutoff-Adjustable from 1 to 10% of the setting range. Below set value, output is driven to the zero flow rate signal level. Display is latched to zero. 读/写 枚举 64
Flow_tube_size 400D Tube size Flow tube size- Nominal inside diameter of the pipe adjacent to the sensor. 读/写 枚举 32
Pulse_output_test 4014 Puls outp test Pulse Output Test Value- Scaled frequency output from 0-1000 Hz, linear with input. 读/写 浮点 4096
preset_value 4015 累加器控制 Totalizer Control Code- Controls the operation of all available totalizers. 读/写 无符号 16
total_count 4000 累加器显示 Totalizer display-Display totalized value. 读/写 无符号 34
flow_gravity 4004 Gravity Specific gravity 读/写 浮点 64
display_select 4005 Disp select Set main display. %: Percent of range. Rate: Flow rate. Total: Totalized value. 读/写 枚举 64
function_set 4006 Func set Select Pulse or DO output. Pulse: Pulse output. ST out: Digital status output. 读/写 枚举 32
ex_value 4012 EX value EX value: Unique detector factor.Ex factor is stamped on the name plate. 读/写 浮点 32