Loading…

Variable Name: device_status

Variable ID: 0x0097

Variable Label: Device status

Variable Help: Field Device Status- Data indicating that the Field Device has detected condition(s) in the Field Device relating to: its hardware / the validity of a variable / its operating status / an internal process

Variable Handling: R/W

Variable Class: Dynamic | Diagnostic | HART

Variable Size: 1

Variable DataType: BitEnum

Variable Enum Value Variable Enum Text
0x0001 Process applied to the primary variable is outside the operating limits of the field device
0x0002 Process applied to the non-primary variable is outside the operating limits of the field device
0x0004 Analog output 1 and its digital representation are outside the operating range limits, and not responding to input
0x0008 Analog output 1 and its digital representation are in fixed mode, and not responsive to input changes
0x0010 Field device has more status available
0x0020 A reset or self test of the field device has occurred, or power has been removed and reapplied
0x0040 A modification has been made to the configuration of the field device
0x0080 Field device has malfunctioned due to a hardware error or failure

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
128 40D1 read_revision
130 40D3 read_pv_sensor_configuration
134 40D7 read_conc_configuration
138 40DB read_writeProtection
140 40DD read_temp_sensor_info
150 40E4 read_TCCurve_part1
151 40E5 read_TCCurve_part2
154 40E8 read_pollAddrandBurstStatus
155 40E9 read_ConcCurve_part1
156 40EA read_ConcCurve_part2
170 40EF read_pv_tempSlope_offset
174 40F3 command_read_stable_PV_1_point_cal
194 40F6 read_cal_mode_status
198 40FA read_cal_progress
213 40FB read_DiagnosisMasking
215 40FF read_DiagnosisSimulation
217 4105 read_PowerOnCounterAndWorkingTimes
227 4106 read_longTag
0 00AE read_unique_identifier
1 00AF read_pv
2 00B0 read_pv_current_and_percent_range
3 00B1 read_dynamic_variables_and_pv_current
12 00B4 read_message
13 00B5 read_tag_descriptor_date
14 00B6 read_pv_sensor_info
15 00B7 read_pv_output_info
16 00B8 read_final_assembly_number
48 0FCE read_additional_transmitter_status

Variable Write Command List

None