Loading…
Name ID Label Description Type Access Class
pressure_units 138D Единица Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit. Pressure- Pressure of the process measured with respect to a reference pressure. R/W Enum 8
pressure_value 138E Давл Field Device Variable Value- Digital value that changes magnitude with respect to time with no user intervention. Pressure- Pressure of the process measured with respect to a reference pressure. R Float 10
pressure_percent_range 138F % диап Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. Pressure- Pressure of the process measured with respect to a reference pressure. R Float 34
pressure_upper_range_limit 1393 USL Upper Sensor Limit Value- Defines the maximum useable value for the Upper Range Value. Pressure- Pressure of the process measured with respect to a reference pressure. R Float 8
pressure_lower_range_limit 1394 LSL Lower Sensor Limit Value- Defines the minimum useable value for the Lower Range Value. Pressure- Pressure of the process measured with respect to a reference pressure. R Float 8
pressure_minimum_span 1390 Мин диап Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. Pressure- Pressure of the process measured with respect to a reference pressure. R Float 8
pressure_output_transfer_function 1391 Функция передачи Transfer Function- Defines the transformation function that will be applied from the Field Device Variable to the Analog Output, and Percent Range. The Transfer Function does not affect the Digital Value representation. Pressure- Pressure of the process measured with respect to a reference pressure. R/W Enum 32
pressure_upper_range_value 1396 URV Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. Pressure- Pressure of the process measured with respect to a reference pressure. R/W Float 32
pressure_lower_range_value 1397 LRV Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. Pressure- Pressure of the process measured with respect to a reference pressure. R/W Float 32
pressure_damping_value 1398 Демфирование Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. Pressure- Pressure of the process measured with respect to a reference pressure. R/W Float 8
Name ID Label Description Type Access Class