Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
xmtr_specific_status_4 | 0FB9 | Status group 5 | Field Device Specific Status Byte 5- Data that has Field Device status information relating to: failures / warnings / status of process's. | R | BitEnum | 2051 |
xmtr_specific_status_5 | 0FBA | Status group 6 | Field Device Specific Status Byte 6- Data that has Field Device status information relating to: failures / warnings / status of process's. | R | BitEnum | 2051 |
transmitter_variable_code_1 | 0FA0 | Index into Dynamic Variables Array- Is the first an array of addresses, whose value is identified by the Field Device Variable Code | R/W | Index | 4096 | |
transmitter_variable_code_2 | 0FA2 | Index into Dynamic Variables Array- Is the second of an array of addresses, whose value identified by the Field Device Variable Code | R/W | Index | 4096 | |
transmitter_variable_code_3 | 0FA3 | Index into Dynamic Variables Array- Is the third of an array of addresses, whose value identified by the Field Device Variable Code | R/W | Index | 4096 | |
transmitter_variable_code_4 | 0FA4 | Index into Dynamic Variables Array- Is the fourth of an array of addresses, whose value identified by the Field Device Variable Code | R/W | Index | 4096 | |
flow_alarm_select | 1F83 | AO Alrm typ | Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. | R/W | Enum | 64 |
flow_analog_value | 1F7D | AO1 | Analog Output Value- Value that tracks the Digital Value representation, under normal operating modes | R/W | Float | 66 |
flow_damping_value | 1F87 | PV Damp | Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. | R/W | Float | 32 |
flow_lower_range_value | 1F86 | PV LRV | Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 32 |
flow_lower_sensor_limit | 1F80 | PV LSL | Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. | R/W | Float | 8 |
flow_minimum_span | 1F81 | PV Min span | Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. | R/W | Float | 32 |
flow_percent_range | 1F7E | PV % rnge | Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. | R/W | Float | 34 |
flow_range_units | 1F88 | PV rnge unit | Range Unit- Engineering unit to be displayed with the Upper Range Value and Lower Range Value | R/W | Enum | 32 |
flow_sensor_serial_number | 1F82 | PV Snsr s/n | Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. | R/W | Unsigned | 2048 |
flow_units | 1F7B | PV unit | Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit | R/W | Enum | 32 |
flow_upper_range_value | 1F85 | PV URV | Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 32 |
flow_upper_sensor_limit | 1F7F | PV USL | Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. | R/W | Float | 8 |
flow_value | 1F7C | PV | Field Device Variable Value- Digital value that changes magnitude with respect to time with no user intervention | R/W | Float | 34 |
pulse_width_value | 1F50 | Puls width | Pulse Width- Width of the frequency output pulse on frequency output number 'X'. | R/W | Integer | 512 |
units_code | 07E9 | R/W | Enum | 4096 | ||
transfer_function | 1F84 | Xfer fnctn | Transfer Function- Defines the transformation function that will be applied from the Field Device Variable to the Analog Output, and Percent Range. The Transfer Function does not affect the Digital Value representation. | R | Enum | 64 |
Name | ID | Label | Description | Type | Access | Class |