0 |
MAGNEW2W |
1 |
Yamatake Corporation |
2 |
3.1f |
3 |
In Status group1, show the status for Nonvolatile memory and CPU. If the status is ON, the device may be damaged. Restore power supply or contact Yamatake representative. |
4 |
NVM FAULT |
5 |
CPU FAULT |
6 |
HI<LO: High limit alarm value < Low limit alarm value. Set alarm value as Hi > Lo. Span over: Check the detector size. Set the span as the flow velocity becomes 10m/s or less. Pulse scale: Correct pulse scale. Set the pulse scale as the span frequency becomes between 0.0001Hz and 200Hz. If engineering unit of span is volumetric, apply the volumetric unit to the pulse scale. If engineering unit of span is mass, apply the mass unit to the pulse scale. Pulse width: Set the correct pulse width to become duty 70% or less. Or set duty 50% as pulse width. |
7 |
IN LOCAL MODE |
8 |
DO OUTPUT MODE |
9 |
PLS OUTPUT MODE |
10 |
AO OUTPUT MODE |
11 |
IN CALIB MODE |
12 |
NOT CALIBRATED |
13 |
EX OUTPUT MODE |
14 |
In Status group2, show the status of loop test and calibration. |
15 |
HI<LO ALM ERROR |
16 |
SPAN OVER ERROR |
17 |
PLS SCALE ERROR |
18 |
PLS WIDTH ERROR |
19 |
Pulse error; See status group 3 |
20 |
Flow Sensor- Hardware that measures flow rate. |
21 |
Pulse output- scaled frequency output from 0-1000 Hz, linear with input. |
22 |
Gross Total- Non-resettable totalizer. |
23 |
Net Total Value- Resettable totalizer. |
24 |
Reverse Total- Non-resettable reverse totalizer. |
25 |
write variables |
26 |
Gross Total- Non-resettable totalizer |
27 |
Net Total Value- Resettable totalizer |
28 |
Reverse Total - Non-resettable reverse totalizer |
29 |
Auto zero trim |
30 |
Auto zero trim-Calibration for zero point. |
31 |
mA |
32 |
AO |
33 |
.1f |
34 |
5.1f |
35 |
.5f |
36 |
6.5f |
37 |
Puls out unit |
38 |
m3/P |
39 |
l/P |
40 |
cm3/P |
41 |
t/P |
42 |
kg/P |
43 |
g/P |
44 |
B/P |
45 |
kG/P |
46 |
G/P |
47 |
mG/P |
48 |
IG/P |
49 |
KIG/P |
50 |
mIG/P |
51 |
lb/P |
52 |
m3/d |
53 |
m3/h |
54 |
m3/m |
55 |
m3/s |
56 |
l/d |
57 |
l/h |
58 |
l/m |
59 |
l/s |
60 |
cm3/d |
61 |
cm3/h |
62 |
cm3/m |
63 |
cm3/s |
64 |
t/d |
65 |
t/h |
66 |
t/m |
67 |
t/s |
68 |
kg/d |
69 |
kg/h |
70 |
kg/m |
71 |
kg/s |
72 |
g/d |
73 |
g/h |
74 |
g/m |
75 |
g/s |
76 |
BPD |
77 |
BPH |
78 |
BPM |
79 |
BPS |
80 |
kGPD |
81 |
kGPH |
82 |
kGPM |
83 |
kGPS |
84 |
IGPD |
85 |
IGPH |
86 |
IGPM |
87 |
IGPS |
88 |
KIGPD |
89 |
KIGPH |
90 |
KIGPM |
91 |
KIGPS |
92 |
mIGPD |
93 |
mIGPH |
94 |
mIGPM |
95 |
mIGPS |
96 |
GPD |
97 |
GPH |
98 |
GPM |
99 |
GPS |
100 |
mGPD |
101 |
mGPH |
102 |
mGPM |
103 |
mGPS |
104 |
lb/d |
105 |
lb/h |
106 |
lb/m |
107 |
lb/s |
108 |
Pulse Width |
109 |
ms |
110 |
4d |
111 |
Lo flo cutoff-Adjustable from 1 to 10% of the setting range. Below set value, output is driven to the zero flow rate signal level. Display is latched to zero. |
112 |
0 % |
113 |
1 % |
114 |
2 % |
115 |
3 % |
116 |
4 % |
117 |
5 % |
118 |
6 % |
119 |
7 % |
120 |
8 % |
121 |
9 % |
122 |
10 % |
123 |
Tube size |
124 |
Flow tube size- Nominal inside diameter of the pipe adjacent to the sensor. |
125 |
2.5 A |
126 |
5 A |
127 |
10 A |
128 |
15 A |
129 |
20 A |
130 |
25 A |
131 |
32 A |
132 |
40 A |
133 |
50 A |
134 |
65 A |
135 |
80 A |
136 |
100 A |
137 |
125 A |
138 |
150 A |
139 |
200 A |
140 |
250 A |
141 |
300 A |
142 |
350 A |
143 |
400 A |
144 |
450 A |
145 |
500 A |
146 |
600 A |
147 |
700 A |
148 |
800 A |
149 |
900 A |
150 |
1000 A |
151 |
1100 A |
152 |
Puls outp test |
153 |
Pulse Output Test Value- Scaled frequency output from 0-1000 Hz, linear with input. |
154 |
% |
155 |
Totalizer Control Code- Controls the operation of all available totalizers. |
156 |
10d |
157 |
Totalizer display-Display totalized value. |
158 |
8d |
159 |
Gravity |
160 |
Specific gravity |
161 |
.4f |
162 |
6.4f |
163 |
Disp select |
164 |
Set main display. %: Percent of range. Rate: Flow rate. Total: Totalized value. |
165 |
Rate |
166 |
Total |
167 |
Func set |
168 |
Select Pulse or DO output. Pulse: Pulse output. DO: Digital status output. |
169 |
Pulse |
170 |
ST out |
171 |
EX value |
172 |
EX value: Unique detector factor.Ex factor is stamped on the name plate. |
173 |
Coefficient |
174 |
Set coefficient. Outputs are calculated by multiplying set coefficient. Default value is 1.0000. |
175 |
Detector type |
176 |
Detector type-Detector type. Set MTG. |
177 |
MTG |
178 |
TST |
179 |
SMT |
180 |
Burn out AO |
181 |
Burn out AO-set burn out high, low or hold. |
182 |
High |
183 |
Low |
184 |
Hold |
185 |
Burn out Pls |
186 |
Burn out Pls-set burn out off or hold. |
187 |
Off |
188 |
Burn out DO |
189 |
Burn out DO-set burn out open or close. |
190 |
Close |
191 |
Open |
192 |
Drop out |
193 |
Drop out-Adjustable from 1 to 10% of the setting range. Below the set value, pulse output is cut. |
194 |
Pls width flag |
195 |
On to 50%, Off to 1ms between 1000ms |
196 |
50 % |
197 |
On |
198 |
Total restart val |
199 |
Total restart val-Restart value of totalizer. |
200 |
Total prev val |
201 |
Hi alarm |
202 |
Hi alarm-Set the upper limit value in percent of range. |
203 |
.0f |
204 |
3.0f |
205 |
Low alarm |
206 |
Low alarm-Set the lower limit value in percent of range. |
207 |
Auto spike cut |
208 |
Auto spike cut-Software signal processing against spike noise. |
209 |
Off |
210 |
On |
211 |
Moving average |
212 |
Moving average-Software signal processing. Apply moving average to output. |
213 |
Mvng av time |
214 |
s |
215 |
Mvng av time-Moving average time. |
216 |
4.1f |
217 |
Pls calib |
218 |
5d |
219 |
PLS output kind |
220 |
Up |
221 |
Down |
222 |
EX current FRQ |
223 |
Hz |
224 |
12.5 |
225 |
15.0 |
226 |
17.5 |
227 |
22.5 |
228 |
25.0 |
229 |
27.5 |
230 |
30.0 |
231 |
5.0 |
232 |
EX current CHG |
233 |
MODE 0 |
234 |
MODE 1 |
235 |
MODE 2 |
236 |
MODE 3 |
237 |
MODE 4 |
238 |
MODE 5 |
239 |
MODE 6 |
240 |
MODE 7 |
241 |
MODE 8 |
242 |
MODE 9 |
243 |
MODE A |
244 |
SI or ALL |
245 |
ALL |
246 |
SI |
247 |
Auto zero range |
248 |
0.2 m/s |
249 |
Release |
250 |
EX value range |
251 |
200-700 |
252 |
EX CURR 3.5mA |
253 |
EX Current |
254 |
mV |
255 |
7.4f |
256 |
Low flow supprs |
257 |
Pulse coef value |
258 |
COMM mode |
259 |
HART |
260 |
SFN.A |
261 |
SFN.D |
262 |
NONE |
263 |
DE word length |
264 |
4 |
265 |
6 |
266 |
Burn out SIM |
267 |
Memory address |
268 |
04X |
269 |
08X |
270 |
06X |
271 |
I.OUT AO % |
272 |
3d |
273 |
P.OUT PLS % |
274 |
EX out check |
275 |
EX0 |
276 |
EX1 |
277 |
EX2 |
278 |
EX3 |
279 |
EX4 |
280 |
STOUT check |
281 |
Done |
282 |
In progress |
283 |
Error |
284 |
Flow direction |
285 |
Forward |
286 |
Reverse |
287 |
Type SMT |
288 |
On |
289 |
Device free condition |
290 |
Free |
291 |
Write protected |
292 |
Device busy |
293 |
Check report |
294 |
Check OK |
295 |
Auto zero error |
296 |
Gain trim error |
297 |
Auto zero and Gain trim error |
298 |
ID check report |
299 |
ID not defined |
300 |
ID passd check |
301 |
Bilingal |
302 |
Low flow cut flag |
303 |
Zero comp |
304 |
Detect fluctu |
305 |
Tow few low limit data |
306 |
Too much low limit data |
307 |
Tow few High limit data |
308 |
Too much High limit data |
309 |
Low > High data |
310 |
Too few coefficent |
311 |
Too much coefficient |
312 |
Too few gravity |
313 |
Too much gravity |
314 |
Burn out (4mA-20mA) data |
315 |
Burn out (PULSE) data |
316 |
Normal contact data |
317 |
Too few averaging time |
318 |
Too much averaging time |
319 |
Device is busy |
320 |
Pulse output is not available. Set pulse in function set in Basic Setup menu. |
321 |
DO is not available. Set DO in function set in Basic setup menu. |
322 |
Too few pulse coefficient |
323 |
Too much pulse coefficient |
324 |
Too few value |
325 |
Too much value |
326 |
Device Status |
327 |
Loop test |
328 |
Calibration |
329 |
EX current trim |
330 |
Factory use |
331 |
Factory use: EX |
332 |
Factory use: FLAGS |
333 |
Memory store |
334 |
Detector config |
335 |
Conf outputs |
336 |
Analog output |
337 |
Pulse output |
338 |
Totalizer |
339 |
Digital output |
340 |
Hart output |
341 |
Noise immunity |
342 |
Device info |
343 |
Revision No. |
344 |
Reset totalizer |
345 |
Reset totalizer-Replace the totalized value with the set value of the Total restart val. |
346 |
D/A trim |
347 |
D/A trim-Calibration for analog output |
348 |
EX D/A value |
349 |
Abort EX D/A value |
350 |
Shipping save |
351 |
Shipping RCVR |
352 |
Shipping data recovery-All data are set as factory default values. |
353 |
Initial RCVR |
354 |
Gain trim |
355 |
Gain trim-Electrical trim. |
356 |
I.OUT D/A value |
357 |
Abort I.OUT D/A value |
358 |
Output check AO |
359 |
Output check of analog current |
360 |
Abort Output check AO |
361 |
Output check Pls |
362 |
Output check of pulse output |
363 |
Abort Output check Pls |
364 |
Output check EX |
365 |
Output check of excitation current |
366 |
Abort Output check EX |
367 |
Output check DO |
368 |
Output check of digital status output |
369 |
Abort Output check DO |
370 |
Pulse trim |
371 |
Pulse trim-Calibration for pulse output. |
372 |
Abort Pulse trim |
373 |
EX current trim-Calibration for excitation current. |
374 |
Abort EX current trim |
375 |
Pulse coeff |
376 |
Abort pulse coeff out |
377 |
Pulse width |
378 |
Abort pulse width |
379 |
COMM output |
380 |
Select communication protocol. |
381 |
Memory operate |
382 |
Abort memory operation |
383 |
Set DEVICE-ID |
384 |
Abort DEVICE-ID |
385 |
EX value-Unique detector factor.Ex factor is stamped on the name plate. |
386 |
NVM Write on |
387 |
FMU860 |
388 |
DT |
389 |
DVC |
390 |
FCX |
391 |
AS800 |
392 |
340T |
393 |
340C |
394 |
344 |
395 |
Siemens Micro K |
396 |
SITRANS L |
397 |
SIPAN PH |
398 |
SITRANS P |
399 |
75SMT |
400 |
UNIDELTA |
401 |
8320 |
402 |
SX5100 |
403 |
TSV175 |
404 |
DMU |
405 |
3780 |
406 |
BM70 |
407 |
8u |
408 |
Pulse Output Unit- Engineering units that the frequency andtotalizer outputs will be displayed with. |
409 |
?? |
410 |
Pulse Scaling Factor- Magnitude of process variable per pulse. |
411 |
7.5f |
412 |
.2f |
413 |
6.2f |
414 |
4.2f |
415 |
Puls outp |
416 |
Pulse Output Value- scaled frequency output from 0-1000 Hz, linear with input. |
417 |
Net Total Value- Resettable totalizer value. Counts frequency output pulses while total control is turned on. |
418 |
Gross Total Value- Non-resettable totalizer value. Counts frequency output pulses while total control is turned on. This value will be reset to 0 when the pulse scaling, line size, or units are changed. |
419 |
Reverse Total Value- Non-resettable totalizer value. Counts frequency output pulses while total control is turned on and flow is in the reverse direction. This value will be reset to 0 when the pulse scaling, line size, or units are changed. |
420 |
7d |
421 |
Coil Drive Frequency- Frequency that the coils operate at. |
422 |
6Hz |
423 |
30Hz |
424 |
gross_total_units |
425 |
Pulse output units- Engineering units that the frequency and totalizer outputs will be displayed with |
426 |
Net Total Value- Counts frequency output pulses while total control is turned on. |
427 |
Pulse Output- Scaled frequency output from 0-1000 Hz, linear with input. |
428 |
Pulse output value- scaled frequency output from 0-1000 Hz, linear with input |
429 |
Totalizer units |
430 |
Gross Total Value- Counts frequency output pulses while total control is turned on. This value will be reset to 0 when the pulse scaling, line size , or units are changed |
431 |
Reverse Total Value- Counts frequency output pulses while total control is turned on and flow is in the reverse direction. This value will be reset to 0 when the pulse scaling, line size, or units are changed |
432 |
Totalizer Variable- Counts pulses from frequency output and scales the value based on the pulse output scaling and units. |
433 |
About to enter auto zero |
434 |
The previous error was seen while trying to initiate auto zero |
435 |
Waiting for auto zero to complete. |
436 |
Device failure. Device may be stuck in Auto Zero. |
437 |
Device failure in Auto Zero. |
438 |
The previous error was seen while trying to burn eeprom |
439 |
Auto zero passed |
440 |
Sensor |
441 |
Sensor Config |
442 |
Sensor Info |
443 |
Device Info |
444 |
Revision #'s |
445 |
Totalizer will be reset |
446 |
Yes;End |
447 |
Totalizer was reset. |
448 |
Choose D/A trim |
449 |
4mA;20mA;End |
450 |
Choose DAC trim func |
451 |
Set;End |
452 |
DAC trim 4mA End |
453 |
DAC trim 20mA End |
454 |
Choose EX value |
455 |
3.5mA;4.9mA;7.0mA;11.9mA;14.0mA;End |
456 |
Set another value |
457 |
EX D/A value ABORTED! |
458 |
Shippng data save Ready? |
459 |
Saved |
460 |
End |
461 |
Device will be reboot, please connect again |
462 |
Shippng data recovery Ready? |
463 |
CAUTION: Shipping data recovery will be soon, DO NOT RETRY. Quit and re-connect 20 seconds later. |
464 |
Initial data recovery Ready? |
465 |
CAUTION: Initial data recovery will be soon, DO NOT RETRY. Quit and re-connect 20 seconds later. |
466 |
Connect MagneW calibrator |
467 |
Choose gain |
468 |
0.0m/s; 2.5m/s;10.0m/s;End |
469 |
Set 0.0m/s on MagneW calibrator, wait 120s |
470 |
Start gain 0.0m/s |
471 |
Set 2.5m/s on MagneW calibrator, wait 30s |
472 |
Start gain 2.5m/s |
473 |
Set 10.0m/s on MagneW calibrator, wait 30s |
474 |
Start gain 10.0m/s |
475 |
Waiting for gain 0.0m/s to complete. |
476 |
Waiting for gain 2.5m/s to complete. |
477 |
Waiting for gain 10.0m/s to complete. |
478 |
Gain trim complete |
479 |
Choose I.OUT Current |
480 |
4mA;20mA;End |
481 |
I.OUT D/A value ABORTED! |
482 |
Choose output check analog current |
483 |
Start;End |
484 |
Output check AO ABORTED! |
485 |
Choose output check pulse |
486 |
Output check Pls ABORTED! |
487 |
Choose output check excitation |
488 |
Select another EX |
489 |
Output check EX ABORTED! |
490 |
Choose output check DO |
491 |
Select another value |
492 |
Output check DO ABORTED! |
493 |
Setting fld dev 90Hz |
494 |
Choose Pulse trim func |
495 |
Set meter digit |
496 |
Pulse trim ABORTED! |
497 |
Choose EX current trim |
498 |
3.5mA; 4.9mA; 7.0mA;11.9mA;14.0mA;End |
499 |
Setting fld dev 3.5mA |
500 |
Setting fld dev 4.9mA |
501 |
Setting fld dev 7.0mA |
502 |
Setting fld dev 11.9mA |
503 |
Setting fld dev 14.0mA |
504 |
Choose EX trim func |
505 |
EX current trim ABORTED! |
506 |
Pulse coeff out ABORTED! |
507 |
Number to DUTY 50% |
508 |
Yes;No;End |
509 |
Input another value |
510 |
DUTY 50% to Number |
511 |
Pulse width ABORTED! |
512 |
Protocol |
513 |
HART;SFN analog;SFN digital;None;End |
514 |
HART protocol |
515 |
Yes;No |
516 |
SFN analog protocol, device will be reboot |
517 |
SFN digital protocol, device will be reboot |
518 |
None protocol, device will be reboot |
519 |
Set memory location |
520 |
Set memory data |
521 |
Set another EX value |
522 |
Out of range error |
523 |
NVM write on Ready? |
524 |
CAUTION: DO NOT RETRY, Re-connect 20 seconds after |
525 |
NVM write on |
526 |
Confirm flow rate is zero, wait 120s |
527 |
Auto zero complete |