Loading…

Variable Name: error_code

Variable ID: 0x41E6

Variable Label:

Variable Help:

Variable Handling: R/W

Variable Class: Local

Variable Size: 1

Variable DataType: Enum

Variable Enum Value Variable Enum Text
0x0001 Mass Flow Mass flow rate > 1.3x nominal flow. (Light)
0x0002 Zero Error Flow rate at zero adjust too high. (Light)
0x0003 Totaliser Overflow Mass totaliser. (Light)
0x0004 Not Used
0x0005 Temperature Outside operating range. (Light)
0x0006 Sensor A Voltage signal too low. (Severe)
0x0007 Sensor B Voltage signal too low. (Severe)
0x0008 Ratio A/B Sensor signals too different. (Severe)
0x0009 DC A Sensor A has a large DC offset. (Severe)
0x000A DC B Sensor B has a large DC offset. (Severe)
0x000B Not Used
0x000C Sampling PLL out of range. (Severe)
0x000D Not Used
0x000E ROM Defaults EEPROM checksum error. (Severe)
0x000F Not Used
0x0010 EEPROM Unable to save data. (Fatal)
0x0011 NVRAM Checksum error Previous data lost. (Severe)
0x0012 NVRAM Cycles NVRAM used up. (Light)
0x0013 Power Fail Main supply has been switched off. (Light)
0x0014 Watchdog System error or power supply drop-off. (Severe)
0x0015 Not Used
0x0016 Temperature Custody Op. temp. has drifted too much. (Light)
0x0017 Strain Strain out of operating range. (Fatal)
0x0018 Current Outp. I1 Sat. Change output range. (Output)
0x0019 Freqency Outp. P Sat. Change output range. (Output)
0x001A Process Alarm Limit check exceeded. (Output)
0x001B Current Outp. I2 Sat. Change output range. (Output)
0x001C Current Outp. I3 Sat. Change output range. (Output)
0x001D Communication Error (Severe)
0x001E System Error Front end / back end. (Severe)

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

None

Variable Write Command List

None