Variable Name: fPosBand

Variable ID: 0x404F

Variable Label: pos error band

Variable Help: Value corresponding to the maximun error (in % opening ) between the setpoint and the valve position allowed, before setting a status flag or putting the valve in fail safe mode regards the selection of associated variables Time 1 and Time 2. Value must be between 0.5% and 100.0% .

Variable Handling: R/W

Variable Class: Correction

Variable Size: 4

Variable DataType: Float

Variable Display Format: |en|.1f

Variable Edit Format: |en|5.1f

Variable Unit:

Variable Max: 100

Variable Min: 0.5

Variable Read Command List

Command Number Command ID Command Name
212 40B2 read_Error_Limit

Variable Write Command List

Command Number Command ID Command Name
175 40B1 write_Error_Limit