Loading…
Loading…
Variable Name: PV_Alarm
Variable ID: 0x4006
Variable Label: Alarm Config
Variable Help: Select the alarm type. Issued when output exceeds URV or LRV. Will never be issued if the output is Type2. Manual alarm is reset when the Write Alarm, Command 145, is sent.
Variable Handling: R/W
Variable Class:
Variable Size: 1
Variable DataType: Enum
Variable Enum Value | Variable Enum Text |
---|---|
0x0000 | High and Auto |
0x0001 | Low and Auto |
0x0002 | High and Manual |
0x0003 | Low and Manual |
0x0004 | No Alarm |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
142 | 4044 | Read_Calc_Method_And_Alarm_Mode |
15 | 00B7 | read_pv_output_info |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
145 | 4047 | Write_Alarm_Mode |