0 |
Yokogawa |
1 |
YTA70-E/Z |
2 |
Sensor errors |
3 |
Error status byte, indicates errors related to sensors or sensorwires |
4 |
sensor1 |
5 |
sensor2 |
6 |
CJC/electr sens |
7 |
Misc. errors |
8 |
Error status byte, indicates errors related to the device. |
9 |
Downscl EEP xor |
10 |
Downscl RAM xor |
11 |
Downscl ADC |
12 |
Field Device Variable Unit - Engineering unit that the Digital Value, Upper Range Value and Lower Range value will be displayed with. Any unit defined in Table 2. Unit Codes of the Common Tables document will be accepted, but calculation of values between units by the device, are only done when units are degC, degF ,degR or Kelvin |
13 |
Field Device Variable Value - Digital value that dynamicly represents the actual measured primary value of the device, in engineering units. |
14 |
.2f |
15 |
.4f |
16 |
Damping Value - Damping time constant applied to both the Digital Value and Analog Value of the respective output. The Unit of this variable is always in seconds. |
17 |
2.2f |
18 |
5.24f |
19 |
Upper Sensor Limit - Value that defines the absolute upper endpoint (largest magnitude) for the digital value. Temperature - Temperature of the process measured with respect to some reference pressure. |
20 |
Lower Sensor Limit - Value that defines the absolute lower endpoint (smallest magnitude) for the digital value. Temperature - Temperature of the process measured with respect to some reference pressure. |
21 |
Minimum Span value - Indicates the minimum allovable value for the span. The span is the algebraic difference between the Upper and Lower Range Value. |
22 |
Sensor Serial Number - Indicates the sensor's module serial number. |
23 |
7d |
24 |
Sensor 1 Units |
25 |
Sensor 1 Units - For differential or average measurements only |
26 |
Snsr1 |
27 |
Sensor 1 digital value - For differential or average measurements only |
28 |
Sensor 2 Units |
29 |
Sensor 2 Units - For differential or average measurements only |
30 |
Snsr2 |
31 |
Sensor 2 digital value - For differential or average measurements only |
32 |
Electr temp units |
33 |
CJC int temp units |
34 |
CJC ext temp units |
35 |
Electr temperature digital units |
36 |
CJC int temperature digital units |
37 |
CJC ext temperature digital units |
38 |
Electr |
39 |
CJC int |
40 |
CJC ext |
41 |
Electr temperature. |
42 |
CJC int temperature. |
43 |
CJC ext temperature. |
44 |
Sensor type - Indicates the type of the sensor element: millivolt, thermocouple type, resistance thermometer type, ohms. |
45 |
Pt100 IEC 751 |
46 |
Ni100 DIN 43760 |
47 |
T/C Type B IEC 584 |
48 |
T/C Type E IEC 584 |
49 |
T/C Type J IEC 584 |
50 |
T/C Type K IEC 584 |
51 |
T/C Type L DIN 43710 |
52 |
T/C Type N IEC 584 |
53 |
T/C Type R IEC 584 |
54 |
T/C Type S IEC 584 |
55 |
T/C Type T IEC 584 |
56 |
T/C Type U DIN 43710 |
57 |
T/C Type W3 ASTM |
58 |
T/C Type W5 ASTM |
59 |
Measurement type - Indicates the type of measurement: single/differential or average, internal/external or const CJC, external CJC sensor Pt100 or Ni100, 2/3 or 4 wire. |
60 |
RTD/Ohm sgl 2-wire |
61 |
RTD/Ohm sgl 3-wire |
62 |
RTD/Ohm sgl 4-wire |
63 |
RTD/Ohm diff 2-wire |
64 |
RTD/Ohm avg 2-wire |
65 |
TC/V sgl int CJC |
66 |
TC/V sgl ext CJC Pt |
67 |
TC/V sgl ext CJC Ni |
68 |
TC/V sgl const. CJC |
69 |
TC/V diff int CJC |
70 |
TC/V diff ext CJC Pt |
71 |
TC/V diff ext CJC Ni |
72 |
TC/V diff const. CJC |
73 |
TC/V avg int CJC |
74 |
TC/V avg ext CJC Pt |
75 |
TC/V avg ext CJC Ni |
76 |
TC/V avg const. CJC |
77 |
Meter option - Defines whether there is a meter installed or not and possibly what information the meter will display. |
78 |
LCD |
79 |
system configuration |
80 |
For future use |
81 |
Const. CJC value |
82 |
Constant CJ temperature value, the actual temperature at the junction of the thermocouple wires and the terminals. Units of PV |
83 |
RTD factor |
84 |
Multiplication factor for 100 Ohm RTD, reciprocal value, e.g. X=2 for Pt50, X=0.1 for Pt1000 |
85 |
Abs. max. value |
86 |
Absolute maximum value on individual sensors for differential measurements in units of PV |
87 |
Cable resistance config |
88 |
Cable resistance configuration - Configures the cable resistance value |
89 |
Sensor1 |
90 |
ext CJC sensor |
91 |
Cable resistance value |
92 |
Cable resistance value in Ohms. If RTD/Ohm 3 or 4 wire is selected, sensor 1 is the expected max value for the total cable resistance in 2 wires, otherwise it is the actual total cable resistance. |
93 |
Error detection |
94 |
Configures the sensor error detection |
95 |
No test performed |
96 |
broken sensor |
97 |
shorted sensor |
98 |
broken and shorted |
99 |
Sh sens |
100 |
Output current value for shorted sensor, units of mA |
101 |
Br sens |
102 |
Output current value for broken sensor, units of mA |
103 |
Write protect control code |
104 |
Enables, disables write protection, or sets new password |
105 |
Enable write protected |
106 |
Disable write protected |
107 |
Set new password |
108 |
Enter password |
109 |
Password for controlling write protection. 8 byte ASCII. No password will be entered as '********' |
110 |
New password |
111 |
New password for controlling write protection. 8 byte ASCII. No password will be entered as '********' |
112 |
Serial Number |
113 |
9 digit production line serial number, consisting of yybbbrrrr, where <yy> is the year of production, <bbb> is the batch number and <rrrr> is a running number for this batch. Expanded from device id |
114 |
09u |
115 |
PV classification |
116 |
Sensor 1 classification |
117 |
Sensor2 classification |
118 |
Electr classification |
119 |
CJC int classification |
120 |
CJC ext classification |
121 |
PV data qual |
122 |
Sensor 1 data qual. |
123 |
Sensor 2 data qual |
124 |
Electr data qual |
125 |
CJC int data qual |
126 |
CJC ext data qual |
127 |
PV lim status |
128 |
Sensor 1 lim status |
129 |
Sensor2 lim status |
130 |
Electr lim status |
131 |
CJC int lim status |
132 |
CJC ext lim status |
133 |
PV family status |
134 |
Sensor 1 family status |
135 |
Sensor2 family status |
136 |
Electr family status |
137 |
CJC int family status |
138 |
CJC ext family status |
139 |
PV device family |
140 |
Sensor 1 device family |
141 |
Sensor2 device family |
142 |
Electr device family |
143 |
CJC int device family |
144 |
CJC ext device family |
145 |
Collection of variable for Temperature Transmitter |
146 |
Collection of variable for sensor 1 temperature |
147 |
Collection of variable for sensor 2 temperature |
148 |
Electr/CJC temp |
149 |
Collection of variable for electronics or CJC temperature |
150 |
Primary Variable Temperature |
151 |
constant CJC value too low |
152 |
RTD factor too high |
153 |
constant CJC value too high |
154 |
RTD factor too low |
155 |
Cable resistance value too high |
156 |
shorted sensor value too high |
157 |
shorted sensor value too low |
158 |
broken sensor value too high |
159 |
broken sensor value too low |
160 |
incorrect password |
161 |
write_variables |
162 |
Status |
163 |
Calibration |
164 |
Write protection |
165 |
Cable resistance |
166 |
Sensors |
167 |
Process sensor |
168 |
Sensor setup |
169 |
Sensor info |
170 |
Signal condition |
171 |
Sens error values |
172 |
Broken sensor |
173 |
Shorted sensor |
174 |
Revision #'s |
175 |
Review |
176 |
Output info |
177 |
Input info |
178 |
Before polling |
179 |
Loop in manual |
180 |
Back to normal |
181 |
Write protect |
182 |
Write protects the device, if correct password is entered |
183 |
Write enable |
184 |
Write enables the device, if correct password is previously entered |
185 |
Sets a new password for write protection, if correct password is entered |
186 |
Sensor config |
187 |
Configures the sensor, sensor type, measurement type, CJC compensation etc. |
188 |
Enter value |
189 |
Enter new value for cable resistance. If the device setup is RTD/Ohm 3 or 4 wire, cable resistance for sensor 1 is the expected max value for the total cable resistance in 2 wires. Otherwise it is the actual total cable resistance for the selected sensor |
190 |
Measure value |
191 |
Automaticly measures the cable resistance. If the device setup is RTD/Ohm 3 or 4 wire, cable resistance for sensor 1 is the expected max value for the total cable resistance in 2 wires. Otherwise it is the actual total cable resistance for the selected sensor |
192 |
restoring configuration |
193 |
NAMUR down |
194 |
Enables broken sensor error detection, and sets the error output value to 3.5 mA acc. to NAMUR NE43 |
195 |
NAMUR up |
196 |
Enables broken sensor error detection, and sets the error output value to 23 mA acc. to NAMUR NE43 |
197 |
Enables shorted sensor error detection, and sets the error output value to 3.5 mA acc. to NAMUR NE43 |
198 |
Enables shorted sensor error detection, and sets the error output value to 23 mA acc. to NAMUR NE43 |
199 |
Override D/A trim |
200 |
Overrides any previously D/A trimming by restoring factory calibration values |
201 |
Common Tables |
202 |
Interoperable * |
203 |
Universal |
204 |
Common Practice |
205 |
Pressure Universal |
206 |
Pressure Common |
207 |
Menu |
208 |
Rosemount Magflow |
209 |
Rosemount Pressure |
210 |
Moore Products |
211 |
Siemens Pressure |
212 |
P2 Common |
213 |
PV |
214 |
Wireless |
215 |
Munge |
216 |
Analytical Oxygen/Combustion/Methane/CO |
217 |
Flow Totalizer - Rate Indicator |
218 |
Flow Variable Area |
219 |
Flow Coriolis Mass |
220 |
Flow Ultrasonic - Gas |
221 |
Flow Ultrasonic - Liquid |
222 |
Level Ultrasonic |
223 |
Level Radar - Microwave |
224 |
Pressure Absolute |
225 |
Level Capacitance |
226 |
Pressure Differential |
227 |
Level Hydrostatic |
228 |
Level |
229 |
Pressure Absolute/Relative |
230 |
Level Microwave |
231 |
Level Radar |
232 |
Level Density - Nuclear |
233 |
Flow Electromagnetic |
234 |
Flow Vortex |
235 |
Flow Magmeter - Rack Version |
236 |
Flow High Performance Magmeter |
237 |
Flow Mass |
238 |
Flow Ultrasonic |
239 |
Flow Magnetic |
240 |
Flow Magnetic - Custody Transfer |
241 |
Flow 2-wire Magnetic |
242 |
Flow Coriolis Mass - Custody Transfer |
243 |
Flow 2-wire Vortex |
244 |
Flow Thermal |
245 |
Temperature Head Mounted |
246 |
Temperature Compact |
247 |
Temperature DIN Rail Mounted |
248 |
Analytical pH |
249 |
Analytical Conductivity - Conductive |
250 |
Analytical Conductivity - Inductive |
251 |
Temperature Sensor |
252 |
Level Servo |
253 |
Temperature DIN Rail |
254 |
Temperature |
255 |
Analytical ORP |
256 |
Analytical pION |
257 |
Analytical IConc |
258 |
Analytical Electrode Conductivity |
259 |
Analytical Toroidal Conductivity |
260 |
Valve Positioner |
261 |
Valve Controller |
262 |
Pressure |
263 |
Pressure Multivariable |
264 |
Analytical pH/ORP |
265 |
Flow Coriolis |
266 |
Analytical Conductivity |
267 |
Valve Positioner/Pneumatic |
268 |
Valve Actuator - Electrical |
269 |
Temperature Dual Input |
270 |
Valve Actuator |
271 |
Analytical Corrosion |
272 |
Analytical Density - Nuclear |
273 |
Level Continuous Gamma |
274 |
Level Laser Ranging |
275 |
Pressure Safety |
276 |
Flow Vortex/Swirl |
277 |
Flow |
278 |
Analytical 4 Electrode Conductivity |
279 |
Analytical 2 Electrode Conductivity |
280 |
Analytical Troidal Conductivity |
281 |
Analytical pH/ORP/pIon/Ion Conc |
282 |
Analytical Oxygen |
283 |
Pressure P, dP + Multivariable |
284 |
Temperature 2-wire |
285 |
Pressure w/ PID |
286 |
Pressure Saturated Steam |
287 |
Analytical Density - Gamma Ray |
288 |
Level Gamma Ray |
289 |
Analytical Weight - Gamma Ray |
290 |
Level w/ Density - Gamma Ray |
291 |
Analytical Motorized Density |
292 |
Flow Multivariable Mass |
293 |
Temperature Multivariable |
294 |
Specialty HART-to-Analog Signal Conv |
295 |
Flow dP |
296 |
Pressure Low Power |
297 |
Pressure Certified SIL2 |
298 |
Interoperable |
299 |
Analytical Density |
300 |
Valve Positioner/Electropneumatic |
301 |
Flow Magnetic Inductive |
302 |
Analytical |
303 |
Analytical Opacity Monitor |
304 |
Analytical Oxygen/Combustion |
305 |
Analytical 2-wire Conductivity |
306 |
Analytical 2-wire Conductivity w/ pure H20 |
307 |
Analytical 2-wire Conductivity w/ % conc |
308 |
Analytical 2-wire Oxygen/Chlorine/Ozone |
309 |
Analytical 2-wire pH/ORP |
310 |
Analytical 2-wire Contacting/Toroidal |
311 |
Analytical Oxygen - High Temperature |
312 |
Analytical Conductivity w/ % conc |
313 |
Analytical pH/ORP/ISE |
314 |
Analytical Amperometric Analyzer |
315 |
Analytical Dual Input Analyzer |
316 |
Pressure Pressure/Level |
317 |
Analytical Consistency |
318 |
Analytical Microwave-Pulp Consistency |
319 |
Analytical Microwave Consistency |
320 |
Valve Digital Positioner |
321 |
Valve Smart Valve Positioner |
322 |
Temperature Differential |
323 |
Analytical Dissolved Oxygen |
324 |
Analytical pH Controller |
325 |
Analytical Conductivity/Resistivity Controller |
326 |
Analytical Conductivity/Resistivity |
327 |
Level Displacement |
328 |
Temperature w/ PID |
329 |
Valve Universal Positioner |
330 |
Level Radar - Reflex |
331 |
Pressure Gauge |
332 |
Pressure Sealed Gauge |
333 |
Valve Digital Positioner w/ PID |
334 |
Valve Intelligent Positioner |
335 |
Analytical Gas Detector |
336 |
Analytical Infrared Gas Detector |
337 |
Analytical Electrochemical Gas Detector |
338 |
Analytical Measuring Instruments |
339 |
Level Magnostrictive |
340 |
Valve On/Off Valve Controller |
341 |
Level Radar - Pulse |
342 |
Level Continuous Capactive |
343 |
Valve Damper Actuator |
344 |
Valve Electric Damper Actuator |
345 |
Flow Electronic |
346 |
Flow Vortex - Multiparameter Mass |
347 |
Analytical UV Flame Detector |
348 |
Analytical UVIR Flame Detector |
349 |
Analytical IR Flame Detector |
350 |
Analytical Fire Detector |
351 |
Analytical Gas Detector Display Interface |
352 |
Analytical Toxic Gas Detector |
353 |
Analytical Flame Detector |
354 |
Level Nuclear |
355 |
Analytical Microwave |
356 |
Analytical Density - Radiometric |
357 |
Level Radiometric |
358 |
Analytical Gas/Steam |
359 |
Level Nucleonic |
360 |
Analytical Blade Consistency |
361 |
Analytical Rotary Consistency |
362 |
Pressure Absolute/Differential |
363 |
Positioner |
364 |
Analytical Combustible Gas Detector |
365 |
Analytical Point Infrared Gas Detector |
366 |
Analytical Multi-Detector Monitor System |
367 |
Valve Positioner/Electro-hydraulic |
368 |
Valve Monitor |
369 |
Enable on token-passing data link layer only |
370 |
Enable on TDMA data link layer only |
371 |
Enable on both TDMA and token-passing data link layer |
372 |
WirelessHART Device |
373 |
IEEE 802.15.4 2.4GHz DSSS with O-QPSK Modulation |
374 |
Primary |
375 |
Primary Analog Channel |
376 |
Secondary |
377 |
Secondary Analog Channel |
378 |
Tertiary |
379 |
Tertiary Analog Channel |
380 |
Quaternary |
381 |
Quaternary Analog Channel |
382 |
Quinary |
383 |
Quinary Analog Channel |
384 |
Critical Power Failure |
385 |
Lock all |
386 |
Trim not supported |
387 |
Configuration cannot be changed |
388 |
Locked by gateway |
389 |
Analog Input Channel |
390 |
Analog Output Channel |
391 |
Secondary Analog Channel Saturated |
392 |
Tertiary Analog Channel Saturated |
393 |
Quaternary Analog Channel Saturated |
394 |
Quinary Analog Channel Saturated |
395 |
Secondary Analog Channel Fixed |
396 |
Tertiary Analog Channel Fixed |
397 |
Quaternary Analog Channel Fixed |
398 |
Quinary Analog Channel Fixed |
399 |
Simulation active |
400 |
The device is in simulation mode and the level output is not representative of the process. |
401 |
Non-Volatile memory failure |
402 |
The Non-Volatile memory check is invalid or maybe corrupt, or the battery of a battery-backed memory has failed. |
403 |
Volatile memory error |
404 |
The RAM memory check is invalid or maybe corrupt |
405 |
Watchdog reset executed |
406 |
A watchdog reset has been performed |
407 |
Voltage conditions out of range |
408 |
A voltage condition is outside its allowable range |
409 |
Environmental conditions out of range |
410 |
An internal or environmental condition is beyond acceptable limits. |
411 |
Electronic failure |
412 |
A hardware problem not related to the sensor has been detected. |
413 |
Subdevice list changed |
414 |
Duplicate master detected |
415 |
Capacity Denied |
416 |
The device was unable to acquire the communication bandwidth required to support the Burst Messaging specified |
417 |
Bandwidth allocation pending |
418 |
Block transfer pending |
419 |
Continuous |
420 |
The Burst Message is published continuously at (worst case) the Minimum Update Period. |
421 |
Window |
422 |
The Burst Message is triggered when the source value deviates more than the specified trigger value |
423 |
Rising |
424 |
The Burst Message is triggered when source value Rises Above the specified trigger value. |
425 |
Falling |
426 |
The Burst Message is triggered when the source value Falls Below the specified trigger value. |
427 |
On-change |
428 |
The Burst Message is triggered when any value in the message changes. |
429 |
Battery life |
430 |
Percent range |
431 |
Loop current |
432 |
Primary variable |
433 |
Secondary variable |
434 |
Tertiary variable |
435 |
Quaternary variable |
436 |
Off |
437 |
Enable event notification on token-passing data link layer |
438 |
Enable event notification on TDMA data link layer |
439 |
Enable event notification on TDMA and token-passing data link layer |
440 |
Configuration changed event pending |
441 |
Device status event pending |
442 |
More status available event pending |
443 |
Disable |
444 |
Enable single data point trending |
445 |
Enable filtered trending |
446 |
The sample is filtered using a time constant equal to one-third the trend sample period |
447 |
Enable average trending |
448 |
The value obtained by dividing the sum of all samples in the period by the total number of samples |
449 |
Read receive time |
450 |
Write date and time |
451 |
Non-Volatile Clock |
452 |
When set the device contains a battery-backed clock. In this case, the clock does not need to be reset if there is a power failure. |
453 |
Clock Uninitialized |
454 |
The real-time clock has never been set with the date and time. For example, the clock is volatile and power was removed from and restored to the device. |
455 |
Line Power |
456 |
Device is powered via a hardwired connection to a plant power source. |
457 |
Battery Power |
458 |
Device operates solely of its (internal) battery. |
459 |
Recharg.B./Power Sc. |
460 |
Rechargeable battery power or power scavenging. The device has a short-term supply of energy (must be at least one hour) that is continuously being replenished. The device's power is being replenished by harvesting and converting energy from the environment surrounding the device (e.g. solar, vibration, heat). |
461 |
Idle |
462 |
Active search |
463 |
Looking for neighbors. |
464 |
Negotiating |
465 |
Quarantined |
466 |
Operational |
467 |
Suspended |
468 |
Deep sleep |
469 |
Ultra-low power |
470 |
Wireless Signal Found |
471 |
Network packets have been recognized |
472 |
Wireless Signal Identified |
473 |
Wireless Time Synchronized |
474 |
WirelessHart Signal Identified |
475 |
Network Admission Requested |
476 |
Set on transmission of first join request |
477 |
Join Retrying |
478 |
Set after the first join request retry (i.e. when number of join requests > 2). Cleared when device is authenticated or when Active Search started. |
479 |
Join Failed |
480 |
Set on transition from Active Search mode to Deep Sleep mode. Cleared on transition from Deep Sleep to Active Search. |
481 |
Network Security Clearance Granted |
482 |
Network Manager Session Established |
483 |
Network Joined |
484 |
Network Joined. Normal superframe and links obtained. |
485 |
Network Bandwidth Requested |
486 |
Negotiating Network Properties. Gateway session obtained. |
487 |
Join Complete |
488 |
Normal operating mode. |
489 |
None |
490 |
No restrictions |
491 |
SI Only |
492 |
Restricted to SI Unit codes only |
493 |
Open - accept all devices |
494 |
Use Whitelist for access |
495 |
Use Blacklist |
496 |
Use Whitelist and Blacklist |
497 |
Lockdown - disable join links |
498 |
Process automation device |
499 |
Discrete device |
500 |
Hybrid:Process automation+discrete |
501 |
I/O System |
502 |
WirelessHART Process automation device |
503 |
WirelessHART Discrete device |
504 |
WirelessHART Process automation+discrete |
505 |
WirelessHART Gateway |
506 |
WirelessHART Access point |
507 |
WirelessHART Process adapter |
508 |
WirelessHART Discrete adapter |
509 |
WirelessHART enabled handheld/portable maintenance tool |
510 |
Don't attempt to join |
511 |
Join now |
512 |
Attempt to join immediately on powerup or reset |
513 |
US |
514 |
United States of America |
515 |
JP |
516 |
Japan |
517 |
DE |
518 |
Germany |
519 |
FR |
520 |
France |
521 |
ES |
522 |
Spain |
523 |
RU |
524 |
Russian Federation |
525 |
CN |
526 |
People's Republic of China |
527 |
Nominal |
528 |
Device Power Status is nominal |
529 |
Low |
530 |
Device Power Status is low |
531 |
Critically Low |
532 |
Device Power Status is critically low |
533 |
Recharging - Low |
534 |
Recharging - High |
535 |
Secondary Master |
536 |
Primary Master |
537 |
PV Analog Channel Saturated |
538 |
PV Analog Channel Fixed |
539 |
Device Profile |
540 |
|
541 |
Device Diagnostic Status 0 |
542 |
Device Diagnostic Status 1 |
543 |
I/O and Subdevice Status |
544 |
WirelessHART Status |
545 |
Time Set Option |
546 |
Real Time Clock Flags |
547 |
Country |
548 |
Country of intended device installation |
549 |
SI Unit Control |
550 |
Indicates if device should only display SI unit codes |
551 |
Burst Trigger Units |
552 |
Burst Trigger Class |
553 |
Wired HART Enabled |
554 |
Enabled on Wired HART device connection only |
555 |
Wireless HART Enabled |
556 |
Enabled on WirelessHART device connection only |
557 |
Both Wired and WirelessHart Enabled |
558 |
Enabled on both Wired and WirelessHART connections |
559 |
Burst Msg Trigger Mode |
560 |
Event Status |
561 |
Event Notification Control |
562 |
Operate mode Mask |
563 |
Not Defined |
564 |
Power Source |
565 |
Power source of the device |
566 |
Wireless Mode |
567 |
Join Status |
568 |
The current location in the joining sequence of operations. |
569 |
Network Access Mode |
570 |
Join Mode |
571 |
Power Status |
572 |
Power status of the device |
573 |
Master Mode |
574 |
This sets the I/O System's Data Link Layer operation on all channels as either primary or secondary master mode. |
575 |
Trend Units |
576 |
Trend Device Variable Unit Code |
577 |
Trend Classification |
578 |
Trend Device Variable Classification |
579 |
Trend Control |
580 |
Device Status Mask |
581 |
Ext dev status Mask |
582 |
Device Diagnostic Status 0 Mask |
583 |
Device Diagnostic Status 1 Mask |
584 |
Device Diagnostic Status 2 Mask |
585 |
Device Diagnostic Status 3 Mask |
586 |
AO saturated Mask |
587 |
AO fixed Mask |
588 |
Latched Device Status |
589 |
Latched Ext dev status |
590 |
Latched Operate Mode |
591 |
Latched Device Diagnostic Status 0 |
592 |
Latched Device Diagnostic Status 1 |
593 |
Latched Device Diagnostic Status 2 |
594 |
Latched Device Diagnostic Status 3 |
595 |
Latched AO saturated |
596 |
Latched AO fixed |
597 |
Wireless Module Device Type |
598 |
Device type of the Wireless Radio |
599 |
Wireless Module Manufacturer ID |
600 |
Manufacturer of the Wireless Radio contained in this device |
601 |
Subdevice Device Type |
602 |
Device type of the subdevice attached to this system. |
603 |
Subdevice Manufacturer Id |
604 |
Manufacturer of the subdevice attached to this system. |
605 |
8u |
606 |
8.3f |
607 |
.3f |
608 |
WARN: Tx with polling address different from 0 cannot be part of a control loop. |
609 |
Note: Loop may be returned to automatic control when SEND is done |
610 |
Enter correct password (ENTER if none): |
611 |
Device write protected |
612 |
Device NOT write protected |
613 |
Enter new password (ENTER if none): |
614 |
Change password to: %{0} |
615 |
Password changed %{0} |
616 |
Enter sensor type: |
617 |
Enter primary variable units: |
618 |
Enter number of sensor wires: |
619 |
2-wire;3-wire;4-wire;2-wire diff;2-wire average |
620 |
Enter RTD factor: |
621 |
choice >4 |
622 |
Enter measurement type: |
623 |
Single;Differential;Average |
624 |
choice >2 |
625 |
Enter cold junction compensation: |
626 |
Internal sensor;External Pt100;External Ni100;Constant (none) |
627 |
Enter constant CJC temperature: |
628 |
Enter highest possible value on each sensor: |
629 |
Wait, sending configuration... |
630 |
Note: Range values is set to default for the chosen sensor type. |
631 |
Note:
Lower range value set to: %{0} %{2}
Upper range value set to: %{1} %{2} |
632 |
Enter cable resistance for: |
633 |
sensor1;sensor2 |
634 |
Enter cable resistance for sensor1: |
635 |
Enter cable resistance for sensor2: |
636 |
Enter cable resistance for external CJC sensor: |
637 |
Measure cable resistance for: |
638 |
Connect sensor1 to terminals 3 and 6, and short circuit the wires as close as possible to the sensor |
639 |
Connect sensor2 to terminals 3 and 6, and short circuit the wires as close as possible to the sensor |
640 |
Connect external CJC sensor to terminals 3 and 6, and short circuit the wires as close as possible to the sensor |
641 |
error in method! |
642 |
wait... measuring cable resistance |
643 |
Sensor1 cable resistance: %{0} %{1} |
644 |
OK;Original value;Read new value |
645 |
Sensor2 cable resistance: %{0} %{1} |
646 |
External CJC sensor cable resistance: %{0} %{1} |
647 |
error in method |
648 |
Cable resistance too high, set to original value! |
649 |
Due to communication error(s), measurement could not be performed, be aware that the configuration of the device could be currupt!! |
650 |
Due to abortion, measurement could not be performed, be aware that the configuration of the device could be currupt!! |
651 |
Sets broken sensor output value to 3.5 mA, and enables broken sensor detection |
652 |
Sets broken sensor output value to 23 mA, and enables broken sensor detection |
653 |
Sets shorted sensor output value to 3.5 mA, and enables shorted sensor detection |
654 |
Sets shorted sensor output value to 23 mA, and enables shorted sensor detection |
655 |
Override D/A trimming with factory calibration |