Loading…

Variable Name: PV_Alarm

Variable ID: 0x4006

Variable Label: Alarm Config

Variable Help: Select the alarm type. Issued when output exceeds URV or LRV. Will never be issued if the output is Type2. Manual alarm is reset when the Write Alarm, Command 145, is sent.

Variable Handling: R/W

Variable Class:

Variable Size: 1

Variable DataType: Enum

Variable Enum Value Variable Enum Text
0x0000 High and Auto
0x0001 Low and Auto
0x0002 High and Manual
0x0003 Low and Manual
0x0004 No Alarm

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
142 4044 Read_Calc_Method_And_Alarm_Mode
15 00B7 read_pv_output_info

Variable Write Command List

Command Number Command ID Command Name
145 4047 Write_Alarm_Mode