Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
mass_flow_digital_units | 4007 | Mass Flow Unit | Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit. | R/W | Enum | 32 |
mass_flow_digital_value | 4009 | Flow Rate | This process variable is the rate at which mass is flowing through the sensor. | R | Float | 10 |
mass_flow_digital_cutoff | 400B | Mass Flow Cutoff | The mass flow rate below which the frequency/pulse output indicates zero flow, and below which totalizers stop counting. Cutoffs can also be configured for the mA output(s) (the AO cutoffs). An AO cutoff is active only if the process variable assigned to the output is mass flow or volume flow. | R/W | Float | 8 |
analog_upper_limit | 4D93 | Límite sup. analóg. | Analog Output Upper Endpoint Value- Defines the upper endpoint, of the respective Analog Output, for normal operating conditions | R | Float | 64 |
analog_lower_limit | 4D94 | Límite inf. analóg. | Analog Output Lower Endpoint Value- Defines the lower endpoint, of the respective Analog Output, for normal operating conditions | R | Float | 64 |
analog_damping | 4D95 | Added Damping | Analog Output Added Damping Value- Damping time constant applied the Analog Output. The units of this variable are always in seconds. | R/W | Float | 32 |
analog_units | 4013 | Anlog unit | R/W | Enum | 32 | |
mass_flow_digital_damping | 4016 | Flow Damping | Valor de amortiguación: Constante de tiempo de amortiguación que se aplica a la representación del valor digital y al valor analógico de la respectiva salida analógica. Las unidades de esta variable siempre se indican en segundos. | R/W | Float | 32 |
serial_number | 4017 | Sensor Serial Number | Sensor Serial Number - Uniquely identifies the sensor from which the field device variables are being read. | R/W | Unsigned | 2048 |
mass_flow_upper_sensor_limit | 400A | Mass Flow Upper Sensor Limit | Valor límite superior del sensor: Define el valor máximo utilizable para el valor de rango superior. | R | Float | 8 |
Name | ID | Label | Description | Type | Access | Class |