Method Name: ejx_method_modify_engr_unit
Method ID: 0x415E
Method Label: Modify Engr Unit
Method Help: Modify engineering unit- Modifies the engineering unit or sets a customized engineering unit. Enter a series of up to eight alphanumeric characters, spaces, or slashes (only first six characters are shown on LCD). Note that if you already select the unit at 'Set Engineering Unit,' the unit appears as a default. Then re-enter the unit but enter a space instead of a character to display the character in lowercase on LCD. For example, in order to show 'aBCd' on LCD, enter 'ABCD' first, then enter '_BC_'.
- {
- char status[3];
- { _set_all_resp_code(0); _set_device_status(0xFF,0); _set_xmtr_device_status(0xFF,0); _set_xmtr_all_resp_code(0); };
- send_command( 154 );
- _get_dev_var_value(("|en|Enter Engr Unit:"),0,16517);
- _vassign(16518,16517);
- _get_dev_var_value(("|en|Enter a space for the character to display it in lowercase:"),0,16518);