0 |
Model |
1 |
Model- References the type of field Device, usually an advertised mode number, that is unique to a single manufacturer. |
2 |
SVI |
3 |
Manufacturer |
4 |
Manufacturer Identification Code- References a specific manufacturer, which is usually a company name, that is responsible for the manufacture of this Field Device. |
5 |
Masoneilan |
6 |
Num resp preams |
7 |
Number of Request Preambles- Number of Preambles required from the Host request by the Field Device. |
8 |
Universal cmd rev |
9 |
Universal Revision- Revision of the Universal Device Description, that the Field Device conforms to. |
10 |
Transmit cmd rev |
11 |
Field Device Revision- Revision of the Field Device Specific Device Description, that the Field Device conforms to. |
12 |
Software rev |
13 |
Field Device Software Revision- This revision corresponds to the software or firmware, that is embedded in the Field Device. |
14 |
Hardware rev |
15 |
Hardware Revision- Revision that corresponds to the electronics hardware of the Field Device. |
16 |
Physicl signl code |
17 |
Physical Signaling Code- The Physical Signaling Code describes the type of Physical Layer that has been implemented in the hardware that is responsible for the HART Communication port. |
18 |
Device flags |
19 |
Field Device Flags- Describes special features of the Field Device that affect the Data Link Layer. |
20 |
Device id |
21 |
Field Device Identification- Uniquely identifies the Field Device when combined with the Manufacturer Identification and Device Type. Therefore, this variable cannot be modified by the Host user. |
22 |
Poll addr |
23 |
Polling Address- Address used by the Host to identify a Field Device, and changeable by the User to control the Multidrop Mode. |
24 |
Tag |
25 |
Tag- Text that is associated with the Field Device installation. This text can be used by the user in any way. A recommended use is as a unique label to a plant that correlates to a Field Device label: a plant drawing, or on a Control System. This variable is also used as a type of data link layer address handle. |
26 |
Message |
27 |
Message- Text that is associated with the Field Device. This text can be used by the user in any way. There is no recommended use. |
28 |
Descriptor |
29 |
Descriptor- Text that is associated with the Field Device.This text can be used by the user in any way. There is no specific recommended use. |
30 |
Date |
31 |
Date- Gregorian calendar date that is stored in the Field Device. This date can be used by the user in any way. There is no specific recommended use. Enter MM/DD/YY |
32 |
Final asmbly num |
33 |
Final Assembly Number- Number that is used for identification purposes, and is associated with the overall Field Device. |
34 |
.3f |
35 |
s |
36 |
8.3f |
37 |
indicate the actual valve position in % with closed 0 % and open 100 % |
38 |
valve pos |
39 |
.1f |
40 |
unit for valve position |
41 |
position unit |
42 |
indicate the actual actuator pressure |
43 |
act pres |
44 |
The act. pressure reported by the SVI can be in psi, bar or kPa |
45 |
pressure unit |
46 |
process variable |
47 |
process var. |
48 |
Unit for the process variable (PV) if the controller mode is selected. |
49 |
PV unit |
50 |
°C |
51 |
°F |
52 |
psi |
53 |
bar |
54 |
mbar |
55 |
kPa |
56 |
CF/min |
57 |
Cubic Feet per minute |
58 |
gal/min |
59 |
l/min |
60 |
m3/h |
61 |
gal/s |
62 |
l/s |
63 |
CF/s |
64 |
Cubic Feet per second |
65 |
m3/s |
66 |
SCF/min |
67 |
standard Cubic Feet per minute |
68 |
CF/h |
69 |
Cubic Feet per hour |
70 |
m3/min |
71 |
gal/h |
72 |
l/h |
73 |
gal |
74 |
l |
75 |
m3 |
76 |
bbl |
77 |
CF |
78 |
Cubic Feet |
79 |
ft |
80 |
m |
81 |
in |
82 |
cm |
83 |
mm |
84 |
min |
85 |
h |
86 |
day |
87 |
gr/s |
88 |
gr/min |
89 |
gr/h |
90 |
kg/s |
91 |
kg/min |
92 |
kg/h |
93 |
kg/day |
94 |
lb/s |
95 |
lb/min |
96 |
lb/h |
97 |
lb/day |
98 |
mV |
99 |
V |
100 |
mA |
101 |
Ohm |
102 |
Hz |
103 |
% |
104 |
controller setpoint |
105 |
remote SP |
106 |
Unit for the controller setpoint (SP) if the controller mode is selected. |
107 |
SP unit |
108 |
Input signal and current loop in mA |
109 |
inp sig |
110 |
6.2f |
111 |
input signal and current loop in percent |
112 |
.2f |
113 |
7d |
114 |
valve pos |
115 |
inpt |
116 |
input signal and current loop in mA |
117 |
analog |
118 |
Hot key menu |
119 |
Offline Config. |
120 |
**NORMAL MODE** |
121 |
**MANUAL MODE** |
122 |
**CONFIG MODE** |
123 |
**CALIBRATE MODE** |
124 |
*DIAGNOSTIC MODE* |
125 |
*FAILSAFE MODE* |
126 |
EXAMINE |
127 |
read identifier |
128 |
positioner config. |
129 |
positioner calibr. |
130 |
diagnostic data |
131 |
read status |
132 |
Clear all the status coming from communication or device errors |
133 |
clear Status |
134 |
positioner PID |
135 |
error limits |
136 |
switches position |
137 |
controller config. |
138 |
controller calibr. |
139 |
controller PID |
140 |
controller param. |
141 |
Limits how fast the output can change. It is expressed as the percent of full output range per second. Value must be between 1%/s and 100.0%/s . |
142 |
Controller output |
143 |
controller SP mode |
144 |
check SVI |
145 |
Manual valve setpoint in %. |
146 |
change pos <-> |
147 |
TO MANUAL MODE |
148 |
MANUAL MODE MENU |
149 |
MANUAL MODE --> |
150 |
NORMAL MODE --> |
151 |
CONFIG MENU |
152 |
|
153 |
Change tag, descriptor, message etc...reported by the SVI. |
154 |
tag |
155 |
Change options in config menu reported by the SVI like valve characterization , button lock , bumpless transfer and other options |
156 |
options |
157 |
Change setup in config menu reported by the SVI like actuator ATO or ATC, direct or reverse instrument, failsafe mode ... |
158 |
setup |
159 |
Access to controller functions.Change setpoint startup, units for process variable (PV) and setpoint (SP) , direct or reverse action, etc... |
160 |
controller |
161 |
CALIBRATE MENU |
162 |
Selects the range sub dialog where the user can enter the upper and lower scale values for the input signal.The values typically are 4 and 20 mA but may be any values between 3.8 and 22 mA(Range signal).This dialog also allows automatic calibration of the position sensor (Stops limit) |
163 |
range |
164 |
The user can set tuning PID coefficients, run auto tune function and set output to I/P |
165 |
tuning |
166 |
To calibrate the signals, you will need a method of setting and changing the input signal.To calibrate the pressure, you will need a method of setting and changing the pressure in the actuator. |
167 |
signals calibrate |
168 |
DIAGNOSTIC MENU |
169 |
Perform valve signature and valve fonctional analysis. |
170 |
perform standard |
171 |
Displays CONTINUOUS DIAGNOSTIC DATA including number of full strokes the valve has made,the number of cycles (direction changes),the time the valve has spent open, the time the valve has been closed and the time the valve has spent throttling near the seat. Displays the DIAGNOSTIC TEST RESULT DATA: after the standard diagnostics are completed the data: friction,spring range, supply pressure and response time open and closed are displays. |
172 |
read diagnostic |
173 |
Reset continuous diagnostic data (stroke count,cycle count, time open, time closed and time near closed ) to 0.The previous data are lost and must be recorded to be used later. |
174 |
reset continuous |
175 |
CONTROLLER |
176 |
Display controller parameters like : setpoint (SP) , process variable (PV) , controller output(OUT-C) and valve position(POS). |
177 |
controller view |
178 |
To change the controller setpoint :remote(R-SP) , local (L-SP)or manual mode (M-SP). |
179 |
mode and setpoint |
180 |
To set tuning PID coefficients for controller mode |
181 |
PID setting |
182 |
Additional parameters for controller mode configuration. |
183 |
Display the alarm message for the controller mode. If ABSOLUTE alarms are selected and the process variable is not between the low and high alarm limit, an alarm message will be displayed. If DEVIATION alarms are set and the difference between the setpoint and the process variable is not between the low and high alarm limit, an alarm message will be displayed. |
184 |
alarms view |
185 |
This function perform a master reset to the device, causing it to go through its startup routine and re-initializing all of its operating parameters from non volatile memory. |
186 |
SVI RESET |
187 |
special return to normal |
188 |
stop procedure |
189 |
return to manual |
190 |
device busy |
191 |
wrong mode |
192 |
command not implemented |
193 |
Manual valve setpoint in %. Value mut be between -5.0% and +105.0% . |
194 |
man pos |
195 |
Manual valve setpoint in mA. |
196 |
set valve pos in mA |
197 |
svi mode can be normal,manual,calibrate, configuration,diagnostic or failsafe. |
198 |
mode |
199 |
1d |
200 |
SVI configuration information and actuator acting. |
201 |
air to close |
202 |
OFF=ATO ON=ATC |
203 |
double acting |
204 |
OFF=single acting (ON=double reserved for future use) |
205 |
reverse instr |
206 |
OFF=direct acting instrument ON=reverse acting instrument option hw reverse must be configured |
207 |
fail high |
208 |
OFF=fail low ON=fail high |
209 |
OFF=controller off ON=controller on |
210 |
bumpless |
211 |
ON=bumpless transfer activation selected returning from manual to normal operating mode is deferred until the input signal matches the current valve position. |
212 |
hw reverse |
213 |
ON=hardware reverse OFF=software reverse |
214 |
Status for low/upper limits and tight shutoff. |
215 |
limits |
216 |
LOWER LIMIT |
217 |
Status for low/upper limits: OFF=not set / ON=set |
218 |
UPPER LIMIT |
219 |
TIGHT_SHUTOFF |
220 |
Status for tight shutoff: OFF=not set / ON=set |
221 |
cam used in the SVI:relationship between flow capacity (Cv) and percentage opening of the valve.Several cams are available:linear, =%50 , =%30 , quick opening coeff 50 , custom. |
222 |
cam |
223 |
cam used in the SVI:relationship between flow capacity (Cv) and percentage opening of the valve.Several cams are available:linear/=%50/=%30/quick opening coeff 50/custom. |
224 |
define lock level for SVI buttons to avoid unintended modifications. |
225 |
buttons |
226 |
Level 3 |
227 |
Define lock level :no restriction |
228 |
Level 2 |
229 |
Define lock level :lock out local calibrate and config menu |
230 |
Level 1 |
231 |
Define lock level :lock out local manual menu |
232 |
Level 0 |
233 |
Define lock level :lock out all buttons |
234 |
This option determines whether the controller setpoint will be in local ,local only , remote or last mode on start up. |
235 |
SP |
236 |
PV_LOCAL_ONLY |
237 |
0=local or remote 1=local only |
238 |
PV_STARTUP_REMOTE |
239 |
0=startup remote 1=startup local |
240 |
PV_STARTUP_LAST |
241 |
0=use flag above 1=start up last mode |
242 |
SP_LOCAL_ONLY |
243 |
SP_STARTUP_REMOTE |
244 |
0=startup remote, 1=startup local |
245 |
SP_STARTUP_LAST |
246 |
0= local or remote, 1=start up last mode |
247 |
LC_DIRECT |
248 |
0=direct, 1=reverse |
249 |
LC_RATIO_CONTROL |
250 |
This option determines whether the controller setpoint will be in local ,local only , remote or last mode on start up. |
251 |
SP startup mode |
252 |
PC mode |
253 |
In ratio control, the setpoint and process variable may be in different engineering units or on different scales. The relationship between the setpoint in process variable units and the raw setpoint is given by: SP(in PV)=ratio gain * SP + ratio bias. |
254 |
Ratio control |
255 |
ratio |
256 |
The controller may be direct action ( its output increases when the process variable is greater than the setpoint) or reverse action (its output decreases then the process variable is greater than the setpoint). |
257 |
controller action |
258 |
action |
259 |
Threshold for tight shutoff: when selected, if the input signal would position the valve below the tight shutoff value, full supply or atmosphere pressure is supplied to the actuator to close the valve with full seating force. Value between -1% and 20%. |
260 |
Tight Shutoff |
261 |
5.2f |
262 |
The SVI allows the user to establish software limit stops.The control functions will NOT allow the valve position to be lower than the lower position limit.However this option DOES NOT PROVIDE MECHANICAL STOPS for the valve.During a electrical or air failure the valve will go to the fail safe position without regard to the software limit stops.The manual position full closed or full open will similary ignore limit stops. |
263 |
Lower Limit |
264 |
The SVI allows the user to establish software limit stops. The control functions will NOT allow the valve position to be above than the upper position limit.However this option DOES NOT PROVIDE MECHANICAL STOPS for the valve.During a electrical or air failure the valve will go to the fail safe position without regard to the software limit stops.The manual position full closed or full open will similary ignore limit stops. |
265 |
Upper Limit |
266 |
Choice of different languages is displayed on the SVI LCD. |
267 |
language |
268 |
English |
269 |
Possibility of different languages display on the SVI LCD |
270 |
French |
271 |
The controller can process the setpoint and the process variable data every 0.15 s to 10.0 s. For fast processes, a rate of 0.2 s would be a reasonable value and for slow processes 2 s would be common. |
272 |
controller rate |
273 |
3.1f |
274 |
When power is applied to the SVI, this parameter determines the setpoint value if the startup mode is local. |
275 |
initial local SP |
276 |
Value corresponding to the maximun error (in % opening ) between the setpoint and the valve position allowed, before setting a status flag or putting the valve in fail safe mode regards the selection of associated variables Time 1 and Time 2. Value must be between 0.5% and 100.0% . |
277 |
pos error band |
278 |
4.2f |
279 |
Value of valve position below which the user considers the valve as being near closed position.Used in continuous diagnostic calculations. Must be between 0 and 20%. |
280 |
valve near closed |
281 |
time before set the flag : valve error position this time must be >= 1 s and below 327 s. |
282 |
time 1 |
283 |
.0f |
284 |
4.0f |
285 |
time before to put the valve in failsafe mode this time must be >= 2 s and below 327 s and in any case greater than Time 1 However to inhibit failsave mode set -1 s. |
286 |
time 2 |
287 |
time before setting the flag : pressure error if the pressure is not correct. |
288 |
press fault limit |
289 |
Low input signal for valve closed (direct acting) or low input signal for valve open (reverse acting). Must be between 3.5 mA and 14 mA. |
290 |
low signal |
291 |
high input signal for valve open (direct acting) or high input signal for valve open (reverse acting). Must be between 8 mA et 22 mA. |
292 |
high signal |
293 |
low pressure value for scaling the pressure sensor. |
294 |
low press value |
295 |
high pressure value for scaling the pressure sensor. Must be between 18 and 150 psi or 1.24 and 10.4 bar or 124 and 1040 kpa. |
296 |
high press value |
297 |
5.1f |
298 |
4.1f |
299 |
9.1f |
300 |
units for input signal. |
301 |
Input sig Unit |
302 |
Engineering value for the process variable that corresponds to 4.0 mA and 20.0 mA. The SVI use these values to convert the auxiliary input to engineering units. |
303 |
low PV value |
304 |
8.2f |
305 |
upper PV value |
306 |
Engineering value for the process variable that corresponds to 4.0 mA. The SVI use these values to convert the auxiliary input to engineering units. |
307 |
low SP value |
308 |
Engineering value for the process variable that corresponds to 20.0 mA. The SVI use these values to convert the auxiliary input to engineering units. |
309 |
upper SP value |
310 |
Proportional gain P is the ratio of proportional action (part of controller output) to error.Value between 10 and 1000. |
311 |
P |
312 |
4d |
313 |
Integal time or reset time, is the time constant of integral control.Value between 0 and 1000. |
314 |
I |
315 |
Derivative time or rate time is the time constant Typical range is 8 to 16 of derivative control.Value between 0 and 5000. |
316 |
D |
317 |
ms |
318 |
Derivative gain is a parameter of derivative control. Value between 0 and 100. |
319 |
Kd |
320 |
Beta is nonlinear gain factor, ranging from -8 to 9. When beta is 0, the controller gain is linear. Otherwise the gain is a function of error. The larger the beta, the smaller the gain for small error. Typical beta value for a valve position controller is 7 or 8. |
321 |
Beta |
322 |
The setpoint is constrained to be between the low and high limits. Both local and remote setpoints are limited. The limits are entered in the same engineering units as the process variable. SP low limit must be lower than SP upper limit. |
323 |
SP low limit |
324 |
The setpoint is constrained to be between the low and high limits. Both local and remote setpoints are limited. The limits are entered in the same engineering units as the process variable. SP upper limit must be upper than SP low limit. |
325 |
SP upper limit |
326 |
Define the high alarm for the controller mode. Alarm are absolute or deviation. The alarm limits are entered in the same units as the process variable . |
327 |
Low alarm limit |
328 |
Define the high alarm for the controller mode. Alarm are absolute or deviation. The alarm limits are entered in the same units as the process variable . |
329 |
Upper alarm limit |
330 |
%/s |
331 |
Only applies to P or PD control. It is the process controller output at a typical operating steady state. If the controller outputs range from 30 to 50 % at normal operation, the manual reset bias should be set at 40% in order to minimize steady state error. Value between 0 and 90% . |
332 |
Manu. reset bias |
333 |
2d |
334 |
|
335 |
Select |
336 |
SP tracking |
337 |
When the controller is changed from manual mode to local mode, the setpoint is set to equal the current process variable. In that case the process will not be upset by the change from manual to local. |
338 |
Freeze output |
339 |
If the process variable read is not a valid reading, the controller output will not be changed. |
340 |
Derivative mode |
341 |
Determines whether a change in process variable or a change in error (setpoint - process variable) will cause derivative action. OFF=PV ON=error. |
342 |
Alarm type |
343 |
OFF=absolute ON=deviation |
344 |
When the difference between the setpoint and the process variable is less than the dead zone, the controller will take no action to change the output.Must be between 0 and 20%. |
345 |
Dead zone |
346 |
In ratio control, the setpoint and process variable may be in different engineering units or on different scales. The relationship between the setpoint in process variable units and the raw setpoint is given by: SP(in PV unit)=ratio gain * SP + ratio bias. |
347 |
Ratio gain |
348 |
Ratio bias |
349 |
Read the controller mode: manual , local or remote. |
350 |
LCMode |
351 |
Read the current loop controller (LC) mode: manual , local or remote. |
352 |
LC current mode |
353 |
local PV |
354 |
local SP |
355 |
Value for open stop adjustment.This value must be between 80%-100%.For some valves the open position stop exceeds the nominal travel of the valve.By entering a value, the position calibration can be adjusted to nominal travel . |
356 |
open stop adj |
357 |
|
358 |
Proportional gain in %.Common values are 50 for small valves up to 4000 for large valves.Must be between 0 and 5000. |
359 |
Integral time or reset time in 1/10 s. Higher values of I cause less integral action, however a value of 0 gives no integral action .Common values are 10 to 200. Values between 0 and 1000. |
360 |
(1/10s) |
361 |
Derivative time or rate time in milli_seconds.Common values are 10 to 100. Values between 0 and 200. |
362 |
Coefficient added to P when the valve is exhausting and compensates the variation in filling and exhausting speed. Can be positive or negative value range between -3000 to +3000. |
363 |
Padj |
364 |
Nonlinear gain factor.When beta is 0,the proportional gain is linear,otherwise the gain P is a function of error. The larger the beta,the smaller the gain for small error. Typical beta value is 7 or 8.Beta is ranging from -8 to +9. |
365 |
Coefficient to increase the valve response for some applications.A value of 0 gives no Damping and 9 gives maximum damping of valve motion. |
366 |
Damping |
367 |
The response of the valve is different when the valve is nearly closed than when nearly open.This coefficient allows the user to make adjustments to try to equalize the valve response.Normal value is 6 and this value is ranging from 0 to 9. |
368 |
Pos.Comp. |
369 |
When the valve position is within the setpoint +/- the dead zone and, no additional position control is performed. This value is normally 0%.Used to avoid limit cycling for high friction valves.Range 0 to 1%. |
370 |
Dead zone |
371 |
Set constant current on the I/P.(2750 optimal value) to adjust the pneumatic block. |
372 |
Output |
373 |
Total number of valve strokes. |
374 |
total travel |
375 |
strokes |
376 |
Time in hours for valve closed. |
377 |
time closed |
378 |
Time in hours for valve open. |
379 |
time open |
380 |
Time in hours for valve near closed. |
381 |
time near closed |
382 |
Number of cycles (direction changes). |
383 |
nbr cycles |
384 |
Friction.This value is given from the standard diagnostic calculations. |
385 |
friction |
386 |
Low spring value.This value is given from the standard diagnostic calculations. |
387 |
low spring range |
388 |
High spring value.This value is given from the standard diagnostic calculations. |
389 |
upper spring range |
390 |
low pressure value in the valve actuator.This value is given from the standard diagnostic calculations. |
391 |
lower pressure |
392 |
Upper pressure value in the valve actuator.This value is given from the standard diagnostic calculations. |
393 |
upper pressure |
394 |
Fastest time to open the valve on the full stroke .This value is given from the standard diagnostic calculations. |
395 |
strok. time open |
396 |
Fastest time to close the valve on the full stroke. This value is given from the standard diagnostic calculations. |
397 |
strok. time close |
398 |
Status from limit switches. |
399 |
limit switches |
400 |
SWITCH 1 |
401 |
OFF=open ON=closed |
402 |
SWITCH 2 |
403 |
A speed between 1 and 10 must be entered.This determines the speed at which the valve will travel during the pressure vs. position test.A speed of 1 or 2 is appropriate for 1 to 3 inch valves,3 to 4 for 6 to 8 inch valves and higher speeds for larger valves. |
404 |
Speed |
405 |
bFaultCode1 |
406 |
Reports Device Errors |
407 |
Position Error |
408 |
Pressure Error 1 |
409 |
Pressure Error 2 |
410 |
I/P Out Voltage Error |
411 |
Position Sensor Error |
412 |
Pressure Sensor Error |
413 |
Current Sensor Error |
414 |
Reference Voltage Error |
415 |
bFaultCode2 |
416 |
Reports Device Errors |
417 |
Position Limit Change |
418 |
Self Check Failure |
419 |
Hart Error |
420 |
Software Error |
421 |
Reset Occurred |
422 |
Switch to I/P |
423 |
Data Overrun |
424 |
Find Stop limits Failed |
425 |
bFaultCode3 |
426 |
Circuit Temperature Error |
427 |
EEPROM Write Failed |
428 |
Position Sensor Error Latch |
429 |
Pressure Sensor Error Latch |
430 |
Reference Voltage Error Latch |
431 |
Circuit Temperature Error Latch |
432 |
Watchdog Timeout |
433 |
Signal Calibration Failed |
434 |
bFaultCode4 |
435 |
Reserved for future use |
436 |
reserved |
437 |
|
438 |
mA value of the auxillary signal |
439 |
fSig2 |
440 |
A/D value of the auxillary signal |
441 |
nSig2 |
442 |
pts |
443 |
A/D value of the primary signal |
444 |
nSig |
445 |
A/D value of the position sensor. |
446 |
nPos |
447 |
A/D value of the pressure sensor |
448 |
nPres |
449 |
output value of the process controller |
450 |
nOutput |
451 |
current value send on the pneumatic block. |
452 |
I/P |
453 |
Internal SVI temperature in °C. |
454 |
temperature |
455 |
X define signal input in % and Y define position valve in % The mini and maxi values are respectively 0.0% and 100.0% The custom curve must have at least one pair. A coordinate (100.0%,100.0%) indicate the end of the curve. |
456 |
X1 |
457 |
Y1 |
458 |
X2 |
459 |
Y2 |
460 |
X3 |
461 |
Y3 |
462 |
X4 |
463 |
Y4 |
464 |
X5 |
465 |
Y5 |
466 |
X6 |
467 |
Y6 |
468 |
X7 |
469 |
Y7 |
470 |
X8 |
471 |
Y8 |
472 |
X9 |
473 |
Y9 |
474 |
X10 |
475 |
Y10 |
476 |
REMOTE MODE *ALARM* |
477 |
REMOTE MODE |
478 |
LOCAL MODE *ALARM* |
479 |
LOCAL MODE |
480 |
MANUAL MODE *ALARM* |
481 |
MANUAL MODE |
482 |
Low value for primary signal calibration. Must be between 3.5mA and 8.0mA . |
483 |
primary signal |
484 |
high value for primary signal calibration. Must be between 12.0mA and 20.0mA . |
485 |
Low value for pressure sensor calibration. Must be between 0 and 9psi / 0 and 0.6bar / 0 and 60kPa . |
486 |
pressure |
487 |
High value for pressure sensor calibration. Must be between 10 and 120psi / 0.7 and 8.0bar / 70 and 800kPa . |
488 |
Low value for secondary signal calibration. Must be between 3.5mA and 8.0mA . |
489 |
secondary signal |
490 |
high value for secondary signal calibration. Must be between 12.0mA and 20.0mA . |
491 |
FMU860 |
492 |
DT |
493 |
DVC |
494 |
FCX |
495 |
AS800 |
496 |
340T |
497 |
340C |
498 |
344 |
499 |
Siemens Micro K |
500 |
SITRANS L |
501 |
SIPAN PH |
502 |
SITRANS P |
503 |
75SMT |
504 |
UNIDELTA |
505 |
8320 |
506 |
SX5100 |
507 |
TSV175 |
508 |
DMU |
509 |
3780 |
510 |
BM70 |
511 |
8u |
512 |
Procedure aborted TRY AGAIN. |
513 |
Position Error |
514 |
Pressure Error (type 1) |
515 |
Pressure Error (type 2) |
516 |
I/P Out Voltage Error |
517 |
Position Sensor Error |
518 |
Pressure Sensor Error |
519 |
Current Sensor Error |
520 |
Référence Voltage Error |
521 |
Position calibration end points have changed |
522 |
Self Check Failure |
523 |
Hart Error |
524 |
SVI Software Error |
525 |
Reset Occurred |
526 |
Switched to I/P mode |
527 |
Data Overrun |
528 |
Find Stop limits Failed |
529 |
Circuit Temperature Error |
530 |
EEPROM Write Failed |
531 |
Position Sensor Error Latch |
532 |
Pressure Sensor Error Latch |
533 |
Référence Voltage Error Latch |
534 |
Circuit Temperature Error Latch |
535 |
Watchdog Timeout |
536 |
Signal Calibration Failed |
537 |
no fault code |
538 |
PLEASE WAIT... |
539 |
Clear Fault Codes NOT Completed |
540 |
Clear Fault Codes Completed |
541 |
Controller output =
%{0}%/s
|
542 |
Manual setpoint: |
543 |
setpoint;full open;full closed |
544 |
Valve Position : |
545 |
Going to MANUAL MODE prevents the valve from responding to the controller! Are you sure you want to go to MANUAL ? |
546 |
WAIT ... |
547 |
RETURN TO NORMAL MODE ? |
548 |
NO;YES |
549 |
WAIT WORK IN PROGRESS |
550 |
Bumpless is set. Change the current loop to match the corresponding valve position ONLY IF NECESSARY. |
551 |
Pos =%{0} %
current =%{2} mA
loop or %{1} % |
552 |
Press ABORT key to abort the process |
553 |
tag |
554 |
descriptor |
555 |
message |
556 |
final assembly number |
557 |
date |
558 |
polling address |
559 |
Record values ? Press: OK for YES ABORT for NO |
560 |
custom cam used |
561 |
no change;linear;equal(50);equal(30);quick open;custom |
562 |
quick open cam used |
563 |
no change;linear;equal%(50);equal%(30);quick_open;custom |
564 |
equal%(30) cam used |
565 |
equal%(50) cam used |
566 |
no change;linear;equal%(50);equal%(30);quick_open;custom; |
567 |
linear cam used |
568 |
NEW CAM CHARACTERIZATION ? |
569 |
Input your 9 XY pairs of points between ( 0.0%, 0.0%) and (100.0%,100.0%) |
570 |
X[%{i}] |
571 |
Y[%{i}] |
572 |
Invalid segment X%{a} , X%{i}
Slope too low . |
573 |
Invalid segment X%{a} , X %{i}
Slope change too high |
574 |
Invalid segment X%{a} , X %{i}
Slope change too much |
575 |
CHANGE BAD SEGMENT(S) ? |
576 |
YES; NO |
577 |
Limits |
578 |
Lower limit value |
579 |
Upper limit value |
580 |
Tight shut off value |
581 |
Pressure units |
582 |
Display language |
583 |
Buttons:lock level |
584 |
Valve near closed |
585 |
I/P selection is not possible. |
586 |
Double acting selection is not possible. |
587 |
Please see documentation for reverse mode before selecting this mode. |
588 |
Issue a Reset when return to Manual mode to ACTIVATE controller mode. |
589 |
Position error band |
590 |
Time1 |
591 |
Time2 |
592 |
Time 2 must be greater than Time 1. |
593 |
Pressure Time |
594 |
Controller mode not set. |
595 |
setpoint:local only |
596 |
no change;startup local;startup remote;startup last mode;local only |
597 |
setpoint:startup last mode |
598 |
setpoint:startup local |
599 |
setpoint:startup remote |
600 |
action:reverse |
601 |
no change;direct;reverse |
602 |
action:direct |
603 |
PV unit |
604 |
remote SP unit |
605 |
Ratio control is ON. |
606 |
Ratio control: YES |
607 |
no change;NO;YES |
608 |
Ratio control: NO |
609 |
initial local SP %{0} |
610 |
spinit |
611 |
controller rate |
612 |
make your choice: |
613 |
range signals;find stop limits |
614 |
low signal |
615 |
high signal |
616 |
Low and high signals must differ by at least 5mA. |
617 |
supply pressure |
618 |
high PV value |
619 |
low SP value |
620 |
high SP value |
621 |
This command will stroke the valve and should NOT be performed with the process running. |
622 |
Change open stop adjustment ? |
623 |
open stop adjustment |
624 |
WAIT WORK IN PROGRESS |
625 |
Find stop limits
executed
|
626 |
PID coefficients;auto tune;bias |
627 |
P =%{0}%
I =%{1}(1/10s)
D =%{2}ms
Padj =%{3}% |
628 |
Beta =%{4}
Damping =%{5}
Compens. pos.=%{6}
Dead zone =%{7}%
|
629 |
P (%) |
630 |
I (1/10s) |
631 |
D (ms) |
632 |
Padj (%) |
633 |
Beta |
634 |
Damping |
635 |
Compensation |
636 |
Dead zone (%) |
637 |
This procedure strokes the valve and should not be run with the valve in service and the process running. |
638 |
WAIT AUTO TUNE IN PROGRESS |
639 |
Press ABORT key to abort the process |
640 |
AUTO TUNE CORRECTLY EXECUTED |
641 |
The found Bias is not in the required range self-tuning is canceled. Ajust the BIAS. |
642 |
Self-tuning for air fill direction fails. Check supply pressure or pneumatic block. |
643 |
Self-tuning for air exhausting direction fails.Check the pneumatic block. |
644 |
set the I/P value: |
645 |
primary signal;secondary signal;pressure;view signals;reset to factory |
646 |
Enter the low
signal value: |
647 |
Set the input
current to: %[.2f]{0}mA
and press OK |
648 |
Enter the high
signal value: |
649 |
Set the input
current to: %[.2f]{0}mA
and press OK |
650 |
primary signal:
%{0} mA
|
651 |
Enter the low
secondary signal
value: |
652 |
Set the secondary
input current to:
%[.2f]{0}mA
and press OK |
653 |
Enter the high
secondary signal
value: |
654 |
secondary signal:
%{0} mA
|
655 |
Enter the low
pressure signal
value: |
656 |
Set the pressure
to: %[.2f]{0}%{1}
and press OK |
657 |
Enter the high
pressure signal
value: |
658 |
pressure:
%{0} %{1}
|
659 |
primary signal:
%[.2f]{0} mA
secondary signal:
%[.2f]{1} mA
pressure:
%[.2f]{2} %{3} |
660 |
This procedure strokes the valve and should not be run with the valve in service and the process running. |
661 |
Remove software limit stops to be able to perform standard diagnostic |
662 |
Valve Speed |
663 |
WAIT STANDARD DIAGNOSTIC IN PROGRESS |
664 |
STANDARD DIAGNOSTIC EXECUTED |
665 |
Continuous data;Result std diagn |
666 |
Total travel= %{0}strokes
Time closed= %{1}h
Time open= %{2}h |
667 |
Time near closed= %{3}h
Nbre Cycles= %{4} |
668 |
Following values are not meaningful if standard diagnostic has not been run. |
669 |
friction = %{0}%{7}
low spring range= %{1}%{7}
upper spring range= %{2}%{7} |
670 |
lower pressure= %{3}%{7}
upper pressure= %{4}%{7} |
671 |
stroking time to
open: %[.1f]{t1}s
stroking time to
close: %[.1f]{t2}s
|
672 |
After resetting , the current values will be lost. Press ABORT if you need these values. |
673 |
RESET CONTINUOUS DATA CORRECTLY EXECUTED |
674 |
%{6}
PV =%{1} %{4}
R-SP =%{2} %{5}
=%[.1f]{t1} %{4}
OUT-C=%{3} %
POS =%{0} % |
675 |
%{6}
PV =%{1} %{4}
R-SP =%{2} %{5}
OUT-C=%{3} %
POS =%{0} % |
676 |
%{6}
PV =%{1} %{4}
L-SP =%[.1f]{t1} %{4}
OUT-C=%{3} %
POS =%{0} %
R-SP =%[.1f]{t2} %{4} |
677 |
%{6}
PV =%{1} %{2}
M-SP =%{3} %
POS =%{0} %
R-SP =%[.1f]{t2} %{2} |
678 |
make your choice: |
679 |
SP value;SP mode |
680 |
setpoint:Remote SP |
681 |
no change;Remote SP;SP Local;Manual |
682 |
setpoint:Local SP |
683 |
no change;Remote SP;Local SP;Manual |
684 |
no change;Local SP;Manual |
685 |
setpoint:Manual |
686 |
setpoint:Manual |
687 |
Local SP |
688 |
P =%{0}%
I =%{1}(s)
D =%{2}ms
Kd =%{3}
Beta =%{4} |
689 |
Ratio Gain |
690 |
Ratio Bias |
691 |
The Ratio Gain and Bias compute setpoint out of range of process variable. |
692 |
Ratio scaling exceeds capabilities of the SVI. |
693 |
SP Low Limit |
694 |
SP High Limit |
695 |
Set point Low Limit must be less than Hight Limit. |
696 |
Low Alarm Limit |
697 |
High Alarm Limit |
698 |
Output Rate Limit in %/s: |
699 |
a |
700 |
Maximum value
allowed is:
%[4.1f]{fK}%/s
using controller
rate : %{0}s |
701 |
Manual Reset Bias |
702 |
Select |
703 |
ALARM TYPE:
DEVIATION
PV =%{0} %{1}
SP =%[.1f]{t2} %{1}
HIGH ALARM |
704 |
ALARM TYPE:
DEVIATION
PV =%{0} %{1}
SP =%[.1f]{t2} %{1}
LOW ALARM |
705 |
ALARM TYPE:
DEVIATION
PV =%{0} %{1}
SP =%[.1f]{t2} %{1}
NO ALARM |
706 |
ALARM TYPE:
ABSOLUTE
PV =%{0} %{1}
SP =%[.1f]{t1} %{1}
HIGH ALARM |
707 |
ALARM TYPE:
ABSOLUTE
PV =%{0} %{1}
SP =%[.1f]{t1} %{1}
LOW ALARM |
708 |
ALARM TYPE:
ABSOLUTE
PV =%{0} %{1}
SP =%[.1f]{t1} %{1}
NO ALARM |
709 |
A reset may cause the valve to move ! Perform RESET ??? |
710 |
Reset on SVI NOT correctly executed |
711 |
Reset on SVI correctly executed |
712 |
interrupt procedure in progress |
713 |
interrupt procedure DONE |
714 |
lower limit value=
%{0}% |
715 |
upper limit value=
%{1}% |
716 |
tight shutoff value=
%{2}% |
717 |
CAM: LINEAR |
718 |
CAM: EQUAL % 50 |
719 |
CAM: EQUAL % 30 |
720 |
CAM: QUICK_OPEN |
721 |
CAM: CUSTOM |
722 |
STARTUP : LOCAL ONLY |
723 |
STARTUP : LAST MODE |
724 |
STARTUP : LOCAL |
725 |
STARTUP : REMOTE |
726 |
Ratio control : ON |
727 |
Ratio control : OFF |
728 |
Action : REVERSE |
729 |
Action : DIRECT |
730 |
LOCAL SP mode |
731 |
REMOTE SP mode |
732 |
MANUAL SP mode |