Variable Name: nBeta
Variable ID: 0x4026
Variable Label: Beta
Variable Help: Nonlinear gain factor. When beta is 0, the proportional gain is linear, otherwise the gain P is a function of error. The larger the beta, the smaller the gain for small error. Typical beta value is 7 or 8. Beta is ranging from -9 to +9.
Variable Handling: R/W
Variable Class: Dynamic | Correction
Variable Size: 2
Variable DataType: Integer
Variable Display Format: |en|d
Variable Edit Format: |en|d
Variable Unit:
Variable Max: 9
Variable Min: 0
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
216 | 4230 | cmdReadPidData |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
173 | 4219 | cmdWritePidData |