0 |
YTA |
1 |
Output Too Low |
2 |
Output Too High |
3 |
Sensor1 Failure |
4 |
Sensor2 Failure |
5 |
S1 Signal Error |
6 |
S2 Signal Error |
7 |
Amb Temp Low |
8 |
Amb Temp High |
9 |
Snsr Bkup Start |
10 |
Illegal PV Map |
11 |
Term Sns Failure |
12 |
EEPROM Failure |
13 |
CPU Failure |
14 |
AD Conv Failure |
15 |
LRV Too Low |
16 |
LRV Too High |
17 |
URV Too Low |
18 |
URV Too High |
19 |
Span Too Small |
20 |
Snsr1 Temp Low |
21 |
Snsr1 Temp High |
22 |
Snsr2 Temp Low |
23 |
Snsr2 Temp High |
24 |
Illegal SV Map |
25 |
Illegal TV Map |
26 |
Illegal 4V Map |
27 |
Fixed Current |
28 |
Snsr Backup Set |
29 |
Wrt Not Protect |
30 |
Last Sum Area |
31 |
WDT over 3 times |
32 |
Dynamic var |
33 |
Sensor 1 Measurement |
34 |
Sensor 2 Measurement |
35 |
Differential Measurement |
36 |
Avg |
37 |
Averaging Measurement |
38 |
Snsr1-Term |
39 |
Sensor 1 Measurement based Terminal temperature |
40 |
Snsr2-Term |
41 |
Sensor 2 Measurement based Terminal temperature |
42 |
Term |
43 |
Terminal Temperature Measurement |
44 |
Sensor 1 Measurement- Measurement of input channel 1. |
45 |
Sensor 2 Measurement- Measurement of input channel 2. |
46 |
Differential Measurement- Measurement derived by computing the difference between two Sensor inputs. |
47 |
Averaging Measurement- Measurement derived by computing the averaging between two Sensor inputs. |
48 |
Sensor1-Term Measurement- Sensor 1 Measurement derived by computing the difference based Terminal temperature. |
49 |
Sensor2-Term Measurement- Sensor 2 Measurement derived by computing the difference based Terminal temperature. |
50 |
Terminal Measurement- Measurement of Terminal temperature. |
51 |
.3f |
52 |
.2f |
53 |
Avg unit |
54 |
Snsr1-Term Unit |
55 |
Snsr2-Term Unit |
56 |
Term Unit |
57 |
8u |
58 |
Term snsr s/n |
59 |
Avg USL |
60 |
Snsr1-Term USL |
61 |
Snsr2-Term USL |
62 |
Term USL |
63 |
Avg LSL |
64 |
Snsr1-Term LSL |
65 |
Snsr2-Term LSL |
66 |
Term LSL |
67 |
Avg min span |
68 |
Snsr1-Term min span |
69 |
Snsr2-Term min span |
70 |
Term min span |
71 |
.0f |
72 |
2.0f |
73 |
Snsr2 damp |
74 |
Avg damp |
75 |
Snsr1-Term damp |
76 |
Snsr2-Term damp |
77 |
Term damp |
78 |
Sensor Variables |
79 |
Which sensor |
80 |
Snsr1 Type |
81 |
Type-B (IEC584) |
82 |
Type-W3 (ASTM E988) |
83 |
Type-W5 (ASTM E988) |
84 |
Type-E (IEC584) |
85 |
Type-J (IEC584) |
86 |
Type-K (IEC584) |
87 |
Type-L (DIN43710) |
88 |
Type-N (IEC584) |
89 |
Type-R (IEC584) |
90 |
Type-S (IEC584) |
91 |
Type-T (IEC584) |
92 |
Type-U (DIN43710) |
93 |
PT100 (IEC751) |
94 |
PT200 (IEC751) |
95 |
PT500 (IEC751) |
96 |
JPt100 (JIS) |
97 |
Cu (SAMA RC21-4) |
98 |
Non-Standard1 |
99 |
Non-Standard2 |
100 |
Non-Connection |
101 |
Snsr2 Type |
102 |
Snsr1 Wire |
103 |
Snsr2 Wire |
104 |
Snsr1 Trim Act |
105 |
Clear |
106 |
Snsr2 Trim Act |
107 |
Snsr1 Lower trim |
108 |
Snsr1 Upper trim |
109 |
Snsr2 Lower trim |
110 |
Snsr2 Upper trim |
111 |
Snsr1 Match Enbl |
112 |
Snsr2 Match Enbl |
113 |
Snsr1 Match R0 |
114 |
Snsr1 Match A |
115 |
.6E |
116 |
14.7E |
117 |
Snsr1 Match B |
118 |
Snsr1 Match C |
119 |
Snsr2 Match R0 |
120 |
Snsr2 Match A |
121 |
Snsr2 Match B |
122 |
Snsr2 Match C |
123 |
EEPROM initialize |
124 |
Completion |
125 |
Not complete |
126 |
Unit mode |
127 |
All unit |
128 |
Japanese unit |
129 |
Com. Protocol |
130 |
HART |
131 |
BRAIN |
132 |
Max snsrs |
133 |
1-input |
134 |
2-input |
135 |
Spcl snsr No1 Inst |
136 |
Spcl snsr No2 Inst |
137 |
Snsr1 Matching |
138 |
Snsr2 Matching |
139 |
S2 4wire |
140 |
Spcl snsr No1 Wire |
141 |
3-4 Wire |
142 |
Spcl snsr No2 Wire |
143 |
Accuracy type |
144 |
Meter installation |
145 |
YTA110 |
146 |
YTA310 |
147 |
YTA320 |
148 |
Prcs var Valid cod |
149 |
PV |
150 |
PV SV |
151 |
PV TV |
152 |
PV SV TV |
153 |
PV 4V |
154 |
PV SV 4V |
155 |
PV TV 4V |
156 |
PV SV TV 4V |
157 |
Snsr trim |
158 |
Both Off |
159 |
S1 Only |
160 |
S2 Only |
161 |
Both On |
162 |
Snsr1 menu ctrl |
163 |
Inhibit |
164 |
Show |
165 |
Snsr2 menu ctrl |
166 |
Sensor Backup- It operates under setting PV to Snsr1 and SV to Snsr2. |
167 |
Snsr Bkup |
168 |
Bkup State |
169 |
Waiting |
170 |
Snsr burnout type |
171 |
User(mA) |
172 |
User(%) |
173 |
Snsr burnout val |
174 |
Diff direction |
175 |
Snsr1-Snsr2 |
176 |
Snsr2-Snsr1 |
177 |
PV damp point |
178 |
2d |
179 |
Process Disp |
180 |
SV |
181 |
TV |
182 |
4V |
183 |
PV,SV |
184 |
PV,SV,TV |
185 |
PV,SV,TV,4V |
186 |
%/mA Disp |
187 |
mA,% |
188 |
Err-No Disp |
189 |
Bar graph |
190 |
Matrix Disp |
191 |
Process |
192 |
Type |
193 |
Wire |
194 |
Process,Type |
195 |
Type,Wire |
196 |
Disp Update |
197 |
Fast |
198 |
Slow |
199 |
Tag extension part |
200 |
Tag Ex |
201 |
Long Tag |
202 |
PV Max |
203 |
PV Min |
204 |
SV Max |
205 |
SV Min |
206 |
TV Max |
207 |
TV Min |
208 |
4V Max |
209 |
4V Min |
210 |
Tm Max |
211 |
Tm Min |
212 |
Error logs |
213 |
Newest |
214 |
Newest Error Log |
215 |
2nd newer |
216 |
2nd newer Error Log |
217 |
3rd newer |
218 |
3rd newer Error Log |
219 |
Oldest |
220 |
Oldest Error Log |
221 |
Which error log |
222 |
Log1-A |
223 |
Log1-B |
224 |
Log2-A |
225 |
Log2-B |
226 |
Log3-A |
227 |
Log3-B |
228 |
Log4-A |
229 |
Log4-B |
230 |
Warn enbl group1 |
231 |
Warn enbl group2 |
232 |
Warn enbl group3 |
233 |
Warn enbl group4 |
234 |
Spcl snsr No1 Info |
235 |
Spcl snsr No2 Info |
236 |
Power Check |
237 |
Operate Time |
238 |
.1f |
239 |
PV unit |
240 |
PV Damp |
241 |
Wrt Enable passwd |
242 |
New password |
243 |
Self Test- Commands the YTA electronics to perform a selftest. Reports any errors that occured. |
244 |
Master Reset- Commands the YTA electronics to reset and perform a selftest. Reports any errors that occured. |
245 |
Variable map |
246 |
Max/Min log Clear |
247 |
Exit log restart |
248 |
Error log Clear |
249 |
Error log view |
250 |
S1 Trim Zero/Gain |
251 |
S2 Trim Zero/Gain |
252 |
D/A Clr to Default |
253 |
Exit clr to Def. |
254 |
Bkup Return Snsr1 |
255 |
Snsr1 Match coefs |
256 |
Snsr2 Match coefs |
257 |
PV max/min log |
258 |
SV max/min log |
259 |
TV max/min log |
260 |
4V max/min log |
261 |
Term max/min log |
262 |
Wrt Enable 10min |
263 |
New Password |
264 |
Variable view |
265 |
Variable setting |
266 |
Unit&Damp |
267 |
PV Unit&Damp |
268 |
SV Unit&Damp |
269 |
TV Unit&Damp |
270 |
4V Unit&Damp |
271 |
Max/Min log |
272 |
Set warning enbl |
273 |
Sensor Trim |
274 |
Snsr 1 inp trim |
275 |
Snsr 2 inp trim |
276 |
AO D/A Trim |
277 |
Error log |
278 |
Power monitoring |
279 |
Snsr 1 config |
280 |
Snsr 2 config |
281 |
Process sensor 1 |
282 |
Snsr 1 Info. |
283 |
Process sensor 2 |
284 |
Snsr 2 Info. |
285 |
Term temp sensor |
286 |
Term temp Limits |
287 |
Snsr Backup |
288 |
Snsr burnout |
289 |
Meter output |
290 |
Display select |
291 |
Sensor 1 Review |
292 |
Sensor 2 Review |
293 |
Term temp Review |
294 |
Out&Meter Review |
295 |
Device Review |
296 |
Upload variables |
297 |
Chng Wrt Protect |
298 |
FMU860 |
299 |
DT |
300 |
DVC |
301 |
FCX |
302 |
AS800 |
303 |
340T |
304 |
340C |
305 |
344 |
306 |
Siemens Micro K |
307 |
SITRANS L |
308 |
SIPAN PH |
309 |
SITRANS P |
310 |
75SMT |
311 |
UNIDELTA |
312 |
8320 |
313 |
SX5100 |
314 |
TSV175 |
315 |
DMU |
316 |
3780 |
317 |
BM70 |
318 |
low |
319 |
high |
320 |
tmp_av |
321 |
Self test in progress please wait |
322 |
Device maybe stuck in selftest. |
323 |
Self Test OK |
324 |
It will reset the master CPU, OK ? |
325 |
Exit;Execute |
326 |
WARN-Loop should be removed from automatic control |
327 |
Master Reset in progress please wait |
328 |
Device maybe stuck in master reset. |
329 |
Master Reset OK |
330 |
PV is %{0}
SV is %{1}
TV is %{2}
4V is %{3}
Press 'OK' to change them. |
331 |
PV is |
332 |
SV is |
333 |
TV is |
334 |
4V is |
335 |
PV is %{0}
SV is %{1}
TV is %{2}
4V is %{3}
Pressing 'OK' will send them. |
336 |
Do you wish to re-send ? |
337 |
yes;no |
338 |
Snsr1 type |
339 |
Snsr2 type |
340 |
Execute OK ? |
341 |
Performing log clear |
342 |
Show the: |
343 |
Log1(newest);Log2;Log3;Log4(oldest);Exit |
344 |
No error |
345 |
Trim activate is not On. You should set it on. |
346 |
Connect Snsr1 Zero ref input in the range:
-10 to +40 mV
(Recommended value:
0 mV) |
347 |
Connect Snsr1 Zero ref input in the range:
-10 to +100 mV
(Recommended value:
0 mV) |
348 |
Connect Snsr1 Zero ref input in the range:
0 to 500 ohm
(Recommended value:
40 ohm) |
349 |
Connect Snsr1 Zero ref input in the range:
0 to 2000 ohm
(Recommended value:
40 ohm) |
350 |
Connect Snsr1 Zero ref input in the special range. |
351 |
Press OK when ref input is stable. |
352 |
Enter Snsr1 Zero trim ref input value (mV): |
353 |
Enter Snsr1 Zero trim ref input value (ohm): |
354 |
Enter Snsr1 Zero trim ref input value (mV or ohm): |
355 |
Connect Snsr1 Gain ref input in the range:
-10 to +40 mV
(Recommended value:
25 mV) |
356 |
Connect Snsr1 Gain ref input in the range:
-10 to +100 mV
(Recommended value:
75 mV) |
357 |
Connect Snsr1 Gain ref input in the range:
0 to 500 ohm
(Recommended value:
330 ohm) |
358 |
Connect Snsr1 Gain ref input in the range:
0 to 2000 ohm
(Recommended value:
1600 ohm) |
359 |
Connect Snsr1 Gain ref input in the special range. |
360 |
Enter Snsr1 Gain trim ref input value (mV): |
361 |
Enter Snsr1 Gain trim ref input value (ohm): |
362 |
Enter Snsr1 Gain trim ref input value (mV or ohm): |
363 |
Trim was not done |
364 |
Performing Sensor trim |
365 |
Connect Snsr2 Zero ref input in the range:
-10 to +40 mV
(Recommended value:
0 mV) |
366 |
Connect Snsr2 Zero ref input in the range:
-10 to +100 mV
(Recommended value:
0 mV) |
367 |
Connect Snsr2 Zero ref input in the range:
0 to 500 ohm
(Recommended value:
40 ohm) |
368 |
Connect Snsr2 Zero ref input in the range:
0 to 2000 ohm
(Recommended value:
40 ohm) |
369 |
Connect Snsr2 Zero ref input in the special range. |
370 |
Enter Snsr2 Zero trim ref input value (mV): |
371 |
Enter Snsr2 Zero trim ref input value (ohm): |
372 |
Enter Snsr2 Zero trim ref input value (mV or ohm): |
373 |
Connect Snsr2 Gain ref input in the range:
-10 to +40 mV
(Recommended value:
25 mV) |
374 |
Connect Snsr2 Gain ref input in the range:
-10 to +100 mV
(Recommended value:
75 mV) |
375 |
Connect Snsr2 Gain ref input in the range:
0 to 500 ohm
(Recommended value:
330 ohm) |
376 |
Connect Snsr2 Gain ref input in the range:
0 to 2000 ohm
(Recommended value:
1600 ohm) |
377 |
Connect Snsr2 Gain ref input in the special range. |
378 |
Enter Snsr2 Gain trim ref input value (mV): |
379 |
Enter Snsr2 Gain trim ref input value (ohm): |
380 |
Enter Snsr2 Gain trim ref input value (mV or ohm): |
381 |
Performing DAC clear to default |
382 |
Pressing 'OK' will return to Sensor1 operation. |
383 |
Choose Coefs type: |
384 |
A B C; alpha delta beta |
385 |
R0=%[15.6f]{R0}
A=%[15.6E]{A}
B=%[15.6E]{B}
C=%[15.6E]{C}
Press 'OK' to change them. |
386 |
R0=%[15.6f]{R0}
alpha=%[15.6E]{alpha}
delta=%[15.6E]{delta}
beta=%[15.6E]{beta}
Press 'OK' to change them. |
387 |
Enter R0 value |
388 |
Enter A value |
389 |
Enter B value |
390 |
Enter C value |
391 |
R0=%[15.6f]{R0}
A=%[15.6E]{A}
B=%[15.6E]{B}
C=%[15.6E]{C}
Pressing 'OK' will send them. |
392 |
R0 |
393 |
Enter alpha value |
394 |
alpha |
395 |
Enter delta value |
396 |
delta |
397 |
Enter beta value |
398 |
beta |
399 |
R0=%[15.6f]{R0}
alpha=%[15.6E]{alpha}
delta=%[15.6E]{delta}
beta=%[15.6E]{beta}
Pressing 'OK' will send them. |
400 |
PV Max log value:
%{0} %{2}
PV Min log value:
%{1} %{2} |
401 |
SV Max log value:
%{0} %{2}
SV Min log value:
%{1} %{2} |
402 |
TV Max log value:
%{0} %{2}
TV Min log value:
%{1} %{2} |
403 |
4V Max log value:
%{0} %{2}
4V Min log value:
%{1} %{2} |
404 |
Term Max log val:
%{0} %{2}
Term Min log val:
%{1} %{2} |
405 |
Enter current password to enable to write for 10 minutes: |
406 |
Do you wish to correct the problem and try again? |
407 |
Released the write protection for 10 minutes. |
408 |
If you wish to release completely, you have to change password to all of spaces. |
409 |
Enter new password to change state of write protect: |
410 |
Re-enter new password within 20 seconds: |
411 |
Changed to new password. |
412 |