Name | ID | Label | Description | Type | Source |
---|---|---|---|---|---|
patch_pv | 40C9 | Checking if current is shutdown... | msrc_UNKNOWN | Details | |
patch_fI | 421E | Checking PV code... | msrc_UNKNOWN | Details | |
hardware_test | 4209 | Hardware | Testing of the BM 70 A/P /700/702 hardware can be initiated with this function when the device is operating. When an error is established, corresponding error/status bit is set. This hardware test is carried out automatically every time the BM 70 A/P /700/702 is started up. During the test the current output holds the last measured value. (Fct. 2.1.1) | msrc_UNKNOWN | Details |
test_current | 420A | Test I | Teste de malha- Permite o usuário a manipular manualemnte a saída analógica para o valor de saída de constante selecionada | msrc_UNKNOWN | Details |
leave_fixed_mode | 4211 | msrc_UNKNOWN | Details | ||
Mtest_relay | 420B | SW Output S | In this test, the switching contact (terminals 41 and 42) can be closed or opened. Not for BM 700/702. (Fct. 2.3.1) | msrc_UNKNOWN | Details |
exit_relay_test | 4068 | msrc_UNKNOWN | Details | ||
as_maintenance | 420D | Entry Code | msrc_UNKNOWN | Details | |
as_specialist | 420E | Service Code | Makes Service functionality accessible in case if correct Service Password is entered. Service Password is a 9-keystroke sequence; valid symbols: 0 ([Right] key of the device keypad), 1 ([Enter]) and 2 ([Up]). The Service data comprises basic operating parameters, some of which are required for initial start-up and/or calibration, while others will enable the Service technician to change certain internal values of the signal converter. Note: Incorrectly set Service parameters may cause improper functioning of the BM 70 A. Therefore, only change those parameters whose function you know exactly! The values in the Service menu are generally set by Krohne or possibly by the Service technician, and remain unchanged in operation. The user should not have access to these values. | msrc_UNKNOWN | Details |
autodetect_tank_height | 4201 | Auto tank height | With this function the height of the tank can be determined by the BM 70 A/P /700/702 itself, provided the following conditions are met: · The tank has been completely drained for at least 2 minutes. · The tank bottom has good reflectivity (not suitable for dished and tapered bottoms without reference plate). · The functions "Antenna", "Antenna extension", "Distance piece" and "Stillwell" must previously have been correctly set. · If the tank is taller than 30 m, the approximate tank height must previously be set manually, as otherwise the measuring range will not suffice to locate the bottom. If the measured value seems plausible for the tank height and you wish to store it, select 'Yes' on the prompt. Otherwise select 'No' - this means that the quality of measurement is not adequate (inadequate bottom reflection or too many interferences) for automatic determination of the tank height. In this case you will need to enter the tank height manually. (Fct. 3.5.1) | msrc_UNKNOWN | Details |
record_empty_spectrum | 405B | Empty spectrum | Under this function the empty spectrum is activated or deactivated, or recorded and stored. To record spectrum the following conditions must be held: · Tank must be totally or partially drained. · All moving parts, e.g. agitators, must be switched on. · Tank height, antenna extension, distance piece and still well must be set correctly. When you select "RECORD", the choice is as following: · AVERAGE - Values are averaged. This setting can be used for most applications. · MAX. VALUES - Only maximum values considered when the empty spectrum is recorded. Of advantage in conjunction with "difficult" agitators, for example. If the tank is not completely drained, the empty tank spectrum can nevertheless still be recorded up to a certain range. In this case, select item PARTIAL. · If TOTAL selected, the empty-tank spectrum is recorded over the complete range. · If PARTIAL selected, interrogation is carried out concerning input of the distance value up to which the empty-tank spectrum shall be recorded. · The tank area below the current product level is excluded from the recording of the empty-tank spectrum. · The distance value is entered in the range of 0 m to tank height. · It is recommended to maintain a safe distance of 20 to 30 cm (8" to 12") to the actual distance. After recording of the empty-tank spectrum is started, countdown of measurements from '1000' to '0' is displayed. Procedure is over after approx. 2 Minutes. Recording of the empty spectrum can be aborted. The "old" empty spectrum is retained in this case. (Fct. 3.5.2) | msrc_UNKNOWN | Details |
cancel_esp_evaluation | 4214 | msrc_UNKNOWN | Details | ||
list_errs_warns | 41F3 | View Errors/Warns | msrc_UNKNOWN | Details | |
input_table | 4203 | Input table | · In order to be able to measure volume with the BM 70 A/P /700/702, a conversion table (volume table) needs to be set. · By means of the volume table, various levels are allocated to specific volumes previously calculated or measured out. · In the case of non-symmetrical tanks, e.g. tanks with dished bottom, the accuracy of volume measurement will depend on the number of set "level/volume pairs". The maximum number of pairs (points) that can be set is 50; the volume is linearly determined (interpolated) between 2 points. Minimum number of points is 2. · To delete table set this field to 0. | msrc_UNKNOWN | Details |
delete_table | 405F | Delete table | msrc_UNKNOWN | Details | |
calib_low | 4207 | I Calibrate 1 | To calibrate the current output, enter the actual current reading (check it) under this menu item in the form of a numerical value. Acceptable input range: 2.0 - 20.0 mA Default value: 3.7 mA( SEr. 4.3.1) | msrc_UNKNOWN | Details |
calib_high | 4208 | I Calibrate 2 | To calibrate the current output, enter the actual current reading (check it) under this menu item in the form of a numerical value. Acceptable input range: 2.0 - 20.0 mA Default value: 17.5 mA( SEr. 4.3.2) | msrc_UNKNOWN | Details |
reset | 4080 | Master reset | msrc_UNKNOWN | Details | |
applied_rerange | 1007 | Aplicar valores | Valores aplicados- Realize um reajuste do dispositivo aplicando um valor faixa superior e valores de faixa inferiors para a entrada de dispositivo | msrc_UNKNOWN | Details |
return_to_normal | 1016 | Abortar retorno para normal | msrc_UNKNOWN | Details | |
warning_message | 1017 | Ajustar malha para manual | msrc_UNKNOWN | Details | |
Name | ID | Label | Description | Type | Source |