Name ID Label Description Type Access Class
mtot_digital_value 4033 Mass totl R Float 2
mtot_hzfreq 4034 Freq factr The number of cycles, in Hertz, that equal a proportional flow rate represented by the frequency/pulse output. R/W Float 512
mtot_hzrate 4035 Rate factr The flow rate that equals a set frequency if the frequency output represents mass or volume flow; or the mass or volume total that equals a set number of pulses if the frequency output represents mass or volume total. R/W Float 512
dens_digital_units 4038 Dens unit Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit R/W Enum 32
dens_digital_value 4039 Dens R Float 2
dens_analog_value 403B Dens anlog valu R/W Float 66
dens_analog_upper_limit 403C Anlog upr limit Analog Output Upper Endpoint Value- Defines the upper endpoint, of the respective Analog Output, for normal operating conditions R Float 66
dens_analog_lower_limit 403D Anlog lor limit Analog Output Lower Endpoint Value- Defines the lower endpoint, of the respective Analog Output, for normal operating conditions R Float 66
dens_additional_analog_damping 403E Added damp Analog Output Added Damping Value- Damping time constant applied the Analog Output. The units of this variable are always in seconds. R/W Float 32
dens_percent_range 403F Dens % rnge Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. R Float 34