Variable Name: fPosBand
Variable ID: 0x404F
Variable Label: pos error band
Variable Help: Value corresponding to the maximun error (in % opening ) between the setpoint and the valve position allowed, before setting a status flag or putting the valve in fail safe mode regards the selection of associated variables Time 1 and Time 2. Value must be between 0.5% and 100.0% .
Variable Handling: R/W
Variable Class: Correction
Variable Size: 4
Variable DataType: Float
Variable Display Format: |en|.1f
Variable Edit Format: |en|5.1f
Variable Unit:
Variable Max: 100
Variable Min: 0.5
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
212 | 40B2 | read_Error_Limit |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
175 | 40B1 | write_Error_Limit |