Variable Name: PRES_AlertScaledVariableBehaviour_1
Variable ID: 0x40CD
Variable Label: Diagnostic behavior
Variable Help: Select event behavior 'Logbook entry only': no digital or analog transmission of the message 'Warning': Current output unchanged. Message is output digitally (default). 'Alarm': Current output assumes the set alarm current. Regardless of the setting, the message appears on the display. If the permissible conditions are reached again, the warning is no longer available in the instrument.
Variable Handling: R/W
Variable Class: Device
Variable Size: 2
Variable DataType: Enum
Variable Enum Value | Variable Enum Text |
---|---|
0x8213 | Alarm |
0x8211 | Warning |
0x00B9 | Logbook entry only |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
173 | 4324 | read_index_parameter_173 |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
178 | 4322 | write_index_parameter_178 |