Name ID Label Description Type Access Class
tertiary_variable_code 0FD2 TV is Tertiary Index into Dynamic Variables Array- An index location, that indicates which Field Device dynamic variable has been mapped into the Tertiary Variable dynamic variable R/W Index 128
fourth_variable_code 0FD3 4V is Fourth Index into Dynamic Variables Array- An index location, that indicates which Field Device dynamic variable has been mapped into the Fourth Variable dynamic variable R/W Index 128
transmitter_variable_code 0FD6 Index into Dynamic Variables Array- An index that identifies a Field Device Variable that is dynamic with respect to time, with no user input R/W Index 4096
response_preambles 0FE2 Num resp preams Number of Response Preambles- Number of Preambles to be sent in the response message from the Field Device to the Host W Unsigned 128
analog_output_code 0FE4 Analog Output Number- Index into an array of Analog Outputs R/W Index 4096
analog_output_code_1 0FE8 Index into Analog Output Array- Is the first of an array of addresses, whose value is identified by the Analog Output Code R/W Index 4096
analog_output_code_2 0FE9 Index into Analog Output Array- Is the second of an array of addresses, whose value is identified by the Analog Output Code R/W Index 4096