Name | ID | Label | Description | Type | Source |
---|---|---|---|---|---|
zero_device_status_method | 401E | Zero device status | Set device status flags off | msrc_UNKNOWN | Details |
sensor_temperature_correction | 403B | Sensor tempr cal | Send reference meter temperature value to the sensor temperature | msrc_UNKNOWN | Details |
housing_temperature_correction | 403C | Housing tempr cal | Send reference meter temperature value to the housing temperature | msrc_UNKNOWN | Details |
pv_zero_calibr | 401F | PV Zero calibr. | Pressure value zero calibration. Set correct value for pressure zero | msrc_UNKNOWN | Details |
pv_span_calibr | 4020 | PV Span calibr. | Pressure value span calibration. Set correct value for pressure span | msrc_UNKNOWN | Details |
loop_test | 1002 | Loop test | Loop test- Allows the User to manually manipulate the Analog Output to a selected constant output value | msrc_UNKNOWN | Details |
leave_fixed_current_mode | 1003 | Leaving fixed crnt mode | Leaving Fixed Current Mode- Takes the Analog Output out of a mode where the output was a constant value, and returns the output to a mode where the output tracks the input | msrc_UNKNOWN | Details |
return_to_normal | 1016 | Aborting return to normal | msrc_UNKNOWN | Details | |
applied_rerange | 1007 | Apply values | Applied values- Perform a device rerange by applying the desired Upper Range Value and Lower Range Values to the device input | msrc_UNKNOWN | Details |
dac_trim | 1004 | Loop calibr. | Loop calibration- Allows the calibration of the Analog Output with an external reference at the operating endpoints of the Analog Output. | msrc_UNKNOWN | Details |
Name | ID | Label | Description | Type | Source |