Loading…
Loading…
方法名称: alarm_lower_value
方法ID: 0x4063
方法标签: Low alarm
方法描述: Low limit of the flow rate, at which an alarm is generated, can be set as % value of the span flow rate of the set maximum range. Low alarm values for flow rate can be set within the range of -10% to 110% (percentage to Range 1) in increments of 0.1%.
- {
- long ids[2];
- int alarm_lower_value10;
- float alarm_lower_value11;
- int alarm_lower_value20;
- float alarm_lower_value21;
- char status[3];
- send(135,status);
- do {
- alarm_lower_value10 = _ivar_value(resolve_record_ref(16598,16455));
- alarm_lower_value10 = (alarm_lower_value10 & 0xff00) / 0x0100 | (alarm_lower_value10 & 0x00ff) * 0x0100;
- alarm_lower_value21 = alarm_lower_value11 = (alarm_lower_value10 >> 8 & 0x00ff | alarm_lower_value10 << 8 & 0xff00) / 10.0;
- if (alarm_lower_value11 > 3276)
- {
- alarm_lower_value10 = alarm_lower_value10 - 0x0100;
- alarm_lower_value10 = alarm_lower_value10 ^ 0xffff;
- alarm_lower_value21 = alarm_lower_value11 = -(alarm_lower_value10 >> 8 & 0x00ff | alarm_lower_value10 << 8 & 0xff00) / 10.0;
- }
- _get_local_var_value(literal_string(509),ids,literal_string(510));
- alarm_lower_value20 = alarm_lower_value21 * 10;