Name | ID | Label | Description | Type | Source |
---|---|---|---|---|---|
transmitter_loop_test_modified | 4434 | Loop test | Loop test- Allows the User to manually manipulate the Analog Output to a selected constant output value | msrc_UNKNOWN | Details |
transmitter_dac_trim_modified | 4435 | D/A trim | Digital to Analog Trim- Allows the calibration of a selected Analog Output with an external reference at the operating endpoints of the Analog Output | msrc_UNKNOWN | Details |
trim_sensor1_one_point | 40B9 | One point trim | For Lower value of Sensor 1 (Offset) - For parallel shifting of all temperature values at least one reference temperature is needed, for example the actual stable measured temperature. | msrc_UNKNOWN | Details |
trim_sensor1_two_point | 40BA | Two point trim | Two point trim is for Lower value and upper Value of Sensor 1 (Gain and Offset). Two exact temperature reference are needed,for example 0 °C and 100 °C. | msrc_UNKNOWN | Details |
trim_sensor1_reset | 40BB | Reset trim | Reset trim for Sensor 1 is reset to default trim (like after Reset Factory in Menu Extras). The current Sensor trim is deleted. | msrc_UNKNOWN | Details |
trim_sensor2_one_point | 40BC | One point trim | For Lower value of Sensor 2 (Offset) - For parallel shifting of all temperature values at least one reference temperature is needed, for example the actual stable measured temperature. | msrc_UNKNOWN | Details |
trim_sensor2_two_point | 40BD | Two point trim | Two point trim is for Lower value and upper Value of Sensor 1 (Gain and Offset). Two exact temperature reference are needed,for example 0 °C and 100 °C | msrc_UNKNOWN | Details |
trim_sensor2_reset | 40BE | Reset trim | Reset trim for Sensor 1 is reset to default trim (like after Reset Factory in Menu Extras). The current Sensor trim is deleted. | msrc_UNKNOWN | Details |
methodLDH_reset_configChangedFlag | 4437 | Conf Chng Flag-reset | msrc_UNKNOWN | Details | |
GetHealthStatus | 0403 | GetHealthStatus | msrc_UNKNOWN | Details | |
abort_method | 4436 | Abort | msrc_UNKNOWN | Details | |
check_SIL | 4438 | Check SIL | Refresh Check SIL | msrc_UNKNOWN | Details |
lock_unlock_device_ABB | 4439 | Lock/Unlock Device | Bloquear/desbloquear dispositivo: Coloca el dispositivo en posición de bloqueo o desbloqueo. | msrc_UNKNOWN | Details |
device_reset | 443A | Device Reset | Perform a device reset | msrc_UNKNOWN | Details |
reset_to_order | 443B | Reset to Order | Device restarts with settings according to the order | msrc_UNKNOWN | Details |
set_write_protection | 443C | Set/Reset Write Protection | Turn ON/OFF software write protection. | msrc_UNKNOWN | Details |
reset_cofig_flag | 443D | Reset Configuration Flag | After each Configuration or Parameter Change the configuration change Flag signals the Configuration change | msrc_UNKNOWN | Details |
makeItSquawk_modified | 443E | Squawk | Make the Field Device Squawk- This causes the device to visually, audibly or mechanically alert to allow technicans to idendify it | msrc_UNKNOWN | Details |
hart_switch | 443F | Software Switch HART 5 / HART 7 | Perform a change from HART 7 To HART 5 | msrc_UNKNOWN | Details |
Mthd_readSoftwareVersion | 4440 | Software Version | msrc_UNKNOWN | Details | |
Mthd_readHardwareVersion | 4441 | Hardware Version | msrc_UNKNOWN | Details | |
Mthd_readSoftwareVersion_offline | 4442 | Software Version | msrc_UNKNOWN | Details | |
Mthd_readHardwareVersion_offline | 4443 | Hardware Version | msrc_UNKNOWN | Details | |
reset_NAMUR_mapping | 4444 | Reset to default NAMUR Configuration | Reset to default NAMUR Configuration Some Examples (not all diagnostics): Set typical diagnostics to NAMUR State **Maintenance Required** - Redundancy: Sensor 1 not available - Redundancy: Sensor 2 not available - Sensordrift detected - Main diagnostics of Sensor 1 and Sensor 2 * Line Resistance too High * Wire break / Sensor break * Short circuit * Over Sensor Range * Under Sensor Range - .... Set typical diagnostics to NAMUR State **Failure** - Electronics Temperature measurement failure - .... Set typical diagnostics to NAMUR State **Out of Specification** - High Limit: Alarm and warning - Low Limit: Alarm and warning - .... | msrc_UNKNOWN | Details |
read_diag_parameters | 4445 | Click to Update Diagnostics | Click on this button to refresh the UI | msrc_UNKNOWN | Details |
Refresh_Event_Monitor | 4446 | Update | Update Event Monitor Table | msrc_UNKNOWN | Details |
Refresh_Config_Monitor | 4447 | Update | Update Configuration Monitor Table | msrc_UNKNOWN | Details |
method_reset_sensor_supervision_info | 4448 | Reset Sensor Supervising | Reset Min Values and Max Values of Sensor 1 and Sensor 2 | msrc_UNKNOWN | Details |
easy_setup_wizard | 4449 | Easy Setup | This method helps user to configure easy setup parameters | msrc_UNKNOWN | Details |
easy_setup_wizard_offline | 444A | Easy Setup | This method helps user to configure easy setup parameters | msrc_UNKNOWN | Details |
sensor1_config_wizard | 444B | Sensor 1 Configuration | This method helps user to configure sensor 1 parameters | msrc_UNKNOWN | Details |
sensor2_config_wizard | 444C | Sensor 2 Configuration | This method helps user to configure sensor 2 parameters | msrc_UNKNOWN | Details |
sensor1_config_wizard_offline | 444D | Sensor 1 Configuration | This method helps user to configure sensor 1 parameters | msrc_UNKNOWN | Details |
sensor2_config_wizard_offline | 444E | Sensor 2 Configuration | This method helps user to configure sensor 2 parameters | msrc_UNKNOWN | Details |
pv_wizard | 444F | PV | This method helps user to configure PV parameters | msrc_UNKNOWN | Details |
sv_wizard | 4450 | SV | This method helps user to configure SV parameters | msrc_UNKNOWN | Details |
tv_wizard | 4451 | TV | This method helps user to configure TV parameters | msrc_UNKNOWN | Details |
qv_wizard | 4452 | QV | This method helps user to configure QV parameters | msrc_UNKNOWN | Details |
pv_wizard_offline | 4453 | PV | This method helps user to configure PV parameters | msrc_UNKNOWN | Details |
sv_wizard_offline | 4454 | SV | This method helps user to configure SV parameters | msrc_UNKNOWN | Details |
tv_wizard_offline | 4455 | TV | This method helps user to configure TV parameters | msrc_UNKNOWN | Details |
qv_wizard_offline | 4456 | QV | This method helps user to configure QV parameters | msrc_UNKNOWN | Details |
Reset_factory | 4457 | Factory Reset | Device restarts with factory settings applied - Sensor 1: PT100 3 wire - Sensor 2: Off - Process Variable PV: Sensor 1 ... | msrc_UNKNOWN | Details |
MthdSetLin_New | 4458 | Load selected Table | Load the selected table from device | msrc_UNKNOWN | Details |
MthdLinearizeInputWrite_NEW | 4459 | Transfering the fixpoint table to device | Save the new fixpoint table to device | msrc_UNKNOWN | Details |
MthdLinearize_Validate_offlinecurve | 445A | Validate Table | msrc_UNKNOWN | Details | |
warning_message | 1017 | Set loop to manual | msrc_UNKNOWN | Details | |
return_to_normal | 1016 | Aborting return to normal | msrc_UNKNOWN | Details | |
leave_fixed_current_mode | 1003 | Leaving fixed crnt mode | Leaving Fixed Current Mode- Takes the Analog Output out of a mode where the output was a constant value, and returns the output to a mode where the output tracks the input | msrc_UNKNOWN | Details |
lock_unlock_device | 1073 | Lock/Unlock device | Bloquear/desbloquear dispositivo: Coloca el dispositivo en posición de bloqueo o desbloqueo. | msrc_UNKNOWN | Details |
makeItSquawk | 101B | Squawk | Make the Field Device Squawk- This causes the device to visually, audibly or mechanically alert to allow technicans to idendify it | msrc_UNKNOWN | Details |
device_master_reset | 1072 | Device reset | Reinicio del dispositivo: Ordena a la electrónica a que realice un reinicio. Esto equivale a apagar la alimentación del dispositivo de campo y luego volver a encenderla. | msrc_UNKNOWN | Details |
Name | ID | Label | Description | Type | Source |