Variable Name: positioner_fail_action
Variable ID: 0x4003
Variable Label: Positioner Fail Action
Variable Help: Defines what action takes place when there is a loss of supply pressure, if a fatal PCB error occurs, or if the controller software discovers a fatal device failure. Set Positioner Fail Action as follows: ·Double-acting actuator: select Close ·Single-acting actuator: set in spring direction (Close or Open).
Variable Handling: R/W
Variable Class: Device
Variable Size: 1
Variable DataType: Enum
Variable Enum Value | Variable Enum Text |
---|---|
0x0001 | Close |
0x0002 | Open |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
209 | 4C04 | read_positioner_fail_action |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
210 | 4C05 | write_positioner_fail_action |