Name | ID | Label | Description | Type | Source |
---|---|---|---|---|---|
Refresh_History_table | 40EF | View History | Displays current status and run time as well as a history of most recent faults and warnings. For each event, the run time when the event occurred and the duration of the event are shown. The run time is the time since power up or a history reset. The table of history events displays the most recent event at the top with successively preceding events in descending order. | msrc_UNKNOWN | Details |
HistReset_method | 40DB | Reset History | Clears entries in Status History and resets the run time to zero. | msrc_UNKNOWN | Details |
TempReset_method | 40D9 | Reset Temperatures | Reset the maximum and minimum temperatures measured in the electronics compartment to the present temperature. | msrc_UNKNOWN | Details |
user_dry_point_method | 40CF | Set Dry Point | Sets sensor value for Dry Hanging Displacer | msrc_UNKNOWN | Details |
user_low_calpt_method | 40D0 | Set Low Calib Pts | Sets sensor value and corresponding process value for low calibration point. | msrc_UNKNOWN | Details |
user_high_calpt_method | 40D1 | Set High Calib Pts | Sets sensor value and corresponding process value for high calibration point. | msrc_UNKNOWN | Details |
fact_dry_point_method | 40D3 | Set Dry Point | Sets sensor value for Dry Hanging Displacer | msrc_UNKNOWN | Details |
fact_low_calpt_method | 40D4 | Set Low Calib Pts | Sets sensor value and corresponding process value for low calibration point. | msrc_UNKNOWN | Details |
fact_high_calpt_method | 40D5 | Set High Calib Pts | Sets sensor value and corresponding process value for high calibration point. | msrc_UNKNOWN | Details |
reset_config_changed | 417E | Reset Config Chgd | Resets the Configuration Changed bit in the Device Status | msrc_UNKNOWN | Details |
transmitter_dac_trim | 1024 | Trim Loop Current | Цифровая-аналоговая регулировка - обеспечивает калибровку выбранного аналогового выхода, по внешнему образцовому прибору крайних рабочих точек аналогового выхода | msrc_UNKNOWN | Details |
transmitter_loop_test | 1023 | Loop Test | Тест петли - позволяет пользователю вручную управлять выбранным аналоговым выходом для установки нужного значения выхода | msrc_UNKNOWN | Details |
applied_rerange | 1007 | Capture Values | Приложенные значения - выполните изменение диапазона устройства, подав необходимые значения верхнего и нижнего пределов диапазона на вход устройства | msrc_UNKNOWN | Details |
return_to_normal | 1016 | Отмена возврата в норм. сост. | msrc_UNKNOWN | Details | |
warning_message | 1017 | Установить ручн. реж. контура | msrc_UNKNOWN | Details | |
leave_fixed_current_mode | 1003 | Выход из режима фикс. тока | Выход из режима фиксированного тока - выводит выбранный аналоговый выход из режима, в котором выход был зафиксирован в постоянное значение, и переводит выход в режим, в котором он соотвествует входным данным | msrc_UNKNOWN | Details |
Name | ID | Label | Description | Type | Source |