Loading…
Loading…
Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
pressurePDQ | 4E39 | Pressure PDQ | Process Data Quality- Indicates the overall process data quality of the device variable value. | R | Enum | 10 |
pressureLS | 4E3A | Pressure LS | Limit Status- Indicates whether the device variable is limited (i.e., not responding to a process). | R | Enum | 10 |
pressureStatus | 4E3B | Pressure Family Status | Device Family Status- Indicates additional status information on a device variable for a specific device family. | R | BitEnum | 10 |
pressureUpdatePeriod | 4E3C | Pressure Update Period | R | Time | 0 | |
pressure_damping | 5244 | Pressure Damping | Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. | R/W | Float | 32 |
drive_digital_units | 41AB | Drive unit | Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit | R | Enum | 32 |
drive_digital_value | 41AC | Drive Gain | Drive gain is the amount of current required to drive the vibrating element, expressed as a percentage of the maximum allowable drive gain. | R | Float | 10 |
drive_upper_sensor_limit | 41B0 | Upper Sensor Limit | Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. | R | Float | 8 |
drive_lower_sensor_limit | 41B1 | Lower Sensor Limit | Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. | R | Float | 8 |
drive_minimum_span | 41B2 | Minimum Span | Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. | R | Float | 8 |
Name | ID | Label | Description | Type | Access | Class |