Variable Name: var_ds_fCurrentUpperLimit
Variable ID: 0x4045
Variable Label: Current Upper Limit
Variable Help: Current Upper Limit Upper limit of the current range for the 4-20 mA current output. For adjustment purposes or to safely identify an over or under measuring range condition, the current range available for the measurement signal is extended beyond the standard range of 4 mA and 20mA. According to Namur specifications (NE 43), the upper current value must not be higher than 20.5mA. The limits can be set within the range from 20 mA to 20.5 mA.
Variable Handling: R/W
Variable Class: AnalogOut
Variable Size: 4
Variable DataType: Float
Variable Display Format: |en|.2f
Variable Edit Format: |en|.2f
Variable Unit:
Variable Max:
Variable Min:
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
178 | 4214 | cmd_rd_loop_limits |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
179 | 4215 | cmd_wr_loop_limits |