Name ID Label Description Type Access Class
KDGM_display2 4050 Display 2 P24 Display 2 - Selects the source of the value to be displayed as an alternate to that selected by P23. The local display is optional R/W Enum 256
KDGM_base_sensor_value 4055 Min sensor output P60 Minimum sensor output - Sets the value of D20 for minimum level R/W Float 8
KDGM_electronics_temperature 4033 Temperature P44 Electronics temperature - If set to a value then the temperature will be fixed, else if set to NaN the integral temperature sensor will be used. The temperature is used to correct for system temperature effects. R/W Float 8
KDGM_temperature_setup 405B Temp setup P58 Temperature setup - The process temperature assumed to apply, that was used for the initial calibration R/W Float 8
KDGM_temperature_coefficient 4034 Temp coeff P45 Temperature coefficient - The correction factor for temperature effects of the system. R/W Float 8
KDGM_process_temperature 402F Process temp P25 Process temperature - defines the temperature inside the vessel being measured. If set to NaN then the temperature measured by the sensor in the instrument head is used R/W Float 8
KDGM_sg_lower 4030 SG lower P26 SG lower - The specific gravity of the lower liquid in the system. R/W Float 32
KDGM_sg_upper 4031 SG upper P27 SG upper - The specific gravity of the upper fluid in the system. R/W Float 32
KDGM_displacer_length 4056 Displacer length P51 Displacer length - The effective length of the displacer R/W Float 2048
KDGM_displacer_cross_section_area 4057 Displacer area P52 Displacer area - The cross sectional area of the displacer R/W Float 2048