Loading…

Variable Name: positioner_fail_action

Variable ID: 0x4003

Variable Label: Positioner Fail Action

Variable Help: Defines what action takes place when there is a loss of supply pressure, if a fatal PCB error occurs, or if the controller software discovers a fatal device failure. Set Positioner Fail Action as follows: ·Double-acting actuator: select Close ·Single-acting actuator: set in spring direction (Close or Open).

Variable Handling: R/W

Variable Class: Device

Variable Size: 1

Variable DataType: Enum

Variable Enum Value Variable Enum Text
0x0001 Close
0x0002 Open

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
209 4C04 read_positioner_fail_action

Variable Write Command List

Command Number Command ID Command Name
210 4C05 write_positioner_fail_action