Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
dTemperatureLowerSensorLimit | 4064 | Temp LRL | Valor límite inferior del sensor: Define el valor mínimo utilizable para el valor de rango inferior. | R | Float | 8 |
dTemperatureMinimumSpan | 4065 | Minimum Span | Valor de span mínimo: Define la menor diferencia permitida entre el valor de rango superior y el valor de rango inferior. | R | Float | 8 |
dTemperatureFrequency | 4236 | Frequency | Value of variable given in frequency output | R | Float | 514 |
dTemperatureFreqRange | 4237 | Temperature Frequency Limit | Pulse frequency at maximum flow rate | R/W | Float | 512 |
dTemperatureFreqPercent | 4238 | Frequency Percent | Percent of maximum flow rate | R | Float | 34 |
txvar_code | 4158 | R/W | Index | 4096 | ||
dMassFlowFallback | 400F | Mass Flow Fallback | Value assigned to the parameter when it can not be determined correctly due to process or system conditions. | R/W | Float | 32 |
dMassFlowHiAlarmSetpoint | 4011 | Mass Flow Hi Alarm Setpoint | Assigns value, above which an alarm indication is given | R/W | Float | 1024 |
dMassFlowLowAlarmSetpoint | 4010 | Mass Flow Low Alarm Setpoint | Assigns value, below which an alarm indication is given | R/W | Float | 1024 |
dMassFlowLfCutoff | 4012 | Mass Flow Low Flow Cutoff | When the actual flow rate is below this value, the indicated flow rate goes to zero, and any outputs configured for this parameter will go the appropriate value. | R/W | Float | 8 |
Name | ID | Label | Description | Type | Access | Class |