0 |
.1f |
1 |
4.1f |
2 |
Type of measurement - Setting of vital input parameters on transmitter. |
3 |
0..391ohms |
4 |
-8..120mv |
5 |
-8..120mv - with external ref. junction |
6 |
-8..120mv - with internal ref. junction |
7 |
Sensor type - Type of currently connected sensor. Depending on the type of selected characteristic line, the measured value is influenced. |
8 |
Linear |
9 |
Free style |
10 |
Pt 100 IEC 751 |
11 |
Ni 100 DIN 43760 |
12 |
Type B Pt30Rh-Pt6Rh |
13 |
Type E NiCr-CuNi |
14 |
Type J Fe-CuNi |
15 |
Type K Ni-CrNi |
16 |
Type L Fe-CuNi |
17 |
Type N NiCrSi-NiSi |
18 |
Type R Pt13Rh-Pt |
19 |
Type S Pt10Rh-Pt |
20 |
Type T Cu-CuNi |
21 |
Type U Cu-CuNi |
22 |
Sensor connection |
23 |
Sensor connection - States the number of wires, via which the sensor is connected to the transmitter. |
24 |
Number of sensors |
25 |
Number of sensors - States the number of sensors which areconnected in series at every input. A multiple number of the built-in characteristic lines can be realised (e.g. 10*Pt100 = Pt1000). |
26 |
1/2 Sensor |
27 |
1 Sensor |
28 |
2 Sensors |
29 |
3 Sensors |
30 |
4 Sensors |
31 |
5 Sensors |
32 |
6 Sensors |
33 |
7 Sensors |
34 |
8 Sensors |
35 |
9 Sensors |
36 |
10 Sensors |
37 |
Sensor monitoring |
38 |
Sensor monitoring - With this setting the monitoring of the sensors can be limited or released.
An internal reference junction is always monitored. |
39 |
No sensor monitoring |
40 |
Break monitoring at input |
41 |
Short-circuit monitoring at input |
42 |
Break and short-circuit monitoring at input |
43 |
Break monitoring of all sensors |
44 |
Short-circuit of all sensors |
45 |
Break and short circuit monitoring of all sensors |
46 |
ext. ref. junction |
47 |
External reference junction - The value states the temperature of the external reference junction. The input is always made in °C! |
48 |
°C |
49 |
6.2f |
50 |
.2f |
51 |
Analog output - The device is only available as signal output 4..20mA. An under- or overrange exceeding this range is however possible. |
52 |
4..20mA |
53 |
Underrange value |
54 |
Underrange value - The control range is limited by the underrange value. In case of failure signal, the value is also accepted by means of underranging. |
55 |
Overrange value |
56 |
Overrange value - The control range is limited by the overrange value. In case of failure signal, the value is also accepted by means of overranging. |
57 |
mA |
58 |
Failure signalling |
59 |
Failure signalling - The setting indicates the strategy for signalling a failure. |
60 |
Overrange in case of sensor failure |
61 |
Underrange in case of sensor failure |
62 |
Default value in case of sensor failure |
63 |
Keep value in case of sensor failure |
64 |
Overrange in case of device or sensor error |
65 |
Underrange in case of device or sensor failure |
66 |
Default value in case of device or sensor failure |
67 |
Keep value in case of device or sensor failure |
68 |
Pass on value in case of device or sensor failure |
69 |
Default value |
70 |
Default value - in case of failure, the analog output is set on the programmed value if the matching error strategy was selected. |
71 |
% |
72 |
Sensor name |
73 |
Sensor name - The function permits the input of a sensor name when using user defined characteristics. |
74 |
Catalog number |
75 |
Catalog number - The function permits the changing of the catalog number after entering changes on transmitter. |
76 |
Signal input |
77 |
Signal input - The setting determines the signal input which must be balanced. |
78 |
Set point - The value states the (e.g. simulated via a reference) input signal. |
79 |
Input assignment |
80 |
Input assignment - measuring range of the transmitter at the input. |
81 |
0.. 391ohms |
82 |
-8..120mV |
83 |
Reference junction |
84 |
Reference junction - The setting determines the type of reference junction during measurements with thermocouples. Always select 'WITHOUT' for measurements witout thermocouples. |
85 |
external |
86 |
internal |
87 |
without |
88 |
No monitoring |
89 |
Break monitoring |
90 |
Short circuit(<5Ohm) |
91 |
Break/short circuit |
92 |
Failure monitoring |
93 |
Failure monitoring - The setting determines if the analog output should react to certain failure states in the transmitter. |
94 |
Sensor failure |
95 |
Sensor-/dev. failure |
96 |
Device failure |
97 |
Signalling |
98 |
Signalling - The setting determines if a failure shall be signalled via the analog output. |
99 |
Overrange |
100 |
underrange |
101 |
Hold the last value |
102 |
Version 1.00 |
103 |
English |
104 |
Language of strings |
105 |
Measured value |
106 |
Measured value - Measured value that changes magnitude with respect to time with no user intervention. |
107 |
Percent of range - Digital value that is proportional to the variable DIGITAL_VALUE with respect to the range defined by the LOWER_RANGE_VALUE and UPPER_RANGE_VALUE. The units of this variable are always in percent. |
108 |
2.2f |
109 |
Upper range value - Defines the operational endpoint from which the variables ANALOG_VALUE, PERCENT_RANGE are derived. |
110 |
Lower range value - Defines the operational endpoint from which the variables ANALOG_VALUE, PERCENT_RANGE are derived. |
111 |
Damping value - Damping time applied to both the variables DIGITAL_VALUE and ANALOG_VALUE of output 'X'. The units of this variable are always expressed in seconds. |
112 |
s |
113 |
8u |
114 |
Upper sensor limit value - Value that defines the absolute upper endpoint (largest magnitude) for the UPPER RANGE VALUE. |
115 |
Lower sensor limit value - Value that defines the absolute lower endpoint (smallest magnitude) for the LOWER RANGE VALUE. |
116 |
Minimum span value - Value that defines the smallest absolute value for the resulting figure derived from the following equation (UPPER RANGE VALUE - LOWER RANGE VALUE). |
117 |
Alarm type |
118 |
not supported |
119 |
special |
120 |
Temp. unit of the reference junction temperature - The temperature on the terminal block of the field unit is always stated in °C during measurements with internal or external reference junction. |
121 |
Reference junction temperature value - Temperature associated with the internal/external reference junction. At an internal reference junction the temperature of the connection terminals of the transmitter will be measured during measurements. |
122 |
Unit - physical unit in which the electrical value of the sensor is expressed. |
123 |
Not Used |
124 |
Sensor value - electrical value of the sensor at the input. |
125 |
Sensor value - electrical value of the sensor at the auxiliary input. |
126 |
TEU411 |
127 |
TEU411-Ex |
128 |
TEU471 |
129 |
TEU421 |
130 |
TEU211 |
131 |
TS11 |
132 |
CMOS-Interface |
133 |
RS232-Interface |
134 |
Memory status |
135 |
Memory failure - The instrument error can possibly be remedied through self-test correction.
If it continues to exist, it means the unit is defective. |
136 |
EEPROM read failure |
137 |
EEPROM failure |
138 |
Input status |
139 |
Input failures - in the measurement electronic are limit value infringements. If the unit is being operated under permissible ambient conditions, the unit is defective. |
140 |
Synchron. failure |
141 |
Zero failure |
142 |
Reference failure |
143 |
AD-Converter failure |
144 |
ADC Time Out |
145 |
Balancing/Parameter |
146 |
Balancing/Parameter - The error status of the balancing and configuration data can be read out. |
147 |
Balancing active |
148 |
Input balancing active |
149 |
Balancing failure at input |
150 |
Balancing failure at auxiliary input |
151 |
Parameter failure |
152 |
Sensor status |
153 |
Sensor status - The status of the active sensors can be read out. |
154 |
Sensor break at input |
155 |
Short circuit at input |
156 |
Input underrange |
157 |
Input overrange |
158 |
Sensor break at auxiliary input |
159 |
Short circuit at auxiliary input |
160 |
Auxiliary input underrange |
161 |
Auxiliary input overrange |
162 |
Output status |
163 |
Output status - The status of the analog output can be read out. |
164 |
Analog output underrange |
165 |
Analog output overrange |
166 |
Default value active |
167 |
Keep last valid value |
168 |
Analog output fixed |
169 |
Self-test - Transmitter self-test in progress. The analog output is frozen. Recognised failures are displayed. |
170 |
CAUTION - The measurement operation is interrupted. |
171 |
Self-test could not be carried out. |
172 |
Self-test in progress, please wait... |
173 |
Transmitter self-test blocked. |
174 |
Self-test completed. No malfunctions discovered. |
175 |
Transmitter reset |
176 |
Transmitter reset - The transmitter is restarted. Non-permanent stored data are lost. Self-test is subsequently conducted. |
177 |
CAUTION - Data not made permanent will be lost! |
178 |
CAUTION - Loop should be removed from automatic control! |
179 |
Reset could not be carried out. |
180 |
Master reset in progress, please wait... |
181 |
Transmitter reset blocked. |
182 |
Lead balancing |
183 |
Lead balancing - The resistance of the connection lines to sensor can be compensated for. This step is only necessary for measurement resistors in 2- or 3-wire circuitry. |
184 |
The lead resistance may not exceed 10 Ohm! |
185 |
Short-circuit all connection lines on sensor! |
186 |
The difference of the conductor resistance may not exceed 10Ohm max.! |
187 |
The parameter setting does not permit any lead balancing. |
188 |
Lead balancing in progress, please wait... |
189 |
Lead balancing could not be carried out! |
190 |
FAILURE - Lead balancing could not be carried out successfully! |
191 |
Check sensor connection! |
192 |
Switch damping mode on. |
193 |
Data is being made permanent, please wait... |
194 |
CAUTION - Data could not be made permanent. |
195 |
Balancing successfully carried out. Remove short-circuit on sensor. |
196 |
Data reset |
197 |
Data reset - All data, which were not made permanent are reset to their original values. This allows the old data to be restored when a parameter setting is interrupted. |
198 |
Data reset in progress, please wait... |
199 |
FAILURE - The data could not be reset! |
200 |
Sensor config. |
201 |
Input parameter - the parameters for wiring to the input (sensor type, etc.) can be fixed via the function. |
202 |
Sensor type |
203 |
Process unit |
204 |
ext. ref. junction [°C]: |
205 |
Sensor monitoring |
206 |
CAUTION - The measuring range is matched to the new permissible limits. |
207 |
Process unit |
208 |
CAUTION - Check measuring range before switching on a connected control loop again. |
209 |
Output config. |
210 |
Configuration of analog output - The setting determines the behaviour of the output in case of failure. |
211 |
Underrange value
valid range: 3.6..4mA |
212 |
Overrange value
valid range: 20..23.6mA |
213 |
Failure monitoring |
214 |
Send data |
215 |
ATTENTION - The new setting must be sent to the field unit. For this purpose Press SEND key. |
216 |
The connected loop can be put into operation again. |
217 |
write_variables |
218 |
Sensor measurement - Measurement input that receives one analog information. |
219 |
Percent of range |
220 |
Sensor 1 measurement - Measurement input 1 receives analog values. |
221 |
Sensor 2 measurement - Measurement input 2 receives analog values. |
222 |
Dynamic variables |
223 |
Ref. junction temp. |
224 |
Measured value - The calculated measured value acquired through parameterised processing. Output is made in the set process unit. |
225 |
Reference junction temp. - The value is required for correction during measurements with thermocouples. The measured value produces the temperature at the terminal block of the field unit. |
226 |
Invalid measure. type |
227 |
Invalid number of sensors |
228 |
Invalid sensor monitoring |
229 |
Temperature of reference junction too low |
230 |
Temperature of the reference junction too high |
231 |
Invalid failure strategy |
232 |
Invalid default value |
233 |
Invalid signal input |
234 |
Invalid unit |
235 |
Caution! Data update in progress. |